MANUFACTURER OF HEATING CONVECTORS<br />

… more than just heat<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

2009/2010<br />

www.minib.cz<br />

www.minib.com<br />

1


table of contents<br />

TABLE OF CONTENTS<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

4 INTRODUCTION<br />

6 Cross sections of convectors<br />

8 FLOOR CONVECTORS WITHOUT FAN<br />

9 COIL - P<br />

10 COIL - P80<br />

11 COIL - PT<br />

12 COIL - PT80<br />

13 COIL - PT105<br />

14 COIL - PT4<br />

15 COIL - PT180<br />

16 COIL - PT300<br />

17 COIL - PO<br />

18 COIL - PO4<br />

19 COIL - PMW90<br />

20 COIL - PMW125<br />

21 COIL - PMW165<br />

22 COIL - PMW205<br />

23 FLOOR CONVECTORS WITH FAN<br />

24 COIL - KT<br />

26 COIL - KT110<br />

28 COIL - KO<br />

30 COIL - KTO<br />

32 COIL - KT1<br />

34 COIL - KT2<br />

36 COIL - KO2<br />

38 COIL - KT3<br />

40 COIL - KT3 105<br />

42 COIL - T50<br />

44 COIL - T60<br />

46 COIL - T80<br />

48 COIL - MT<br />

50 COIL - MO<br />

52 COIL - HC<br />

54 COIL - HC4pipe<br />

56 COIL - HCM<br />

58 COIL - HCM4pipe<br />

60 COIL - MT2<br />

62 SPECIAL<br />

64 COIL - TE<br />

65 COIL - SK<br />

66 COIL - KP<br />

2 www.minib.cz


table of contents<br />

67 COIL - LP<br />

68 COIL - DP<br />

69 WALL AND SELF-STANDING CONVECTORS<br />

WITH FAN<br />

70 COIL - NK1<br />

72 COIL - NK2<br />

74 COIL - SK1<br />

76 COIL - SK2<br />

78 COIL - SK PTG, NK PTG<br />

WITHOUT FAN<br />

79 COIL - NU1<br />

80 COIL - NU2<br />

81 COIL - SU1<br />

82 COIL - SU2<br />

83 COIL - NP1/4<br />

84 COIL - NP2/4<br />

85 COIL - SP0<br />

86 COIL - SP1/4<br />

87 COIL - SP2/4<br />

88 COIL - NW170<br />

89 COIL - NW340<br />

90 COIL - SW250<br />

91 COIL - SW420<br />

92 REGULATION<br />

92 Control A1 (wet interior)<br />

93 Control A<br />

94 Control B<br />

95 Control C<br />

96 Control D<br />

97 Control E1 (wet interior)<br />

98 Control E<br />

99 Control MT-2, TE<br />

100 PHYSICAL PROPERTIES AND CONNECTIONS<br />

102 Examples of convector connections<br />

104 ACCESSORIES<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

105 Antivibration foil<br />

106 ASSEMBLY INSTRUCTION MANUALS<br />

www.minib.cz<br />

3


introduction<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Dear customers,<br />

We thank you for your interest in our products and would like to introduce you to a number of <strong>MINIB</strong>’s innovations.<br />

1. As a result of increased requirements for cooling our innovations have especially centred on units which<br />

provide both high heat outputs and the ability to add effective cooling to the space. Units in question are the<br />

single circuit HCM fan assisted convector capable of 2kW of heat output and 0.75kW of cooling output from<br />

a 1m length of trench. This unit is suitable for inclusion in a 2-pipe heating/cooling changeover system. Also<br />

new to the range is the HCM4pipe which has separate heating and cooling circuits to suit a 4-pipe system.<br />

2. Minib has released the PTG range of fan assisted convectors using 12V DC fans but with no power supply<br />

required due to the innovative thermoelectric generators which provide power to the fans from the hot water<br />

flowing through the heating pipes.<br />

3. Many of the range of floor and wall-mounted convectors are now supplied with thermostatic valve head as<br />

standard (see catalogue for details).<br />

4. All fan-assisted convectors are now supplied with temperature sensors to prevent the fans from running when<br />

the water temperatures are low.<br />

A reminder of the standard features of <strong>MINIB</strong> units<br />

Economical Heating<br />

<strong>MINIB</strong> has been supplying energy efficient 12V DC fan motors for over three years. Compared to more commonly used<br />

AC fan motors an energy saving of around 80% is to be expected (average consumption of 12V DC fan motor is only 7W<br />

per metre of convector length). In addition, the DC motors can be readily equipped with advanced electronic controls<br />

to provide optimal comfort levels and energy efficiency. Unlike many other heat emitters, trench elements minimise<br />

the volume of water within the heat exchanger ensuring fast response and short warm-up times.<br />

Standard <strong>MINIB</strong> controls<br />

a) On/off control – Type A, B, A1<br />

b) On/off and 3 speed control – Type C<br />

c) IQ intelligent electronic control – Type E, D, E1<br />

Other new products and improvements<br />

As of 1st July 2009 the following innovations are available:<br />

- Fan assisted convectors: New models SK PTG, NK PTG. Reduced height on models KT110, KT 105.<br />

- Natural convectors: New high output models PMW90, PMW125, PMW165, PMW205, NW170, NW340,<br />

SW250, SW420. Reduced height on model PT105.<br />

- Special convectors: Increased output on models LP, KP.<br />

- As of 1st May 2009 end fitting have been supplied in 3/8” to ease installation on models HC, HC4pipe, HCM,<br />

HCM4pipe, KT-0, T50.<br />

Further features and information<br />

1/ Trenches are manufactured from food quality A2 stainless steel as standard. A4 quality (chrome-molybdenum)<br />

is used in wet environments (not designed for salt water environments).<br />

2/ The company manufactures its own, high quality, heat exchangers and fans.<br />

3/ Angle connection pieces are available on all types of floor convectors.<br />

4/ Curved convectors can be manufactured (see catalogue for details or consult company for special<br />

requirements). The use of energy efficient 12V DC motors with a consumption of only around 7W per metre<br />

length of trench (not swimming pool applications or TE electric heated unit). 80% energy saving compared with<br />

traditional AC motors.<br />

5/ Tangential fans providing even spread of air across the length of the entire convector.<br />

4 www.minib.cz


introduction<br />

6/ Convector outputs up to 6kW.<br />

7/ Special convectors for winter heating and partial summer space cooling.<br />

8/ Minimum floor convector height of 50mm (T50 unit).<br />

9/ Minimum floor convector width of 106mm (KT0 unit).<br />

10/ Minimal internal water volume allowing quick thermal response.<br />

11/ Non-standard convector lengths available in multiples of 50mm.<br />

12/ On/off and 3-speed control plus automatic step control and continuous speed control available.<br />

13/ Ex-works delivery in 2 to 15 days depending on style of unit.<br />

14/ Stainless steel flexible hose connectors allow angling of heating element for easy cleaning of the trench.<br />

15/ Fan assisted convectors should have the fan wheels greased annually to ensure low noise levels and longevity.<br />

16/ All convectors are delivered, as standard, with water connections on the RHS when looking from the window.<br />

17/ Opposite connections can be supplied if requested.<br />

<strong>MINIB</strong> are able to provide testing facilities at their factory in their accredited test chamber. Tests provide documented<br />

heating outputs in line with EN 442-2.<br />

Standard features<br />

- Stainless steel trough.<br />

- Stainless steel flexible connection hoses to facilitate piping-up and cleaning.<br />

- Shut off cock and adjustable valve.<br />

- Any type of segmented aluminium or wooden grille for standard convector lengths. Convectors with widths of<br />

380mm and above are supplied with roll-up grille. Stainless steel grilles available at additional cost. Decorative<br />

surrounds also available at extra charge.<br />

- Safe low voltage fan motors.<br />

Warranties<br />

Full warranty of 2 years is provided for <strong>MINIB</strong> convectors as of the invoice date. Warranty on the stainless steel trough<br />

and the heat exchanger is extended to 10 years. The warranties do not cover damage caused by incorrect handling,<br />

incorrect installation, use in corrosive or salt-laden environments nor does it cover normal wear and tear.<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

5


cross sections of convectors<br />

FLOOR CONVECTORS WITHOUT A FAN<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

105<br />

COIL – P<br />

COIL – P80<br />

COIL – PT<br />

COIL – PT80<br />

243 243<br />

303 303<br />

246<br />

COIL – PT105<br />

303<br />

305<br />

COIL – PT4<br />

303<br />

305<br />

243<br />

COIL – PT180<br />

303<br />

308<br />

COIL – PO4<br />

303<br />

305<br />

305<br />

COIL – PT300<br />

303<br />

308<br />

305<br />

COIL – PO<br />

303<br />

305<br />

COIL – PMW90<br />

420<br />

423<br />

COIL – PMW125 COIL – PMW165 COIL – PMW205<br />

420<br />

420<br />

420<br />

125<br />

165<br />

205<br />

423<br />

423<br />

423<br />

FLOOR CONVECTORS WITH A FAN<br />

COIL – KT<br />

COIL – KT110<br />

COIL – KO<br />

COIL – KTO COIL – KT1<br />

303<br />

303<br />

303<br />

106<br />

164<br />

248<br />

246<br />

384<br />

384<br />

COIL – T50<br />

COIL – T60<br />

COIL – T80<br />

COIL – MT<br />

COIL – MO<br />

161<br />

177<br />

50<br />

125<br />

125<br />

243<br />

243<br />

80<br />

125<br />

180<br />

125<br />

110<br />

125<br />

125<br />

305<br />

305<br />

305<br />

114 165<br />

COIL – KT2<br />

COIL – KO2<br />

COIL – KT3 COIL – KT3 105<br />

380<br />

380<br />

243<br />

243<br />

243<br />

303<br />

303<br />

305<br />

305<br />

COIL –HC COIL –HC4pipe COIL –HCM COIL –HCM4pipe<br />

243<br />

303<br />

340<br />

340<br />

125<br />

132<br />

147<br />

147<br />

245<br />

305<br />

COIL – MT2 338<br />

338<br />

380<br />

151<br />

151<br />

125<br />

105<br />

140<br />

65<br />

80<br />

125<br />

243<br />

300<br />

90<br />

125<br />

125<br />

125<br />

382<br />

6 www.minib.cz


cross sections of convectors<br />

SPECIAL<br />

COIL – TE<br />

COIL – DP<br />

176<br />

177<br />

COIL – SK PTG<br />

COIL – NP1/4<br />

156<br />

303<br />

305<br />

214<br />

COIL – SK<br />

WALL AND SELF-STANDING CONVECTORS<br />

COIL – NK 1 COIL – NK 2<br />

156<br />

156<br />

COIL – NK PTG<br />

156 156<br />

300<br />

170<br />

125<br />

COIL – NP2/4<br />

156<br />

328<br />

COIL – KP<br />

COIL – SK 1<br />

156<br />

COIL – NU 1<br />

COIL – NU 2<br />

116 116<br />

COIL – SP0 COIL – SP1/4 COIL – SP2/4<br />

156<br />

COIL – LP<br />

272 281<br />

COIL – SK 2<br />

156<br />

COIL – SU 1<br />

COIL – SU 2<br />

116 116<br />

COIL – NW170 COIL – NW340 COIL – SW250 COIL – SW420<br />

232 232<br />

232 232<br />

170<br />

240<br />

340<br />

170<br />

340<br />

170<br />

135<br />

102<br />

340<br />

156<br />

242<br />

340<br />

230<br />

230<br />

250<br />

135<br />

156<br />

230<br />

400<br />

400<br />

232<br />

400<br />

435<br />

420<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

7


<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

FLOOR CONVECTORS<br />

WITHOUT A FAN<br />

8 www.minib.cz


COIL - P<br />

without a fan<br />

COIL – P<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 lower heat output<br />

6 standard variant from P convector series<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

CROSS SECTION OF COIL-P<br />

243 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended to be combined with another heating system or to be<br />

used individually in interiors with lower heat demands. These convectors<br />

can be combined with the <strong>Coil</strong> – KT-3 with the 12V fan that has a significantly<br />

higher heat output at the same width.<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

72 62<br />

62<br />

where:<br />

m= 1,4633 temperature exponent<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other<br />

than nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

51 63<br />

243<br />

LONGITUDINAL SECTION COIL-P<br />

246<br />

101 136<br />

Ø30<br />

Ø30<br />

125<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – P<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 329 299 287<br />

80 269 240 229<br />

70 213 186 176<br />

50 113 91 82<br />

length L (mm) 1000<br />

15 20 22<br />

90 384 348 335<br />

80 314 281 268<br />

70 248 217 205<br />

50 131 106 96<br />

length L (mm) 1250<br />

15 20 22<br />

90 521 473 454<br />

80 426 381 363<br />

70 337 295 278<br />

50 178 144 130<br />

length L (mm) 1500<br />

15 20 22<br />

90 658 597 574<br />

80 538 481 459<br />

70 426 372 351<br />

50 225 181 165<br />

length L (mm) 1750<br />

15 20 22<br />

90 795 722 693<br />

80 650 581 554<br />

70 514 450 425<br />

50 272 219 199<br />

length L (mm) 2000<br />

15 20 22<br />

90 933 846 812<br />

80 763 681 650<br />

70 603 527 498<br />

50 319 257 233<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 207 1 095 1 051<br />

80 987 882 841<br />

70 780 682 644<br />

50 413 333 302<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 481 1 344 1 290<br />

80 1 211 1 082 1 032<br />

70 958 837 791<br />

50 507 408 371<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

9


COIL - P80<br />

without a fan<br />

COIL – P80<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – P80<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 245 221 212<br />

80 199 177 168<br />

70 156 135 127<br />

50 80 64 58<br />

length L (mm) 1000<br />

15 20 22<br />

90 286 258 248<br />

80 232 206 196<br />

70 181 158 149<br />

50 94 75 68<br />

length L (mm) 1250<br />

15 20 22<br />

90 388 351 336<br />

80 315 280 266<br />

70 246 214 202<br />

50 127 101 92<br />

length L (mm) 1500<br />

15 20 22<br />

90 490 443 424<br />

80 397 353 336<br />

70 311 271 255<br />

50 161 128 116<br />

length L (mm) 1750<br />

15 20 22<br />

90 592 535 513<br />

80 480 427 406<br />

70 376 327 308<br />

50 194 155 140<br />

length L (mm) 2000<br />

15 20 22<br />

90 694 627 601<br />

80 563 501 476<br />

70 441 383 361<br />

50 227 182 164<br />

length L (mm) 2500<br />

15 20 22<br />

90 898 812 778<br />

80 728 648 616<br />

70 570 496 467<br />

50 294 235 212<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 102 996 955<br />

80 894 795 757<br />

70 700 609 574<br />

50 361 288 261<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 lower heat output<br />

6 lower and dimensionally more acceptable variant<br />

of the convector COIL-P<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

243 mm<br />

80 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with lower heat<br />

demands on intensity of heating and low construction height.<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

43<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 1,4062 temperature exponent<br />

for P 80<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior<br />

[ºC]<br />

Q N<br />

CROSS SECTION OF COIL-P80<br />

LONGITUDINAL SECTION COIL-P80<br />

52<br />

51<br />

63<br />

89 46<br />

243<br />

243<br />

nominal heat transfer rate for<br />

difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the<br />

diagram for other than nominal flow<br />

values)<br />

Q heat transfer rate for other<br />

temperatures [W]<br />

30<br />

Ø30<br />

80<br />

Window<br />

10 www.minib.cz


without a fan<br />

COIL – PT<br />

COIL – PT<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 the most popular convector without a fan<br />

6 supplied with thermostatic head as standard<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL – PT is recommended to be used individually for dry<br />

interiors with lower heating demands. The convector can<br />

be combined with the COIL – KT or COIL – KO that have a<br />

higher heat output.<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

72<br />

62<br />

61<br />

m<br />

m= temperature exponent 1,3932<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than nominal flow<br />

values)<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-PT<br />

52<br />

LONGITUDINAL SECTION COIL-PT<br />

136<br />

101<br />

63<br />

Ø30<br />

303<br />

75 63<br />

305<br />

Ø30<br />

125<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – PT<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 436 396 381<br />

80 358 320 305<br />

70 283 248 234<br />

50 151 122 111<br />

length L (mm) 1000<br />

15 20 22<br />

90 509 462 444<br />

80 417 373 356<br />

70 331 289 273<br />

50 176 142 129<br />

length L (mm) 1250<br />

15 20 22<br />

90 691 628 603<br />

80 566 506 483<br />

70 449 393 371<br />

50 239 193 175<br />

length L (mm) 1500<br />

15 20 22<br />

90 873 793 761<br />

80 715 640 610<br />

70 567 496 469<br />

50 302 244 221<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 055 958 920<br />

80 864 773 737<br />

70 685 600 566<br />

50 365 294 267<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 237 1 123 1 079<br />

80 1 013 906 864<br />

70 803 703 664<br />

50 428 345 313<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 600 1 454 1 396<br />

80 1 311 1 173 1 119<br />

70 1 039 910 859<br />

50 553 446 406<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 964 1 784 1 713<br />

80 1 609 1 439 1 373<br />

70 1 275 1 116 1 055<br />

50 679 548 498<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

11


COIL - PT80<br />

without a fan<br />

COIL – PT80<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – Pt80<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 282 255 245<br />

80 230 206 196<br />

70 182 159 150<br />

50 96 77 70<br />

length L (mm) 1000<br />

15 20 22<br />

90 328 298 286<br />

80 268 240 229<br />

70 212 186 175<br />

50 112 90 82<br />

length L (mm) 1250<br />

15 20 22<br />

90 446 404 388<br />

80 364 326 310<br />

70 288 252 238<br />

50 152 123 111<br />

length L (mm) 1500<br />

15 20 22<br />

90 563 511 490<br />

80 460 411 392<br />

70 364 318 300<br />

50 192 155 141<br />

length L (mm) 1750<br />

15 20 22<br />

90 680 617 593<br />

80 556 497 474<br />

70 440 384 363<br />

50 233 187 170<br />

length L (mm) 2000<br />

15 20 22<br />

90 798 724 695<br />

80 652 583 555<br />

70 515 451 425<br />

50 273 219 199<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 032 937 899<br />

80 844 754 719<br />

70 667 583 551<br />

50 353 284 258<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 267 1 150 1 104<br />

80 1 036 925 882<br />

70 818 716 676<br />

50 433 349 316<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

45<br />

49<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 lower heat output<br />

6 construction height only 80 mm<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

m<br />

CROSS SECTION OF COIL-PT80<br />

LONGITUDINAL SECTION COIL-PT80<br />

303 mm<br />

80 mm<br />

900 to 3000 mm<br />

USAGE<br />

Designed for use in dry interiors with lower heat demands<br />

on intensity of heating and low construction height.<br />

303<br />

52 63 76 63<br />

114 35<br />

m= temperature exponent 1,4085<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than<br />

nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

303<br />

Ø30<br />

Ø30<br />

80<br />

Window<br />

12 www.minib.cz


without a fan<br />

COIL – PT105<br />

COIL – PT105<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 lower heat output<br />

6 construction height only 105 mm<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

303 mm<br />

105 mm<br />

900 to 3000 mm<br />

USAGE<br />

Designed for use in dry interiors with lower heat demands<br />

on intensity of heating and low construction height.<br />

105<br />

60<br />

45<br />

45<br />

m= temperature exponent 1,4006<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than<br />

nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-PT105<br />

50<br />

LONGITUDINAL SECTION COIL-PT105<br />

136<br />

101<br />

63<br />

Ø30<br />

303<br />

305<br />

Ø30<br />

HEAT TRANSFER RATE q [W] coil – PT105<br />

Window<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 363 330 317<br />

80 297 266 254<br />

70 235 206 195<br />

50 125 101 91<br />

length L (mm) 1000<br />

15 20 22<br />

90 424 385 370<br />

80 347 310 296<br />

70 275 240 227<br />

50 146 118 107<br />

length L (mm) 1250<br />

15 20 22<br />

90 576 523 502<br />

80 471 421 402<br />

70 373 326 308<br />

50 198 159 145<br />

length L (mm) 1500<br />

15 20 22<br />

90 727 660 634<br />

80 595 532 507<br />

70 471 412 389<br />

50 250 201 183<br />

length L (mm) 1750<br />

15 20 22<br />

90 878 798 766<br />

80 719 643 613<br />

70 569 498 470<br />

50 302 243 221<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 030 935 898<br />

80 843 753 719<br />

70 667 584 551<br />

50 354 285 259<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 333 1 210 1 162<br />

80 1 091 975 930<br />

70 863 755 713<br />

50 458 369 335<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 636 1 485 1 426<br />

80 1 339 1 197 1 141<br />

70 1 059 927 875<br />

50 562 453 412<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

13


COIL - PT4<br />

without a fan<br />

COIL – PT4<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – Pt4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 514 464 445<br />

80 416 370 352<br />

70 326 283 267<br />

50 168 134 121<br />

length L (mm) 1000<br />

15 20 22<br />

90 599 542 519<br />

80 486 432 411<br />

70 380 331 311<br />

50 196 156 141<br />

length L (mm) 1250<br />

15 20 22<br />

90 813 735 705<br />

80 659 586 558<br />

70 516 449 423<br />

50 266 212 192<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 027 929 890<br />

80 833 741 705<br />

70 652 567 534<br />

50 336 268 242<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 242 1 122 1 075<br />

80 1 006 895 852<br />

70 788 685 645<br />

50 406 324 293<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 456 1 316 1 261<br />

80 1 180 1 049 998<br />

70 924 803 756<br />

50 476 380 343<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 884 1 702 1 632<br />

80 1 527 1 358 1 292<br />

70 1 195 1 039 979<br />

50 616 491 444<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 312 2 089 2 002<br />

80 1 874 1 667 1 586<br />

70 1 467 1 276 1 201<br />

50 756 603 545<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 identical in dimension to convectors PT, PO but<br />

it has a higher output Q<br />

6 supplied with thermostatic head as standard<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL PT/4 is recommended for individual use in interiors<br />

where COIL PT does not efficiently cover the heat requirement.<br />

COIL PT/4 can be also combined with COIL KT or MT,<br />

which have a significantly higher heat output.<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

78<br />

49<br />

86<br />

46<br />

m<br />

m= temperature exponent 1,4667<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other<br />

than nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-PT/4<br />

65<br />

63<br />

303<br />

305<br />

LONGITUDINAL SECTION COIL-PT/4<br />

141<br />

110<br />

Ø30<br />

Ø30<br />

125<br />

Window<br />

14 www.minib.cz


without a fan<br />

COIL – PT180<br />

COIL – PT180<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

303 mm<br />

180 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with<br />

medium heat demand where the construction height is not<br />

a limiting factor.<br />

TEMPERATURE EQUATION<br />

115<br />

80<br />

Q=µ Q N<br />

40 79<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

CROSS SECTION OF COIL-PT180<br />

52<br />

LONGITUDINAL SECTION COIL-PT180<br />

130<br />

105<br />

63<br />

Ø30<br />

303<br />

308<br />

Ø30<br />

m= temperature exponent 1,4312<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than nominal<br />

flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

180<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – PT180<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 564 511 490<br />

80 459 410 390<br />

70 362 315 298<br />

50 189 152 138<br />

length L (mm) 1000<br />

15 20 22<br />

90 658 596 572<br />

80 536 478 455<br />

70 422 368 347<br />

50 221 177 161<br />

length L (mm) 1250<br />

15 20 22<br />

90 892 809 776<br />

80 727 648 618<br />

70 573 500 471<br />

50 300 240 218<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 127 1 021 980<br />

80 918 819 780<br />

70 723 631 595<br />

50 379 304 275<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 362 1 234 1 184<br />

80 1 110 990 943<br />

70 874 762 719<br />

50 458 367 333<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 597 1 447 1 388<br />

80 1 301 1 160 1 105<br />

70 1 024 894 843<br />

50 537 430 390<br />

length L (mm) 2500<br />

15 20 22<br />

90 2 067 1 872 1 796<br />

80 1 684 1 502 1 431<br />

70 1 326 1 157 1 091<br />

50 694 557 504<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 536 2 298 2 204<br />

80 2 067 1 843 1 756<br />

70 1 627 1 420 1 339<br />

50 852 683 619<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

15


COIL - PT300<br />

without a fan<br />

COIL – PT300<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – Pt300<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 630 572 549<br />

80 516 462 440<br />

70 409 358 338<br />

50 218 176 160<br />

length L (mm) 1000<br />

15 20 22<br />

90 735 667 641<br />

80 602 539 514<br />

70 477 418 395<br />

50 254 205 187<br />

length L (mm) 1250<br />

15 20 22<br />

90 997 906 870<br />

80 817 731 697<br />

70 648 567 536<br />

50 345 279 253<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 259 1 144 1 099<br />

80 1 032 923 881<br />

70 818 716 677<br />

50 436 352 320<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 522 1 382 1 328<br />

80 1 247 1 116 1 064<br />

70 988 866 818<br />

50 527 425 386<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 784 1 621 1 557<br />

80 1 462 1 308 1 248<br />

70 1 159 1 015 959<br />

50 618 499 453<br />

length L (mm) 2500<br />

15 20 22<br />

90 2 309 2 097 2 015<br />

80 1 892 1 693 1 615<br />

70 1 500 1 314 1 241<br />

50 800 645 586<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 833 2 574 2 472<br />

80 2 322 2 077 1 982<br />

70 1 841 1 612 1 523<br />

50 982 792 720<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

CROSS SECTION OF COIL-PT300<br />

303 mm<br />

300 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with<br />

medium heat demand where the construction height is not<br />

a limiting factor.<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

88<br />

206<br />

43<br />

43<br />

40 200<br />

m= temperature exponent 1,3909<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other<br />

than nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

56<br />

63<br />

303<br />

308<br />

300<br />

LONGITUDINAL SECTION COIL-PT300<br />

146<br />

Ø30<br />

Ø30<br />

Window<br />

16 www.minib.cz


without a fan<br />

COIL – PO<br />

COIL – PO<br />

CHARACTERISTICS<br />

6 for heating wet interiors<br />

6 the most popular convector without a fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL PO has a formed drain pan to provide drainage of stored<br />

water from the trough drain pan. COIL PO can be combined<br />

with the COIL – KT or COIL – MO, which have a significantly<br />

higher heat output These convectors are equipped with an<br />

18 mm CU outlet tube placed in the front of the convector.<br />

The convector cannot be installed to swimming pools with<br />

salt or other aggressive water.<br />

116<br />

72<br />

62<br />

61<br />

m<br />

CROSS SECTION OF COIL-PO<br />

303<br />

51 63 75 63<br />

LONGITUDINAL SECTION COIL-PO<br />

136<br />

101<br />

305<br />

Ø30<br />

m= temperature exponent 1,3932<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than nominal<br />

flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

Ø18<br />

Ø30<br />

125<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – Po<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 436 396 381<br />

80 358 320 305<br />

70 283 248 234<br />

50 151 122 111<br />

length L (mm) 1000<br />

15 20 22<br />

90 509 462 444<br />

80 417 373 356<br />

70 331 289 273<br />

50 176 142 129<br />

length L (mm) 1250<br />

15 20 22<br />

90 691 628 603<br />

80 566 506 483<br />

70 449 393 371<br />

50 239 193 175<br />

length L (mm) 1500<br />

15 20 22<br />

90 873 793 761<br />

80 715 640 610<br />

70 567 496 469<br />

50 302 244 221<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 055 958 920<br />

80 864 773 737<br />

70 685 600 566<br />

50 365 294 267<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 237 1 123 1 079<br />

80 1 013 906 864<br />

70 803 703 664<br />

50 428 345 313<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 600 1 454 1 396<br />

80 1 311 1 173 1 119<br />

70 1 039 910 859<br />

50 553 446 406<br />

length L (mm) 3000<br />

15 20 22<br />

90 1 964 1 784 1 713<br />

80 1 609 1 439 1 373<br />

70 1 275 1 116 1 055<br />

50 679 548 498<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

17


COIL - PO4<br />

without a fan<br />

COIL – PO4<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – Po4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 514 464 445<br />

80 416 370 352<br />

70 326 283 267<br />

50 168 134 121<br />

length L (mm) 1000<br />

15 20 22<br />

90 599 542 519<br />

80 486 432 411<br />

70 380 331 311<br />

50 196 156 141<br />

length L (mm) 1250<br />

15 20 22<br />

90 813 735 705<br />

80 659 586 558<br />

70 516 449 423<br />

50 266 212 192<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 027 929 890<br />

80 833 741 705<br />

70 652 567 534<br />

50 336 268 242<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 242 1 122 1 075<br />

80 1 006 895 852<br />

70 788 685 645<br />

50 406 324 293<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 456 1 316 1 261<br />

80 1 180 1 049 998<br />

70 924 803 756<br />

50 476 380 343<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 884 1 702 1 632<br />

80 1 527 1 358 1 292<br />

70 1 195 1 039 979<br />

50 616 491 444<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 312 2 089 2 002<br />

80 1 874 1 667 1 586<br />

70 1 467 1 276 1 201<br />

50 756 603 545<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CHARACTERISTICS<br />

6 for heating wet interiors<br />

6 identical in dimension to convectors PO but it has<br />

the 4 – tube heat exchanger and therefore a higher<br />

output Q<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

CROSS SECTION OF COIL-PO/4<br />

LONGITUDINAL SECTION COIL-PO/4<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL PO/4 is recommended for individual use in interiors<br />

where COIL PO does not efficiently cover the heat requirement.<br />

COIL PO/4 has a profiled drain pan to provide drainage<br />

of stored water from the trough drain pan. COIL PO/4 can<br />

be combined with COIL – KO or COIL – MO, which have a<br />

significantly higher heat output. These convectors are equipped<br />

with an 18 mm CU drain tube placed in the front of the<br />

convector. The convector cannot be installed to swimming<br />

pools with salt or other aggressive water.<br />

117<br />

78<br />

m<br />

86<br />

49<br />

46<br />

where:<br />

m= temperature exponent 1,4667<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than nominal<br />

flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

124<br />

65<br />

140<br />

110<br />

Ø30<br />

303<br />

Ø30<br />

305<br />

Ø18<br />

125<br />

Window<br />

18 www.minib.cz


without a fan<br />

COIL – PMW90<br />

COIL – PMW90<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

6 construction height only 90 mm<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

420 mm<br />

90 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with<br />

medium heat demands in places where the construction height<br />

is not a limiting factor.<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

90<br />

43<br />

43<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

CROSS SECTION OF COIL-PMW90<br />

49<br />

LONGITUDINAL SECTION COIL-PMW90<br />

130<br />

95<br />

190<br />

Ø30<br />

420<br />

423<br />

where:<br />

m= temperature exponent 1,3577<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than<br />

nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

Ø30<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – PmW90<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 521 475 456<br />

80 429 385 368<br />

70 342 301 284<br />

50 185 150 137<br />

length L (mm) 1000<br />

15 20 22<br />

90 608 554 532<br />

80 501 449 429<br />

70 399 351 332<br />

50 216 175 160<br />

length L (mm) 1250<br />

15 20 22<br />

90 826 752 723<br />

80 680 610 582<br />

70 542 476 450<br />

50 293 238 217<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 043 950 913<br />

80 859 770 736<br />

70 684 601 569<br />

50 370 301 274<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 260 1 147 1 103<br />

80 1 037 931 889<br />

70 827 727 687<br />

50 448 363 331<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 477 1 345 1 293<br />

80 1 216 1 091 1 042<br />

70 970 852 806<br />

50 525 426 388<br />

length L (mm) 2500<br />

15 20 22<br />

90 1 912 1 741 1 674<br />

80 1 574 1 412 1 349<br />

70 1 255 1 102 1 043<br />

50 679 551 502<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 346 2 136 2 054<br />

80 1 932 1 733 1 655<br />

70 1 540 1 353 1 280<br />

50 834 676 616<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

19


COIL - PMW125<br />

without a fan<br />

COIL – PMW125<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – PmW125<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 619 562 540<br />

80 508 455 434<br />

70 403 353 334<br />

50 216 174 159<br />

length L (mm) 1000<br />

15 20 22<br />

90 722 656 630<br />

80 592 530 506<br />

70 470 412 390<br />

50 252 204 185<br />

length L (mm) 1250<br />

15 20 22<br />

90 980 891 856<br />

80 804 720 687<br />

70 638 559 529<br />

50 342 276 251<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 237 1 125 1 081<br />

80 1 015 909 868<br />

70 806 707 668<br />

50 432 349 317<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 495 1 359 1 306<br />

80 1 227 1 099 1 048<br />

70 974 854 807<br />

50 522 422 383<br />

length L (mm) 2000<br />

15 20 22<br />

90 1 753 1 594 1 531<br />

80 1 439 1 288 1 229<br />

70 1 142 1 001 946<br />

50 612 494 449<br />

length L (mm) 2500<br />

15 20 22<br />

90 2 269 2 062 1 981<br />

80 1 862 1 667 1 590<br />

70 1 478 1 296 1 225<br />

50 792 640 582<br />

length L (mm) 3000<br />

15 20 22<br />

90 2 784 2 531 2 432<br />

80 2 285 2 046 1 952<br />

70 1 814 1 590 1 503<br />

50 971 785 714<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

125<br />

49<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

CROSS SECTION OF COIL-PMW125<br />

LONGITUDINAL SECTION COIL-PMW125<br />

420 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with<br />

medium heat demands in places where the construction height<br />

is not a limiting factor.<br />

m<br />

49<br />

49<br />

130<br />

95<br />

where:<br />

m= temperature exponent 1,3816<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for<br />

other than nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

190<br />

Ø30<br />

420<br />

423<br />

Ø30<br />

Window<br />

20 www.minib.cz


without a fan<br />

COIL – PMW165<br />

COIL – PMW165<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

420 mm<br />

165 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with demand<br />

on higher heat output where the construction height<br />

is not a limiting factor.<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

165<br />

92<br />

50<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

95<br />

50<br />

m<br />

where:<br />

m= temperature exponent 1,3854<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than<br />

nominal flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-PMW165<br />

LONGITUDINAL SECTION COIL-PMW165<br />

50<br />

240<br />

130<br />

95<br />

420<br />

423<br />

Ø30<br />

Ø30<br />

Window<br />

HEAT TRANSFER RATE q [W] coil – PMW165<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 823 748 718<br />

80 675 604 576<br />

70 535 469 443<br />

50 286 231 210<br />

length L (mm) 1000<br />

15 20 22<br />

90 960 873 838<br />

80 787 705 672<br />

70 625 547 517<br />

50 334 270 245<br />

length L (mm) 1250<br />

15 20 22<br />

90 1 303 1 184 1 138<br />

80 1 069 956 913<br />

70 848 743 702<br />

50 453 366 333<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 646 1 496 1 437<br />

80 1 350 1 208 1 153<br />

70 1 071 938 887<br />

50 573 462 420<br />

length L (mm) 1750<br />

15 20 22<br />

90 1 989 1 807 1 736<br />

80 1 631 1 460 1 393<br />

70 1 294 1 134 1 072<br />

50 692 559 508<br />

length L (mm) 2000<br />

15 20 22<br />

90 2 331 2 119 2 036<br />

80 1 912 1 711 1 633<br />

70 1 517 1 329 1 256<br />

50 811 655 595<br />

length L (mm) 2500<br />

15 20 22<br />

90 3 017 2 742 2 634<br />

80 2 475 2 215 2 113<br />

70 1 963 1 720 1 626<br />

50 1 050 848 771<br />

length L (mm) 3000<br />

15 20 22<br />

90 3 703 3 365 3 233<br />

80 3 037 2 718 2 594<br />

70 2 410 2 111 1 995<br />

50 1 288 1 040 946<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

21


COIL - PMW205<br />

without a fan<br />

COIL – PMW205<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

HEAT TRANSFER RATE q [W] coil – PmW205<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 961 871 836<br />

80 784 700 667<br />

70 618 540 509<br />

50 325 261 236<br />

length L (mm) 1000<br />

15 20 22<br />

90 1 121 1 016 975<br />

80 915 816 778<br />

70 721 630 594<br />

50 379 304 276<br />

length L (mm) 1250<br />

15 20 22<br />

90 1 522 1 379 1 324<br />

80 1 241 1 108 1 055<br />

70 979 854 806<br />

50 514 413 374<br />

length L (mm) 1500<br />

15 20 22<br />

90 1 922 1 742 1 672<br />

80 1 568 1 399 1 333<br />

70 1 236 1 079 1 018<br />

50 650 522 473<br />

length L (mm) 1750<br />

15 20 22<br />

90 2 323 2 105 2 020<br />

80 1 895 1 691 1 611<br />

70 1 494 1 304 1 230<br />

50 785 630 571<br />

length L (mm) 2000<br />

15 20 22<br />

90 2 723 2 468 2 369<br />

80 2 221 1 982 1 889<br />

70 1 751 1 529 1 443<br />

50 920 739 670<br />

length L (mm) 2500<br />

15 20 22<br />

90 3 524 3 194 3 065<br />

80 2 875 2 565 2 444<br />

70 2 266 1 979 1 867<br />

50 1 191 956 867<br />

length L (mm) 3000<br />

15 20 22<br />

90 4 325 3 920 3 762<br />

80 3 528 3 148 3 000<br />

70 2 781 2 428 2 291<br />

50 1 461 1 174 1 064<br />

TEMPERATURE EQUATION<br />

Q=µ Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

205<br />

115<br />

53<br />

115<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output without fan<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

CROSS SECTION OF COIL-PMW205<br />

420 mm<br />

205 mm<br />

900 to 3000 mm<br />

USAGE<br />

It is recommended for individual use in dry interiors with demand<br />

on higher heat output where the construction height<br />

is not a limiting factor.<br />

53<br />

m<br />

50<br />

where:<br />

m= temperature exponent 1,4236<br />

t W, A<br />

mean heating water temperature,<br />

mean air temperature in the interior [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

µ µ=1 (select µ according to the diagram for other than nominal<br />

flow values)<br />

Q heat transfer rate for other temperatures [W]<br />

189<br />

420<br />

423<br />

LONGITUDINAL SECTION COIL-PMW205<br />

130<br />

95<br />

Ø30<br />

Ø30<br />

Window<br />

22 www.minib.cz


FLOOR CONVECTORS<br />

WITH A FAN<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

23


COIL - KT<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

72<br />

62<br />

61<br />

52<br />

coil – KT<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CROSS SECTION OF COIL-KT<br />

CHARACTERISTICS<br />

6 the most popular convector with fan<br />

6 for heating dry interiors<br />

6 high heat output<br />

6 also heating when the fan is switched off<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

LONGITUDINAL SECTION COIL-KT<br />

136<br />

101<br />

63<br />

m<br />

where:<br />

m = temperature exponent 1,0127<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for<br />

difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

Q<br />

heat transfer rate for other<br />

temperatures [W]<br />

Window<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

The most universal <strong>MINIB</strong> convector for dry applications.<br />

The convector produces high levels of heat out-put with<br />

the 12V fan switched on but it also heats – tempers the<br />

interior when the fan is switched off. A high heat output<br />

and ability to keep low levels of natural convection when<br />

the fan is switched off provide a wide range of uses for<br />

interiors with a variety of safety and heating demands.<br />

303<br />

75 63<br />

305<br />

Ø30<br />

Ø30<br />

125<br />

24 www.minib.cz


with a fan<br />

COIL – KT<br />

HEAT TRANSFER RATE q [W] coil – kt<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 341 1 251 1 215 90 1 465 1 366 1 327 90 1 634 1 524 1 480<br />

80 1 161 1 070 1 034 80 1 268 1 169 1 129 80 1 414 1 304 1 260<br />

70 980 890 854 70 1 070 972 933 70 1 194 1 084 1 040<br />

50 620 530 495 50 677 579 540 50 755 646 602<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 565 1 459 1 417 90 1 710 1 594 1 548 90 1 906 1 778 1 726<br />

80 1 354 1 249 1 206 80 1 479 1 364 1 318 80 1 649 1 521 1 469<br />

70 1 143 1 038 996 70 1 249 1 134 1 088 70 1 392 1 264 1 213<br />

50 723 619 577 50 790 676 630 50 881 754 703<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 124 1 981 1 923 90 2 320 2 164 2 101 90 2 587 2 413 2 343<br />

80 1 837 1 694 1 637 80 2 007 1 851 1 788 80 2 238 2 064 1 994<br />

70 1 551 1 409 1 352 70 1 695 1 539 1 476 70 1 890 1 716 1 646<br />

50 982 840 783 50 1 072 917 855 50 1 196 1 023 954<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 683 2 502 2 430 90 2 931 2 733 2 654 90 3 268 3 047 2 959<br />

80 2 321 2 140 2 068 80 2 535 2 338 2 259 80 2 827 2 607 2 519<br />

70 1 960 1 779 1 707 70 2 141 1 944 1 865 70 2 387 2 167 2 080<br />

50 1 240 1 061 989 50 1 354 1 159 1 081 50 1 510 1 292 1 205<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 242 3 023 2 936 90 3 541 3 302 3 207 90 3 949 3 682 3 576<br />

80 2 805 2 586 2 499 80 3 063 2 825 2 730 80 3 416 3 150 3 044<br />

70 2 368 2 150 2 063 70 2 587 2 349 2 254 70 2 884 2 619 2 513<br />

50 1 498 1 282 1 195 50 1 637 1 400 1 306 50 1 825 1 561 1 456<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 801 3 544 3 442 90 4 152 3 872 3 760 90 4 630 4 317 4 192<br />

80 3 288 3 032 2 930 80 3 592 3 312 3 200 80 4 005 3 693 3 569<br />

70 2 776 2 521 2 419 70 3 033 2 754 2 642 70 3 382 3 071 2 946<br />

50 1 757 1 503 1 401 50 1 919 1 641 1 531 50 2 140 1 830 1 707<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 919 4 587 4 454 90 5 373 5 010 4 865 90 5 991 5 587 5 425<br />

80 4 255 3 924 3 791 80 4 648 4 286 4 141 80 5 183 4 780 4 618<br />

70 3 593 3 262 3 130 70 3 925 3 563 3 419 70 4 376 3 974 3 813<br />

50 2 273 1 945 1 814 50 2 483 2 124 1 981 50 2 769 2 369 2 209<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 6 037 5 629 5 466 90 6 594 6 149 5 971 90 7 353 6 857 6 658<br />

80 5 222 4 816 4 653 80 5 704 5 260 5 083 80 6 361 5 866 5 668<br />

70 4 409 4 004 3 842 70 4 817 4 373 4 196 70 5 371 4 877 4 679<br />

50 2 790 2 387 2 226 50 3 048 2 607 2 431 50 3 398 2 907 2 711<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

25


COIL - KT 110<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

60<br />

50<br />

50<br />

coil – KT 110<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 high heat output<br />

6 also heating when the fan is switched off<br />

6 KT110 variant with lower demands<br />

on construction height.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

303 mm<br />

110 mm<br />

900 to 3000 mm<br />

USAGE<br />

The most universal <strong>MINIB</strong> convector for dry applications.<br />

The convector produces high levels of heat out-put with<br />

the 12V fan switched on but it also heats – tempers the<br />

interior when the fan is switched off. A high heat output<br />

and ability to keep low levels of natural convection when<br />

the fan is switched off provide a wide range of uses for<br />

interiors with a variety of safety and heating demands.<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CROSS SECTION OF COIL-KT110<br />

51<br />

LONGITUDINAL SECTION COIL-KT110<br />

136<br />

101<br />

303<br />

63 75 63<br />

Ø30<br />

305<br />

m<br />

Ø30<br />

110<br />

where:<br />

m =<br />

t W<br />

, A<br />

Q N<br />

Q<br />

Window<br />

1,0543 temperature exponent pro<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50<br />

ºC [W]<br />

heat transfer rate for other<br />

temperatures [W]<br />

26 www.minib.cz


with a fan COIL – KT 110<br />

HEAT TRANSFER RATE q [W] coil – kt 110<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 114 1 036 1 005 90 1 220 1 134 1 100 90 1 374 1 278 1 239<br />

80 958 881 850 80 1 049 964 930 80 1 182 1 086 1 048<br />

70 804 727 696 70 880 796 762 70 991 896 858<br />

50 499 424 394 50 546 464 432 50 615 523 486<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 300 1 209 1 172 90 1 423 1 324 1 284 90 1 603 1 491 1 446<br />

80 1 118 1 028 991 80 1 224 1 125 1 086 80 1 379 1 267 1 223<br />

70 937 848 812 70 1 026 928 889 70 1 156 1 046 1 002<br />

50 582 495 460 50 637 542 504 50 718 610 567<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 764 1 641 1 591 90 1 932 1 796 1 742 90 2 176 2 023 1 962<br />

80 1 517 1 394 1 346 80 1 661 1 527 1 473 80 1 871 1 720 1 659<br />

70 1 272 1 151 1 102 70 1 393 1 260 1 207 70 1 569 1 419 1 359<br />

50 790 671 624 50 865 735 684 50 974 828 770<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 229 2 072 2 010 90 2 440 2 269 2 201 90 2 748 2 556 2 479<br />

80 1 917 1 761 1 700 80 2 098 1 929 1 861 80 2 364 2 172 2 096<br />

70 1 607 1 453 1 392 70 1 760 1 591 1 524 70 1 982 1 792 1 717<br />

50 998 848 789 50 1 093 929 864 50 1 231 1 046 973<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 693 2 504 2 429 90 2 949 2 742 2 659 90 3 321 3 088 2 995<br />

80 2 316 2 128 2 054 80 2 536 2 330 2 249 80 2 856 2 625 2 533<br />

70 1 942 1 756 1 682 70 2 126 1 923 1 842 70 2 395 2 166 2 075<br />

50 1 206 1 025 953 50 1 320 1 122 1 043 50 1 487 1 264 1 175<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 157 2 936 2 847 90 3 457 3 214 3 118 90 3 894 3 620 3 511<br />

80 2 715 2 495 2 408 80 2 973 2 732 2 636 80 3 348 3 077 2 969<br />

70 2 277 2 059 1 972 70 2 493 2 254 2 159 70 2 808 2 539 2 432<br />

50 1 414 1 202 1 117 50 1 548 1 316 1 223 50 1 743 1 482 1 378<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 086 3 799 3 685 90 4 474 4 160 4 035 90 5 039 4 685 4 544<br />

80 3 514 3 229 3 116 80 3 847 3 536 3 412 80 4 333 3 982 3 843<br />

70 2 946 2 665 2 552 70 3 226 2 917 2 795 70 3 633 3 286 3 148<br />

50 1 829 1 555 1 446 50 2 003 1 703 1 583 50 2 256 1 918 1 783<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 014 4 663 4 522 90 5 490 5 105 4 951 90 6 184 5 750 5 577<br />

80 4 312 3 963 3 824 80 4 721 4 339 4 187 80 5 318 4 888 4 716<br />

70 3 616 3 270 3 132 70 3 959 3 581 3 430 70 4 459 4 033 3 863<br />

50 2 245 1 908 1 775 50 2 458 2 090 1 943 50 2 769 2 354 2 188<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

27


COIL - KO<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

72<br />

62<br />

116<br />

61<br />

where:<br />

m =<br />

t W<br />

, A<br />

Q N<br />

Q<br />

coil – KO<br />

CHARACTERISTICS<br />

6 the most popular convector with the fan<br />

6 for heating wet interiors<br />

6 high heat output<br />

6 also heating when the fan is switched off<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

The universal <strong>MINIB</strong> convector for wet applications. The<br />

convector produces high levels of heat out-put with the<br />

12V fan switched on but it also heats – tempers the interior<br />

when the fan is switched off with the heat output of<br />

ca. 300W/1m. A high heat output and ability to keep low<br />

levels of natural convection when the fan is switched off<br />

provide a wide range of uses for interiors with a variety<br />

of safety and heating demands.<br />

Thanks to the voltage 12 V the all <strong>MINIB</strong> convectors are<br />

also safe for applications in wet areas. COIL-KO is supplied<br />

with an 18mm diameter pipe placed in the front of<br />

the convector to ensure water drainage from the drain<br />

pan. The convector cannot be installed to swimming<br />

pools with salt or other aggressive water.<br />

1,013 temperature exponent<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-KO<br />

51<br />

303<br />

63 75<br />

305<br />

Ø18<br />

63<br />

Ø30<br />

125<br />

LONGITUDINAL SECTION COIL-KO<br />

136<br />

101<br />

Ø30<br />

Window<br />

28 www.minib.cz


with a fan<br />

COIL – KO<br />

HEAT TRANSFER RATE q [W] coil – ko<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 341 1 251 1 215 90 1 465 1 366 1 327 90 1 634 1 524 1 480<br />

80 1 161 1 070 1 034 80 1 268 1 169 1 129 80 1 414 1 304 1 260<br />

70 980 890 854 70 1 070 972 933 70 1 194 1 084 1 040<br />

50 620 530 495 50 677 579 540 50 755 646 602<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 565 1 459 1 417 90 1 710 1 594 1 548 90 1 906 1 778 1 726<br />

80 1 354 1 249 1 206 80 1 479 1 364 1 318 80 1 649 1 521 1 469<br />

70 1 143 1 038 996 70 1 249 1 134 1 088 70 1 392 1 264 1 213<br />

50 723 619 577 50 790 676 630 50 881 754 703<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 124 1 981 1 923 90 2 320 2 164 2 101 90 2 587 2 413 2 343<br />

80 1 837 1 694 1 637 80 2 007 1 851 1 788 80 2 238 2 064 1 994<br />

70 1 551 1 409 1 352 70 1 695 1 539 1 476 70 1 890 1 716 1 646<br />

50 982 840 783 50 1 072 917 855 50 1 196 1 023 954<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 683 2 502 2 430 90 2 931 2 733 2 654 90 3 268 3 047 2 959<br />

80 2 321 2 140 2 068 80 2 535 2 338 2 259 80 2 827 2 607 2 519<br />

70 1 960 1 779 1 707 70 2 141 1 944 1 865 70 2 387 2 167 2 080<br />

50 1 240 1 061 989 50 1 354 1 159 1 081 50 1 510 1 292 1 205<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 242 3 023 2 936 90 3 541 3 302 3 207 90 3 949 3 682 3 576<br />

80 2 805 2 586 2 499 80 3 063 2 825 2 730 80 3 416 3 150 3 044<br />

70 2 368 2 150 2 063 70 2 587 2 349 2 254 70 2 884 2 619 2 513<br />

50 1 498 1 282 1 195 50 1 637 1 400 1 306 50 1 825 1 561 1 456<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 801 3 544 3 442 90 4 152 3 872 3 760 90 4 630 4 317 4 192<br />

80 3 288 3 032 2 930 80 3 592 3 312 3 200 80 4 005 3 693 3 569<br />

70 2 776 2 521 2 419 70 3 033 2 754 2 642 70 3 382 3 071 2 946<br />

50 1 757 1 503 1 401 50 1 919 1 641 1 531 50 2 140 1 830 1 707<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 919 4 587 4 454 90 5 373 5 010 4 865 90 5 991 5 587 5 425<br />

80 4 255 3 924 3 791 80 4 648 4 286 4 141 80 5 183 4 780 4 618<br />

70 3 593 3 262 3 130 70 3 925 3 563 3 419 70 4 376 3 974 3 813<br />

50 2 273 1 945 1 814 50 2 483 2 124 1 981 50 2 769 2 369 2 209<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 6 037 5 629 5 466 90 6 594 6 149 5 971 90 7 353 6 857 6 658<br />

80 5 222 4 816 4 653 80 5 704 5 260 5 083 80 6 361 5 866 5 668<br />

70 4 409 4 004 3 842 70 4 817 4 373 4 196 70 5 371 4 877 4 679<br />

50 2 790 2 387 2 226 50 3 048 2 607 2 431 50 3 398 2 907 2 711<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

29


COIL - KT0<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

coil – kt0<br />

CHARACTERISTICS<br />

6 the narrowest available <strong>MINIB</strong> floor convector, total<br />

width only 106 mm<br />

6 for heating dry interiors<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

106 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

The convector COIL – KT0 is <strong>MINIB</strong>‘s narrowest available<br />

floor convector. It is a fast-responding heater from the<br />

lower heat output series of <strong>MINIB</strong> convectors with the 12V<br />

fan. Despite the extremely narrow design, the convector<br />

can achieve heat outputs of approx. 420 W/m of length.<br />

The use is recommended in cases when the extremely<br />

narrow profile of the floor convector is required. This<br />

convector has been supplied with connection fittings and<br />

flexible hoses “3/8” for connection of the heat exchanger<br />

since 1st May 2009.<br />

info:<br />

COIL-KT0 convectors are newly supplied with levelling<br />

screws for height adjustment of the convector before<br />

concreting but only with the Al transverse grill.<br />

where:<br />

m= 1,1076 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

93<br />

47<br />

CROSS SECTION OF COIL-KT0<br />

42<br />

32<br />

106<br />

75<br />

30<br />

Window<br />

LONGITUDINAL SECTION COIL-KT0<br />

40<br />

36<br />

Ø30<br />

114<br />

Ø25<br />

125<br />

30 www.minib.cz


with a fan<br />

COIL – KT0<br />

HEAT TRANSFER RATE q [W] coil – kt0<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 469 435 421 90 560 519 502 90 723 670 649<br />

80 400 366 353 80 478 437 421 80 617 565 544<br />

70 333 299 286 70 397 357 342 70 513 462 441<br />

50 202 170 157 50 241 203 188 50 311 262 243<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 547 507 491 90 653 605 586 90 844 782 757<br />

80 467 427 412 80 557 510 491 80 720 659 635<br />

70 388 349 334 70 463 417 398 70 598 538 515<br />

50 235 198 184 50 281 237 219 50 363 306 283<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 743 688 666 90 887 821 795 90 1 145 1 061 1 027<br />

80 634 580 559 80 757 692 667 80 977 894 861<br />

70 527 474 453 70 629 566 541 70 812 731 698<br />

50 319 269 249 50 381 321 298 50 492 415 384<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 938 869 842 90 1 120 1 037 1 005 90 1 446 1 340 1 298<br />

80 801 733 706 80 956 875 842 80 1 234 1 130 1 088<br />

70 665 599 572 70 794 715 683 70 1 026 923 882<br />

50 403 340 315 50 481 406 376 50 622 524 486<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 134 1 050 1 017 90 1 353 1 254 1 214 90 1 748 1 619 1 568<br />

80 967 885 853 80 1 155 1 057 1 018 80 1 492 1 365 1 315<br />

70 804 723 691 70 960 864 825 70 1 240 1 115 1 066<br />

50 487 411 381 50 582 490 454 50 751 633 587<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 329 1 231 1 192 90 1 586 1 470 1 423 90 2 049 1 898 1 838<br />

80 1 134 1 038 1 000 80 1 354 1 239 1 193 80 1 749 1 600 1 541<br />

70 943 848 811 70 1 125 1 012 968 70 1 453 1 308 1 250<br />

50 571 482 446 50 682 575 533 50 881 743 688<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 720 1 593 1 543 90 2 053 1 902 1 842 90 2 652 2 457 2 379<br />

80 1 468 1 343 1 294 80 1 752 1 603 1 544 80 2 263 2 071 1 995<br />

70 1 220 1 098 1 049 70 1 456 1 310 1 252 70 1 881 1 692 1 618<br />

50 739 623 577 50 883 744 689 50 1 140 961 890<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 111 1 955 1 894 90 2 520 2 334 2 261 90 3 254 3 015 2 920<br />

80 1 801 1 649 1 588 80 2 150 1 968 1 895 80 2 777 2 542 2 448<br />

70 1 497 1 347 1 288 70 1 787 1 608 1 537 70 2 308 2 077 1 985<br />

50 907 765 709 50 1 083 913 846 50 1 399 1 180 1 093<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

31


COIL - KT1<br />

with a fan<br />

coil – kt1<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

91<br />

57<br />

72<br />

40<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CHARACTERISTICS<br />

6 narrow but powerful convector<br />

6 for heating dry interiors<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

164 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL-KT1 is the very narrow <strong>MINIB</strong> floor convector. It is a<br />

very fast responding heating unit that forms a part of the<br />

medium power series of <strong>MINIB</strong> convectors with the 12 V<br />

fan. The design is based on an arrangement whereby the<br />

heat exchanger is located above the fan (while maintaining<br />

a convector standard depth of 125mm). Air is both<br />

drawn and then blown across the surfaces of the heat<br />

exchanger. Due to the aesthetic design only the heat exchanger<br />

is visible from above; the fan cannot be seen.<br />

m<br />

CROSS SECTION OF COIL-KT1<br />

45<br />

164<br />

51 63<br />

Window<br />

LONGITUDINAL SECTION COIL-KT1<br />

Ø30<br />

165<br />

where:<br />

m= 1,1887 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

Ø30<br />

125<br />

32 www.minib.cz


with a fan<br />

COIL – KT1<br />

HEAT TRANSFER RATE q [W] coil – kt1<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 712 656 633 90 757 697 674 90 861 794 767<br />

80 600 546 524 80 639 581 558 80 727 661 635<br />

70 492 440 419 70 524 468 445 70 596 532 507<br />

50 288 239 221 50 306 255 235 50 348 290 267<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 830 765 739 90 883 814 786 90 1 005 926 895<br />

80 700 637 612 80 745 677 651 80 848 771 740<br />

70 574 513 488 70 611 545 520 70 695 621 591<br />

50 336 279 257 50 357 297 274 50 406 338 312<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 127 1 038 1 003 90 1 199 1 104 1 067 90 1 364 1 257 1 214<br />

80 951 864 830 80 1 011 919 883 80 1 151 1 046 1 005<br />

70 779 696 663 70 829 740 705 70 943 842 802<br />

50 455 379 349 50 484 403 372 50 551 459 423<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 423 1 311 1 267 90 1 514 1 395 1 348 90 1 723 1 587 1 533<br />

80 1 201 1 092 1 049 80 1 277 1 161 1 115 80 1 453 1 321 1 269<br />

70 984 879 837 70 1 047 935 891 70 1 192 1 064 1 014<br />

50 575 479 441 50 612 509 469 50 696 580 534<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 720 1 584 1 531 90 1 829 1 685 1 628 90 2 082 1 918 1 853<br />

80 1 451 1 319 1 267 80 1 543 1 403 1 348 80 1 756 1 597 1 534<br />

70 1 190 1 062 1 012 70 1 265 1 130 1 076 70 1 440 1 286 1 225<br />

50 695 579 533 50 739 616 567 50 841 701 645<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 016 1 858 1 795 90 2 145 1 976 1 909 90 2 441 2 249 2 172<br />

80 1 701 1 547 1 486 80 1 809 1 645 1 580 80 2 059 1 872 1 798<br />

70 1 395 1 245 1 186 70 1 483 1 325 1 262 70 1 688 1 507 1 436<br />

50 815 678 625 50 867 722 665 50 986 821 757<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 609 2 404 2 323 90 2 776 2 557 2 471 90 3 159 2 910 2 811<br />

80 2 201 2 001 1 922 80 2 342 2 129 2 045 80 2 665 2 423 2 327<br />

70 1 805 1 612 1 535 70 1 920 1 714 1 633 70 2 185 1 951 1 858<br />

50 1 055 878 809 50 1 122 934 860 50 1 277 1 063 979<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 203 2 950 2 850 90 3 407 3 138 3 032 90 3 877 3 571 3 450<br />

80 2 702 2 456 2 359 80 2 874 2 613 2 510 80 3 270 2 973 2 856<br />

70 2 215 1 978 1 884 70 2 356 2 104 2 004 70 2 681 2 394 2 281<br />

50 1 294 1 078 993 50 1 377 1 146 1 056 50 1 567 1 304 1 202<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

33


COIL - KT2<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

75<br />

coil – kt2<br />

CHARACTERISTICS<br />

6 universal convector, which also provides heat with<br />

the fan switched off<br />

6 high heat output<br />

6 it can be connected to air diffuser with an 80 mm<br />

diameter<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-KT2<br />

LONGITUDINAL SECTION COIL-KT2<br />

380 mm<br />

151 mm<br />

900 to 2500 mm<br />

USAGE<br />

COIL–KT2 is the universal convector suitable for heating<br />

of interiors with a possibility of using the air diffuser<br />

with the diameter of 80mm for inlet of conditioned air<br />

supplied to the interior. For this purpose, a part of the<br />

convector is separated by a longitudinal partition from<br />

the heat exchanger and fan sections.<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

73<br />

63<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

180<br />

240<br />

136<br />

101<br />

m<br />

380<br />

384<br />

where:<br />

m= 1.0127 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q<br />

heat transfer rate for other temperatures [W]<br />

Ø30<br />

Ø30<br />

65<br />

151<br />

Window<br />

34 www.minib.cz


with a fan<br />

COIL – KT2<br />

HEAT TRANSFER RATE q [W] coil – kt2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 341 1 251 1 215 90 1 465 1 366 1 327 90 1 634 1 524 1 480<br />

80 1 161 1 070 1 034 80 1 268 1 169 1 129 80 1 414 1 304 1 260<br />

70 980 890 854 70 1 070 972 933 70 1 194 1 084 1 040<br />

50 620 530 495 50 677 579 540 50 755 646 602<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 565 1 459 1 417 90 1 710 1 594 1 548 90 1 906 1 778 1 726<br />

80 1 354 1 249 1 206 80 1 479 1 364 1 318 80 1 649 1 521 1 469<br />

70 1 143 1 038 996 70 1 249 1 134 1 088 70 1 392 1 264 1 213<br />

50 723 619 577 50 790 676 630 50 881 754 703<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 124 1 981 1 923 90 2 320 2 164 2 101 90 2 587 2 413 2 343<br />

80 1 837 1 694 1 637 80 2 007 1 851 1 788 80 2 238 2 064 1 994<br />

70 1 551 1 409 1 352 70 1 695 1 539 1 476 70 1 890 1 716 1 646<br />

50 982 840 783 50 1 072 917 855 50 1 196 1 023 954<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 683 2 502 2 430 90 2 931 2 733 2 654 90 3 268 3 047 2 959<br />

80 2 321 2 140 2 068 80 2 535 2 338 2 259 80 2 827 2 607 2 519<br />

70 1 960 1 779 1 707 70 2 141 1 944 1 865 70 2 387 2 167 2 080<br />

50 1 240 1 061 989 50 1 354 1 159 1 081 50 1 510 1 292 1 205<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 242 3 023 2 936 90 3 541 3 302 3 207 90 3 949 3 682 3 576<br />

80 2 805 2 586 2 499 80 3 063 2 825 2 730 80 3 416 3 150 3 044<br />

70 2 368 2 150 2 063 70 2 587 2 349 2 254 70 2 884 2 619 2 513<br />

50 1 498 1 282 1 195 50 1 637 1 400 1 306 50 1 825 1 561 1 456<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 801 3 544 3 442 90 4 152 3 872 3 760 90 4 630 4 317 4 192<br />

80 3 288 3 032 2 930 80 3 592 3 312 3 200 80 4 005 3 693 3 569<br />

70 2 776 2 521 2 419 70 3 033 2 754 2 642 70 3 382 3 071 2 946<br />

50 1 757 1 503 1 401 50 1 919 1 641 1 531 50 2 140 1 830 1 707<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 919 4 587 4 454 90 5 373 5 010 4 865 90 5 991 5 587 5 425<br />

80 4 255 3 924 3 791 80 4 648 4 286 4 141 80 5 183 4 780 4 618<br />

70 3 593 3 262 3 130 70 3 925 3 563 3 419 70 4 376 3 974 3 813<br />

50 2 273 1 945 1 814 50 2 483 2 124 1 981 50 2 769 2 369 2 209<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

35


COIL - KO2<br />

with a fan<br />

coil – kO2<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 1.0127 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature, vzduchu [°C]<br />

Q N<br />

jmenovitý HEAT TRANSFER RATE pro teploty<br />

t W<br />

- t A<br />

= 50 °C [W]<br />

Q heat transfer rate for other temperatures [W]<br />

m<br />

75<br />

73<br />

63<br />

CHARACTERISTICS<br />

6 universal convector, which also provides heat<br />

with the fan switched off<br />

6 high heat output<br />

6 COIL – KO2 is designed for heating of wet interiors<br />

especially where flooding is possible (heating<br />

of swimming pools)<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-KO2<br />

243<br />

180<br />

LONGITUDINAL SECTION COIL-KO2<br />

136<br />

101<br />

52<br />

380 mm<br />

151 mm<br />

900 to 2500 mm<br />

USAGE<br />

COIL–KO2 is the universal convector suitable for use<br />

especially in wet spaces, where intensive flooding of the<br />

trough space occurs – e.g. swimming pools. The convector<br />

body is divided into 2 sections with a longitudinal partition.<br />

The narrower (empty) section of the trough is used to<br />

collect most of the water coming into the convector from<br />

the swimming pool area thus protecting the wider section<br />

of the convector with the fan and heat exchanger from excessive<br />

flooding. Both longitudinal separated sections of<br />

the convector are fitted with drain pipes for the removal of<br />

the water from the bottom of the trough. The partition wall<br />

includes fall-over openings. The wider section of the trough<br />

with the fan and the heat exchanger is used for standard<br />

heating or partial cooling of the interior. The whole body<br />

of the unit is covered with an integral grille. The convector<br />

features high heat transfer levels when the fan is switched<br />

on but it also tempers the space when the fan is switched<br />

off. With 12V operation <strong>MINIB</strong> convectors are safe for applications<br />

in wet interiors as well. The convector cannot<br />

be installed to swimming pools with salt or other aggressive<br />

water.<br />

380<br />

384<br />

Ø30<br />

Ø30<br />

65<br />

151<br />

142<br />

Window<br />

Ø18<br />

36 www.minib.cz


with a fan<br />

COIL – KO2<br />

HEAT TRANSFER RATE q [W] coil – k02<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 341 1 251 1 215 90 1 465 1 366 1 327 90 1 634 1 524 1 480<br />

80 1 161 1 070 1 034 80 1 268 1 169 1 129 80 1 414 1 304 1 260<br />

70 980 890 854 70 1 070 972 933 70 1 194 1 084 1 040<br />

50 620 530 495 50 677 579 540 50 755 646 602<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 565 1 459 1 417 90 1 710 1 594 1 548 90 1 906 1 778 1 726<br />

80 1 354 1 249 1 206 80 1 479 1 364 1 318 80 1 649 1 521 1 469<br />

70 1 143 1 038 996 70 1 249 1 134 1 088 70 1 392 1 264 1 213<br />

50 723 619 577 50 790 676 630 50 881 754 703<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 124 1 981 1 923 90 2 320 2 164 2 101 90 2 587 2 413 2 343<br />

80 1 837 1 694 1 637 80 2 007 1 851 1 788 80 2 238 2 064 1 994<br />

70 1 551 1 409 1 352 70 1 695 1 539 1 476 70 1 890 1 716 1 646<br />

50 982 840 783 50 1 072 917 855 50 1 196 1 023 954<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 683 2 502 2 430 90 2 931 2 733 2 654 90 3 268 3 047 2 959<br />

80 2 321 2 140 2 068 80 2 535 2 338 2 259 80 2 827 2 607 2 519<br />

70 1 960 1 779 1 707 70 2 141 1 944 1 865 70 2 387 2 167 2 080<br />

50 1 240 1 061 989 50 1 354 1 159 1 081 50 1 510 1 292 1 205<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 242 3 023 2 936 90 3 541 3 302 3 207 90 3 949 3 682 3 576<br />

80 2 805 2 586 2 499 80 3 063 2 825 2 730 80 3 416 3 150 3 044<br />

70 2 368 2 150 2 063 70 2 587 2 349 2 254 70 2 884 2 619 2 513<br />

50 1 498 1 282 1 195 50 1 637 1 400 1 306 50 1 825 1 561 1 456<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 801 3 544 3 442 90 4 152 3 872 3 760 90 4 630 4 317 4 192<br />

80 3 288 3 032 2 930 80 3 592 3 312 3 200 80 4 005 3 693 3 569<br />

70 2 776 2 521 2 419 70 3 033 2 754 2 642 70 3 382 3 071 2 946<br />

50 1 757 1 503 1 401 50 1 919 1 641 1 531 50 2 140 1 830 1 707<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 919 4 587 4 454 90 5 373 5 010 4 865 90 5 991 5 587 5 425<br />

80 4 255 3 924 3 791 80 4 648 4 286 4 141 80 5 183 4 780 4 618<br />

70 3 593 3 262 3 130 70 3 925 3 563 3 419 70 4 376 3 974 3 813<br />

50 2 273 1 945 1 814 50 2 483 2 124 1 981 50 2 769 2 369 2 209<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

37


COIL - KT3<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

72<br />

62<br />

coil – kt3<br />

CHARACTERISTICS<br />

6 trough identical with the COIL – P; width 243 mm<br />

6 dry environment heating<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

243 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL-KT3 is a fast reacting heating unit from the medium<br />

power series of <strong>MINIB</strong> convectors with the 12V fan. The<br />

convector COIL-KT3 is an economically advantageous alternative<br />

to the COIL-KT unit for applications where heating<br />

demands on interior heating are lower and the COIL-KT<br />

would be oversized for the space heat losses.<br />

where:<br />

m= 1,1059 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-KT3<br />

62<br />

51<br />

63<br />

243<br />

246<br />

125<br />

LONGITUDINAL SECTION COIL-KT3<br />

136<br />

101<br />

Ø30<br />

Ø30<br />

Window<br />

38 www.minib.cz


with a fan<br />

COIL – KT3<br />

HEAT TRANSFER RATE q [W] coil – kt3<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 911 844 818 90 978 906 878 90 1 137 1 054 1 020<br />

80 778 712 686 80 835 764 736 80 971 888 856<br />

70 647 582 556 70 694 625 597 70 807 726 694<br />

50 392 331 307 50 421 355 329 50 490 413 382<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 063 985 954 90 1 141 1 057 1 024 90 1 327 1 229 1 190<br />

80 908 831 800 80 974 891 859 80 1 133 1 037 998<br />

70 754 679 649 70 810 729 697 70 941 847 810<br />

50 458 386 358 50 491 414 384 50 571 482 446<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 443 1 337 1 295 90 1 549 1 435 1 389 90 1 801 1 668 1 616<br />

80 1 232 1 127 1 086 80 1 322 1 210 1 165 80 1 537 1 407 1 355<br />

70 1 024 922 881 70 1 099 989 945 70 1 278 1 150 1 099<br />

50 621 524 485 50 667 562 521 50 775 654 606<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 823 1 689 1 635 90 1 956 1 812 1 755 90 2 274 2 107 2 041<br />

80 1 556 1 424 1 372 80 1 670 1 528 1 472 80 1 941 1 777 1 712<br />

70 1 293 1 164 1 113 70 1 388 1 249 1 194 70 1 614 1 453 1 388<br />

50 785 662 613 50 842 710 658 50 979 826 765<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 202 2 041 1 976 90 2 364 2 190 2 121 90 2 748 2 546 2 466<br />

80 1 880 1 721 1 657 80 2 018 1 847 1 779 80 2 346 2 147 2 068<br />

70 1 563 1 407 1 344 70 1 677 1 509 1 443 70 1 950 1 755 1 678<br />

50 948 799 741 50 1 017 858 795 50 1 183 998 924<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 582 2 392 2 317 90 2 771 2 567 2 486 90 3 222 2 985 2 891<br />

80 2 204 2 017 1 943 80 2 365 2 165 2 085 80 2 750 2 517 2 425<br />

70 1 832 1 649 1 576 70 1 966 1 770 1 692 70 2 286 2 058 1 967<br />

50 1 112 937 868 50 1 193 1 006 932 50 1 387 1 170 1 084<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 341 3 096 2 998 90 3 586 3 323 3 218 90 4 170 3 863 3 741<br />

80 2 852 2 611 2 515 80 3 061 2 802 2 699 80 3 559 3 258 3 138<br />

70 2 371 2 134 2 040 70 2 545 2 290 2 189 70 2 959 2 663 2 545<br />

50 1 438 1 213 1 124 50 1 544 1 302 1 206 50 1 795 1 514 1 402<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 101 3 800 3 680 90 4 401 4 078 3 949 90 5 117 4 741 4 592<br />

80 3 501 3 204 3 086 80 3 757 3 439 3 312 80 4 368 3 998 3 851<br />

70 2 910 2 619 2 503 70 3 123 2 811 2 687 70 3 631 3 268 3 124<br />

50 1 765 1 489 1 379 50 1 895 1 598 1 480 50 2 203 1 858 1 721<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

39


COIL - KT3 105<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

coil – kt3 105<br />

CHARACTERISTICS<br />

6 dry environment heating<br />

6 KT3 105 is the variant with lower demands<br />

on the construction height<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

243 mm<br />

105 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL-KT3 105 is a fast reacting heating unit from the medium<br />

power series of <strong>MINIB</strong> convectors with the 12V fan. The<br />

convector COIL-KT3 is an economically advantageous alternative<br />

for applications where heating demands on interior<br />

heating are lower and the COIL-KT would be oversized for<br />

the space heat losses.<br />

where:<br />

m= 1,10542 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-KT3 105<br />

105<br />

47<br />

51<br />

63<br />

243<br />

248<br />

Window<br />

LONGITUDINAL SECTION COIL-KT3 105<br />

64<br />

54<br />

136<br />

101<br />

Ø30<br />

Ø30<br />

40 www.minib.cz


with a fan COIL – KT3 105<br />

HEAT TRANSFER RATE q [W] coil – kt3 105<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 185 1 102 1 068 90 1 346 1 251 1 214 90 1 590 1 479 1 434<br />

80 1 019 936 903 80 1 157 1 064 1 026 80 1 368 1 257 1 213<br />

70 854 773 740 70 970 878 841 70 1 147 1 037 993<br />

50 530 451 419 50 603 512 476 50 712 605 563<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 382 1 285 1 246 90 1 570 1 460 1 416 90 1 855 1 725 1 673<br />

80 1 189 1 092 1 054 80 1 350 1 241 1 197 80 1 595 1 466 1 415<br />

70 997 901 863 70 1 132 1 024 981 70 1 338 1 210 1 159<br />

50 619 526 489 50 703 598 556 50 831 706 657<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 876 1 744 1 692 90 2 131 1 981 1 922 90 2 518 2 341 2 271<br />

80 1 613 1 483 1 431 80 1 832 1 684 1 625 80 2 165 1 990 1 920<br />

70 1 353 1 223 1 172 70 1 537 1 390 1 331 70 1 816 1 642 1 573<br />

50 840 714 664 50 954 811 754 50 1 127 958 891<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 369 2 203 2 137 90 2 692 2 503 2 427 90 3 180 2 957 2 868<br />

80 2 038 1 873 1 807 80 2 315 2 127 2 053 80 2 735 2 514 2 426<br />

70 1 709 1 545 1 480 70 1 941 1 755 1 681 70 2 293 2 074 1 987<br />

50 1 061 902 839 50 1 205 1 024 953 50 1 424 1 211 1 126<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 863 2 662 2 582 90 3 252 3 024 2 933 90 3 843 3 573 3 466<br />

80 2 462 2 263 2 183 80 2 797 2 571 2 480 80 3 305 3 038 2 931<br />

70 2 065 1 867 1 789 70 2 345 2 121 2 032 70 2 771 2 506 2 401<br />

50 1 282 1 090 1 013 50 1 456 1 238 1 151 50 1 721 1 463 1 360<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 357 3 121 3 027 90 3 813 3 546 3 439 90 4 506 4 190 4 064<br />

80 2 887 2 653 2 560 80 3 279 3 014 2 908 80 3 875 3 561 3 436<br />

70 2 420 2 189 2 097 70 2 750 2 487 2 382 70 3 249 2 939 2 815<br />

50 1 503 1 278 1 188 50 1 707 1 451 1 350 50 2 018 1 715 1 595<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 344 4 039 3 918 90 4 935 4 588 4 450 90 5 831 5 422 5 259<br />

80 3 736 3 433 3 313 80 4 244 3 900 3 763 80 5 014 4 609 4 447<br />

70 3 132 2 833 2 714 70 3 558 3 218 3 083 70 4 205 3 803 3 643<br />

50 1 945 1 653 1 537 50 2 210 1 878 1 746 50 2 611 2 219 2 064<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 331 4 957 4 808 90 6 056 5 631 5 462 90 7 156 6 654 6 454<br />

80 4 585 4 214 4 066 80 5 208 4 787 4 619 80 6 154 5 656 5 457<br />

70 3 844 3 477 3 330 70 4 367 3 950 3 783 70 5 160 4 667 4 470<br />

50 2 387 2 029 1 887 50 2 712 2 305 2 143 50 3 204 2 724 2 533<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

41


COIL - T 50<br />

with a fan<br />

<strong>Coil</strong> – T50<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

35<br />

26<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CHARACTERISTICS<br />

6 lowest height <strong>MINIB</strong> convector with fan<br />

6 construction height only 50 mm<br />

6 supplied only with 12.7 mm high Al grille<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-T50<br />

32<br />

77<br />

161<br />

177<br />

161 mm<br />

50 mm<br />

900 to 3000 mm<br />

chaRakteristika<br />

A newly developed convector with minimal construction<br />

height of only 50 mm and a heat output up to 600 W/m<br />

of the convector. It can be placed into the final layer of<br />

the floor concrete or into a very low step of the floor.<br />

The convector body is made from aluminium alloy and<br />

forms one compact unit with the fan. COIL-T50 is equipped<br />

with <strong>MINIB</strong> 12 V DC specially-modified fan motors,<br />

which provided minimal consumption of approx. 7 W of<br />

electric energy per meter length of the convector. The<br />

convector grille is designed for walking on it and is made<br />

from aluminium. The convector body is manufactured to<br />

match the colour of the grille – either silver eloxal coating<br />

or light bronze.<br />

This convector has been supplied with connection fittings<br />

and flexible hoses “3/8” for connection of the heat<br />

exchanger since 1st May 2009.<br />

Info:<br />

This convector is newly supplied with levelling screws.<br />

m<br />

Ø25<br />

where:<br />

m= 0,9955 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

50<br />

Window<br />

42 www.minib.cz


with a fan COIL – T 50<br />

HEAT TRANSFER RATE q [W] coil – t 50<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 449 419 407 90 580 541 526 90 841 785 763<br />

80 390 360 348 80 503 464 449 80 729 673 651<br />

70 330 300 288 70 426 387 372 70 617 561 539<br />

50 210 180 168 50 271 233 217 50 394 338 315<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 524 489 475 90 676 631 613 90 981 916 890<br />

80 454 420 406 80 586 541 524 80 851 785 759<br />

70 385 350 336 70 497 452 434 70 720 655 629<br />

50 245 210 197 50 317 272 254 50 459 394 368<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 711 664 645 90 918 857 832 90 1 331 1 243 1 207<br />

80 617 570 551 80 796 735 710 80 1 154 1 066 1 030<br />

70 522 475 456 70 674 613 588 70 977 889 854<br />

50 333 286 267 50 430 369 344 50 623 535 499<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 898 839 815 90 1 159 1 082 1 051 90 1 681 1 570 1 525<br />

80 779 719 696 80 1 005 928 897 80 1 458 1 346 1 302<br />

70 660 600 576 70 851 774 743 70 1 235 1 123 1 078<br />

50 421 361 337 50 543 466 435 50 787 675 630<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 086 1 013 985 90 1 401 1 308 1 270 90 2 032 1 897 1 843<br />

80 941 869 840 80 1 215 1 122 1 084 80 1 762 1 627 1 573<br />

70 797 725 696 70 1 029 935 898 70 1 492 1 357 1 303<br />

50 508 436 407 50 656 563 525 50 951 816 762<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 273 1 188 1 154 90 1 642 1 533 1 490 90 2 382 2 224 2 160<br />

80 1 104 1 019 985 80 1 424 1 315 1 271 80 2 066 1 907 1 844<br />

70 935 850 816 70 1 206 1 097 1 053 70 1 749 1 591 1 527<br />

50 596 511 477 50 769 660 616 50 1 115 957 893<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 647 1 538 1 494 90 2 125 1 984 1 928 90 3 082 2 878 2 796<br />

80 1 428 1 319 1 275 80 1 843 1 702 1 645 80 2 673 2 468 2 386<br />

70 1 209 1 100 1 056 70 1 561 1 419 1 363 70 2 263 2 059 1 977<br />

50 771 661 618 50 995 854 797 50 1 443 1 238 1 156<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 021 1 887 1 834 90 2 608 2 435 2 366 90 3 783 3 532 3 431<br />

80 1 753 1 619 1 565 80 2 262 2 089 2 019 80 3 281 3 029 2 929<br />

70 1 484 1 350 1 296 70 1 915 1 742 1 673 70 2 778 2 526 2 426<br />

50 946 812 758 50 1 221 1 047 978 50 1 771 1 519 1 418<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

43


COIL - T 60<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

COIL –T60<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 very low <strong>MINIB</strong> convector(only 65 mm in the floor)<br />

6 COIL – T60 is supplied only with the 16.5 mm<br />

high aluminium grille<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

243 mm<br />

65 mm<br />

900 to 3000 mm<br />

USAGE<br />

Designed for individual use in dry interiors with higher heating<br />

demands on intensity of heating and low construction<br />

height requirements (up to 65 mm) when the deeper<br />

COIL-KT or COIL-KT3 units cannot be used.<br />

where:<br />

m= 1,0966 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q<br />

heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-T60<br />

65<br />

39<br />

LONGITUDINAL SECTION COIL-T60<br />

44<br />

51<br />

89<br />

63<br />

243<br />

243<br />

46<br />

Ø30<br />

Ø30<br />

Window<br />

44 www.minib.cz


with a fan COIL – T 60<br />

HEAT TRANSFER RATE q [W] coil – t 60<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 852 790 765 90 1 026 952 922 90 1 323 1 226 1 188<br />

80 728 667 643 80 877 804 774 80 1 131 1 036 998<br />

70 606 546 522 70 730 658 629 70 941 848 811<br />

50 369 312 289 50 445 376 348 50 573 484 449<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 994 921 892 90 1 198 1 110 1 076 90 1 543 1 431 1 386<br />

80 849 778 750 80 1 024 938 903 80 1 319 1 208 1 164<br />

70 707 637 609 70 852 768 734 70 1 098 989 946<br />

50 431 364 337 50 519 438 406 50 669 565 524<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 349 1 250 1 211 90 1 625 1 507 1 460 90 2 094 1 942 1 881<br />

80 1 153 1 056 1 017 80 1 389 1 272 1 226 80 1 790 1 640 1 580<br />

70 960 865 827 70 1 157 1 042 996 70 1 491 1 343 1 284<br />

50 585 494 458 50 705 595 552 50 908 767 711<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 703 1 579 1 530 90 2 053 1 903 1 844 90 2 646 2 453 2 376<br />

80 1 456 1 334 1 285 80 1 755 1 607 1 549 80 2 261 2 071 1 996<br />

70 1 212 1 092 1 044 70 1 461 1 316 1 258 70 1 883 1 696 1 622<br />

50 739 624 578 50 890 752 697 50 1 147 969 898<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 058 1 908 1 849 90 2 481 2 300 2 228 90 3 197 2 964 2 871<br />

80 1 759 1 612 1 553 80 2 120 1 942 1 871 80 2 733 2 503 2 412<br />

70 1 465 1 320 1 262 70 1 765 1 590 1 521 70 2 275 2 049 1 960<br />

50 892 754 699 50 1 075 908 842 50 1 386 1 170 1 085<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 413 2 237 2 167 90 2 908 2 696 2 612 90 3 748 3 475 3 366<br />

80 2 063 1 889 1 820 80 2 486 2 277 2 194 80 3 204 2 934 2 827<br />

70 1 717 1 547 1 479 70 2 070 1 864 1 783 70 2 667 2 403 2 297<br />

50 1 046 883 819 50 1 261 1 065 987 50 1 625 1 372 1 272<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 123 2 895 2 805 90 3 764 3 489 3 380 90 4 850 4 497 4 356<br />

80 2 669 2 445 2 356 80 3 217 2 947 2 839 80 4 146 3 798 3 659<br />

70 2 223 2 002 1 914 70 2 678 2 413 2 307 70 3 452 3 109 2 973<br />

50 1 354 1 143 1 060 50 1 632 1 378 1 277 50 2 103 1 776 1 646<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 833 3 553 3 442 90 4 619 4 282 4 148 90 5 953 5 519 5 346<br />

80 3 276 3 001 2 891 80 3 948 3 616 3 484 80 5 088 4 661 4 491<br />

70 2 728 2 457 2 349 70 3 287 2 961 2 831 70 4 236 3 816 3 649<br />

50 1 662 1 403 1 301 50 2 002 1 691 1 568 50 2 581 2 179 2 021<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

45


COIL - T 80<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

m<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

43<br />

43<br />

COIL –T80<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 very low <strong>MINIB</strong> convector (only 80 mm in the floor)<br />

6 supplied with any aluminium or wooden grille<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

243 mm<br />

80 mm<br />

900 to 3000 mm<br />

USAGE<br />

Designed for individual use in dry interiors with higher heating<br />

demands on intensity of heating and low construction<br />

height requirements (up to 80 mm) when the deeper<br />

COIL-KT or COIL-KT3 units cannot be used.<br />

where:<br />

m= 1,0966 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q<br />

heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-T80<br />

LONGITUDINAL SECTION COIL-T80<br />

89<br />

52<br />

63<br />

46<br />

243<br />

243<br />

Ø30<br />

Ø30<br />

80<br />

Window<br />

46 www.minib.cz


with a fan COIL – T 80<br />

HEAT TRANSFER RATE q [W] coil – t 80<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 017 943 914 90 1 225 1 136 1 101 90 1 580 1 465 1 419<br />

80 870 797 767 80 1 047 959 924 80 1 350 1 237 1 192<br />

70 724 652 624 70 872 786 751 70 1 124 1 013 968<br />

50 441 372 345 50 531 449 416 50 685 578 536<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 187 1 100 1 066 90 1 430 1 325 1 284 90 1 843 1 709 1 655<br />

80 1 015 929 895 80 1 222 1 119 1 078 80 1 576 1 443 1 390<br />

70 845 761 728 70 1 017 916 876 70 1 312 1 182 1 130<br />

50 515 435 403 50 620 523 485 50 799 675 626<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 611 1 493 1 447 90 1 940 1 799 1 743 90 2 502 2 319 2 247<br />

80 1 377 1 261 1 215 80 1 658 1 519 1 464 80 2 138 1 959 1 887<br />

70 1 146 1 033 987 70 1 381 1 244 1 189 70 1 780 1 604 1 533<br />

50 698 590 547 50 841 710 659 50 1 084 916 849<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 035 1 887 1 827 90 2 451 2 272 2 201 90 3 160 2 930 2 838<br />

80 1 739 1 593 1 535 80 2 095 1 919 1 849 80 2 701 2 474 2 384<br />

70 1 448 1 304 1 247 70 1 744 1 571 1 502 70 2 249 2 026 1 937<br />

50 882 745 691 50 1 063 897 832 50 1 370 1 157 1 073<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 459 2 280 2 208 90 2 961 2 746 2 660 90 3 818 3 540 3 429<br />

80 2 102 1 925 1 855 80 2 531 2 319 2 234 80 3 264 2 989 2 880<br />

70 1 750 1 576 1 507 70 2 108 1 898 1 815 70 2 717 2 448 2 340<br />

50 1 066 900 835 50 1 284 1 084 1 005 50 1 655 1 398 1 296<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 883 2 673 2 589 90 3 472 3 219 3 118 90 4 476 4 150 4 020<br />

80 2 464 2 257 2 175 80 2 968 2 718 2 619 80 3 826 3 505 3 377<br />

70 2 051 1 848 1 767 70 2 471 2 226 2 128 70 3 186 2 870 2 744<br />

50 1 250 1 055 978 50 1 505 1 271 1 178 50 1 941 1 639 1 519<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 730 3 459 3 350 90 4 493 4 166 4 035 90 5 793 5 371 5 203<br />

80 3 189 2 921 2 814 80 3 841 3 518 3 389 80 4 952 4 536 4 370<br />

70 2 655 2 391 2 287 70 3 198 2 880 2 754 70 4 123 3 714 3 551<br />

50 1 617 1 366 1 266 50 1 948 1 645 1 525 50 2 511 2 121 1 966<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 578 4 245 4 112 90 5 514 5 113 4 953 90 7 110 6 592 6 385<br />

80 3 913 3 584 3 454 80 4 713 4 317 4 160 80 6 077 5 566 5 363<br />

70 3 258 2 935 2 806 70 3 924 3 535 3 380 70 5 060 4 558 4 358<br />

50 1 985 1 676 1 554 50 2 391 2 019 1 872 50 3 082 2 603 2 413<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

47


COIL - MT<br />

with a fan<br />

coil – mt<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

78<br />

49<br />

46<br />

40<br />

m<br />

CHARACTERISTICS<br />

6 very powerful <strong>MINIB</strong> floor convector<br />

6 COIL – MT: for heating dry interiors<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

Convector COIL – MT is a fast reacting heating unit suitable<br />

for heating of interiors with high demands on intensity<br />

of heating.<br />

where:<br />

m= 1,0435 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-MT<br />

65 63<br />

303<br />

305<br />

125<br />

LONGITUDINAL SECTION COIL-MT<br />

140<br />

110<br />

Ø30<br />

Ø30<br />

Window<br />

48 www.minib.cz


with a fan<br />

COIL – MT<br />

HEAT TRANSFER RATE q [W] coil – mt<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 740 1 620 1 571 90 1 824 1 698 1 647 90 1 995 1 856 1 801<br />

80 1 499 1 379 1 331 80 1 571 1 445 1 395 80 1 718 1 580 1 525<br />

70 1 259 1 140 1 092 70 1 320 1 195 1 145 70 1 443 1 307 1 252<br />

50 786 669 622 50 824 701 653 50 900 767 713<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 030 1 889 1 833 90 2 128 1 981 1 922 90 2 327 2 165 2 101<br />

80 1 749 1 609 1 553 80 1 833 1 686 1 628 80 2 004 1 844 1 780<br />

70 1 469 1 330 1 275 70 1 540 1 394 1 336 70 1 684 1 524 1 461<br />

50 917 780 726 50 961 818 761 50 1 051 894 832<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 756 2 564 2 488 90 2 889 2 688 2 608 90 3 158 2 939 2 851<br />

80 2 373 2 183 2 107 80 2 488 2 289 2 209 80 2 720 2 502 2 415<br />

70 1 994 1 805 1 730 70 2 090 1 892 1 813 70 2 285 2 069 1 982<br />

50 1 244 1 059 986 50 1 304 1 110 1 033 50 1 426 1 214 1 130<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 481 3 239 3 143 90 3 649 3 395 3 294 90 3 989 3 712 3 602<br />

80 2 998 2 758 2 662 80 3 143 2 891 2 790 80 3 436 3 161 3 051<br />

70 2 518 2 280 2 185 70 2 640 2 390 2 290 70 2 886 2 613 2 504<br />

50 1 571 1 338 1 245 50 1 647 1 402 1 305 50 1 801 1 533 1 427<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 206 3 914 3 797 90 4 409 4 103 3 980 90 4 820 4 485 4 352<br />

80 3 623 3 332 3 216 80 3 797 3 493 3 372 80 4 152 3 819 3 686<br />

70 3 043 2 755 2 640 70 3 190 2 888 2 767 70 3 488 3 157 3 026<br />

50 1 899 1 617 1 504 50 1 990 1 695 1 577 50 2 176 1 853 1 724<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 931 4 589 4 452 90 5 169 4 810 4 667 90 5 651 5 259 5 102<br />

80 4 247 3 907 3 771 80 4 452 4 095 3 953 80 4 868 4 477 4 322<br />

70 3 568 3 230 3 095 70 3 740 3 386 3 245 70 4 089 3 702 3 547<br />

50 2 226 1 895 1 764 50 2 334 1 987 1 849 50 2 551 2 172 2 021<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 6 382 5 938 5 761 90 6 689 6 225 6 039 90 7 314 6 806 6 603<br />

80 5 496 5 056 4 880 80 5 762 5 300 5 116 80 6 299 5 794 5 593<br />

70 4 617 4 180 4 006 70 4 840 4 382 4 199 70 5 291 4 791 4 591<br />

50 2 881 2 453 2 282 50 3 020 2 571 2 393 50 3 302 2 811 2 616<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 7 832 7 288 7 071 90 8 210 7 640 7 412 90 8 976 8 352 8 103<br />

80 6 746 6 205 5 989 80 7 071 6 504 6 278 80 7 731 7 111 6 864<br />

70 5 666 5 130 4 916 70 5 940 5 378 5 153 70 6 494 5 879 5 634<br />

50 3 536 3 010 2 801 50 3 706 3 156 2 936 50 4 052 3 450 3 210<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

49


COIL - MO<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 1,0435 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

m<br />

117<br />

86<br />

46<br />

78<br />

49<br />

coil – mO<br />

CHARACTERISTICS<br />

6 very powerful <strong>MINIB</strong> floor convector<br />

6 heating of any interior (in winter) and interior<br />

cooling (in summer) with the possibility of moisture<br />

condensation in the trough<br />

6 heating of swimming pools<br />

6 implied condensate outlet<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

303 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

Convector COIL – MO is used as a fast reacting heating<br />

unit suitable for heating of interiors with high heat loads.<br />

Convector COIL – MO is also suitable for use in wet spaces,<br />

where pooling of water in the trench can occur. The<br />

convector has a specially profiled base enabling draining<br />

of collected water (eventually condensed water) through<br />

the outlet pipe at the bottom of the trough. The fan operates<br />

at the safe voltage of 12V. If there is a source of<br />

chilled water (6/12 ºC) available the COIL-MO may also be<br />

used for cooling of the interior The convector will cause<br />

formation of cool air curtain by the window where it prevents<br />

room heating through convection from heated window<br />

surfaces. The cooling effect is most evident especially<br />

in the vicinity of windows so that the interior air is not<br />

fully cooled as in case of when using standard air conditioning.<br />

The convector cannot be installed to swimming<br />

pools with salt or other aggressive water.<br />

CROSS SECTION OF COIL-MO<br />

124<br />

65<br />

140<br />

110<br />

303<br />

Ø30<br />

305<br />

Ø30<br />

Ø18<br />

125<br />

LONGITUDINAL SECTION COIL-MO<br />

Window<br />

50 www.minib.cz


with a fan<br />

COIL – MO<br />

HEAT TRANSFER RATE q [W] coil – mo<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 740 1 620 1 571 90 1 824 1 698 1 647 90 1 995 1 856 1 801<br />

80 1 499 1 379 1 331 80 1 571 1 445 1 395 80 1 718 1 580 1 525<br />

70 1 259 1 140 1 092 70 1 320 1 195 1 145 70 1 443 1 307 1 252<br />

50 786 669 622 50 824 701 653 50 900 767 713<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 030 1 889 1 833 90 2 128 1 981 1 922 90 2 327 2 165 2 101<br />

80 1 749 1 609 1 553 80 1 833 1 686 1 628 80 2 004 1 844 1 780<br />

70 1 469 1 330 1 275 70 1 540 1 394 1 336 70 1 684 1 524 1 461<br />

50 917 780 726 50 961 818 761 50 1 051 894 832<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 756 2 564 2 488 90 2 889 2 688 2 608 90 3 158 2 939 2 851<br />

80 2 373 2 183 2 107 80 2 488 2 289 2 209 80 2 720 2 502 2 415<br />

70 1 994 1 805 1 730 70 2 090 1 892 1 813 70 2 285 2 069 1 982<br />

50 1 244 1 059 986 50 1 304 1 110 1 033 50 1 426 1 214 1 130<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 481 3 239 3 143 90 3 649 3 395 3 294 90 3 989 3 712 3 602<br />

80 2 998 2 758 2 662 80 3 143 2 891 2 790 80 3 436 3 161 3 051<br />

70 2 518 2 280 2 185 70 2 640 2 390 2 290 70 2 886 2 613 2 504<br />

50 1 571 1 338 1 245 50 1 647 1 402 1 305 50 1 801 1 533 1 427<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 206 3 914 3 797 90 4 409 4 103 3 980 90 4 820 4 485 4 352<br />

80 3 623 3 332 3 216 80 3 797 3 493 3 372 80 4 152 3 819 3 686<br />

70 3 043 2 755 2 640 70 3 190 2 888 2 767 70 3 488 3 157 3 026<br />

50 1 899 1 617 1 504 50 1 990 1 695 1 577 50 2 176 1 853 1 724<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 931 4 589 4 452 90 5 169 4 810 4 667 90 5 651 5 259 5 102<br />

80 4 247 3 907 3 771 80 4 452 4 095 3 953 80 4 868 4 477 4 322<br />

70 3 568 3 230 3 095 70 3 740 3 386 3 245 70 4 089 3 702 3 547<br />

50 2 226 1 895 1 764 50 2 334 1 987 1 849 50 2 551 2 172 2 021<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 6 382 5 938 5 761 90 6 689 6 225 6 039 90 7 314 6 806 6 603<br />

80 5 496 5 056 4 880 80 5 762 5 300 5 116 80 6 299 5 794 5 593<br />

70 4 617 4 180 4 006 70 4 840 4 382 4 199 70 5 291 4 791 4 591<br />

50 2 881 2 453 2 282 50 3 020 2 571 2 393 50 3 302 2 811 2 616<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 7 832 7 288 7 071 90 8 210 7 640 7 412 90 8 976 8 352 8 103<br />

80 6 746 6 205 5 989 80 7 071 6 504 6 278 80 7 731 7 111 6 864<br />

70 5 666 5 130 4 916 70 5 940 5 378 5 153 70 6 494 5 879 5 634<br />

50 3 536 3 010 2 801 50 3 706 3 156 2 936 50 4 052 3 450 3 210<br />

Cooling effect of the convector COIL - MO:<br />

For water flow temperatures of 6/12.C take<br />

an estimated cooling output of 200W/per linear metre at speed 2<br />

and approximately 350W per linear metre at speed 3.<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

51


COIL - HC<br />

with a fan<br />

coil – HC<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

125<br />

118<br />

59<br />

48<br />

CROSS SECTION OF COIL-HC<br />

89<br />

66<br />

58<br />

Ø18<br />

243<br />

245<br />

Ø30<br />

LONGITUDINAL SECTION COIL-HC<br />

72<br />

56<br />

112 152<br />

Ø30<br />

Window<br />

CHARACTERISTICS<br />

6 very effective convector for heating and cooling<br />

6 2-pipe connection<br />

6 air is blown tangentially into the interior<br />

6 cooling output approximately 1000 W for<br />

the 2-meter long convector<br />

6 implied condensate outlet<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

243 mm<br />

125 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL – HC is the <strong>MINIB</strong> floor convector specially designed<br />

for both heating and cooling of the space. The convector<br />

has the 2-pipe connection and common cooling<br />

and heating circuit. The air is tangentially blown across<br />

the floor of the room to a distance of 3 to 4 m – so that<br />

in summer there is a lightly flowing cool air effect in locations<br />

remote from the windows.<br />

This convector has been supplied with connection fittings<br />

and flexible hoses “3/8” for connection of the heat<br />

exchanger since 1st May 2009.<br />

TEMPERATURE EQUATION FOR HEATING<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

TEMPERATURE EQUATION FOR COOLING<br />

m<br />

( 17 )<br />

Q= Q t m<br />

w<br />

- t a<br />

N<br />

where:<br />

m= 1,0455 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate<br />

for temperatures tw /tA = 70/20 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

where:<br />

m= 0,864 teplotní exponen<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for<br />

temperatures tw /tA = 9/26 ºC [W]<br />

Q heat transfer rate for other<br />

temperatures [W]<br />

52 www.minib.cz


with a fan<br />

COIL – HC<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

HEAT TRANSFER RATE q [W] coil – HC<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 317 1 225 1 189 90 1 446 1 345 1 305 90 1 734 1 613 1 565<br />

80 1 134 1 043 1 007 80 1 245 1 145 1 105 80 1 493 1 373 1 325<br />

70 952 862 826 70 1 045 946 907 70 1 253 1 135 1 087<br />

50 594 505 470 50 652 555 516 50 781 665 619<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 537 1 430 1 387 90 1 687 1 569 1 523 90 2 022 1 882 1 825<br />

80 1 323 1 217 1 175 80 1 452 1 336 1 289 80 1 741 1 602 1 546<br />

70 1 111 1 006 964 70 1 220 1 104 1 058 70 1 462 1 324 1 268<br />

50 693 590 549 50 760 647 602 50 912 776 722<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 085 1 940 1 882 90 2 289 2 130 2 066 90 2 745 2 554 2 477<br />

80 1 796 1 652 1 594 80 1 971 1 813 1 750 80 2 363 2 174 2 098<br />

70 1 508 1 365 1 308 70 1 655 1 498 1 436 70 1 985 1 796 1 721<br />

50 940 800 744 50 1 032 878 817 50 1 237 1 053 980<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 634 2 451 2 378 90 2 892 2 691 2 610 90 3 467 3 226 3 129<br />

80 2 268 2 086 2 013 80 2 490 2 290 2 210 80 2 985 2 746 2 650<br />

70 1 905 1 724 1 652 70 2 091 1 893 1 813 70 2 507 2 269 2 174<br />

50 1 187 1 011 940 50 1 303 1 109 1 032 50 1 563 1 330 1 238<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 183 2 962 2 873 90 3 494 3 251 3 154 90 4 189 3 898 3 781<br />

80 2 741 2 521 2 433 80 3 009 2 767 2 671 80 3 607 3 318 3 202<br />

70 2 302 2 083 1 996 70 2 526 2 287 2 191 70 3 029 2 742 2 627<br />

50 1 435 1 221 1 136 50 1 575 1 341 1 247 50 1 888 1 607 1 495<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 732 3 472 3 369 90 4 097 3 812 3 698 90 4 912 4 570 4 433<br />

80 3 213 2 955 2 852 80 3 527 3 244 3 131 80 4 229 3 890 3 754<br />

70 2 698 2 442 2 340 70 2 962 2 681 2 569 70 3 551 3 214 3 080<br />

50 1 682 1 432 1 332 50 1 847 1 572 1 462 50 2 214 1 884 1 753<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 830 4 493 4 359 90 5 302 4 933 4 785 90 6 356 5 914 5 737<br />

80 4 158 3 825 3 691 80 4 565 4 198 4 052 80 5 473 5 034 4 858<br />

70 3 492 3 161 3 029 70 3 833 3 470 3 325 70 4 596 4 160 3 986<br />

50 2 177 1 853 1 724 50 2 390 2 034 1 892 50 2 865 2 439 2 269<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 927 5 515 5 350 90 6 507 6 054 5 873 90 7 801 7 258 7 041<br />

80 5 104 4 694 4 530 80 5 602 5 153 4 973 80 6 717 6 177 5 962<br />

70 4 286 3 879 3 717 70 4 704 4 258 4 080 70 5 640 5 105 4 892<br />

50 2 672 2 274 2 116 50 2 933 2 496 2 322 50 3 516 2 993 2 784<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

COOLING TRANSFER RATE q [W] coil – HC<br />

2 3<br />

med. speed<br />

max. speed<br />

length L (mm) 900 length L (mm) 900<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 306 324 341 359 9 340 360 379 398<br />

11 271 289 306 324 11 301 321 340 360<br />

13 234 253 271 289 13 260 281 301 321<br />

15 197 216 234 253 15 219 240 260 281<br />

16 178 197 216 234 16 198 219 240 260<br />

length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 357 378 398 418 9 397 420 442 465<br />

11 316 337 357 378 11 351 374 397 420<br />

13 273 295 316 337 13 304 327 351 374<br />

15 230 252 273 295 15 255 280 304 327<br />

16 208 230 252 273 16 231 255 280 304<br />

length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 485 513 540 568 9 539 570 600 631<br />

11 429 457 485 513 11 476 508 539 570<br />

13 371 400 429 457 13 412 444 476 508<br />

15 312 342 371 400 15 347 380 412 444<br />

16 282 312 342 371 16 313 347 380 412<br />

length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 613 648 682 717 9 681 720 758 797<br />

11 541 577 613 648 11 602 641 681 720<br />

13 469 505 541 577 13 521 561 602 641<br />

15 394 431 469 505 15 438 480 521 561<br />

16 356 394 431 469 16 395 438 480 521<br />

length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 740 783 825 866 9 822 870 916 963<br />

11 654 697 740 783 11 727 775 822 870<br />

13 566 610 654 697 13 629 678 727 775<br />

15 476 521 566 610 15 529 579 629 678<br />

16 430 476 521 566 16 478 529 579 629<br />

length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 868 917 967 1 016 9 964 1 020 1 074 1 129<br />

11 767 818 868 917 11 852 908 964 1 020<br />

13 664 716 767 818 13 738 795 852 908<br />

15 558 611 664 716 15 620 679 738 795<br />

16 504 558 611 664 16 560 620 679 738<br />

length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 123 1 187 1 251 1 315 9 1 248 1 319 1 390 1 461<br />

11 992 1 058 1 123 1 187 11 1 103 1 176 1 248 1 319<br />

13 859 926 992 1 058 13 955 1 029 1 103 1 176<br />

15 722 791 859 926 15 803 879 955 1 029<br />

16 652 722 791 859 16 725 803 879 955<br />

length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 378 1 457 1 536 1 613 9 1 531 1 619 1 706 1 793<br />

11 1 218 1 298 1 378 1 457 11 1 353 1 443 1 531 1 619<br />

13 1 054 1 136 1 218 1 298 13 1 171 1 263 1 353 1 443<br />

15 886 971 1 054 1 136 15 985 1 079 1 171 1 263<br />

16 801 886 971 1 054 16 890 985 1 079 1 171<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

53


COIL - HC4p<br />

with a fan<br />

coil – HC4pipe<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

132<br />

123<br />

94815845<br />

CROSS SECTION OF COIL-HC4pipe<br />

LONGITUDINAL<br />

SECTION<br />

COIL-HC4pipe<br />

50<br />

156<br />

129<br />

96<br />

74<br />

47<br />

96<br />

35<br />

303<br />

Ø18<br />

305<br />

Ø30<br />

Ø30<br />

Window<br />

outlet = heating circuit<br />

inlet = cooling circuit<br />

inlet = heating circuit<br />

outlet = cooling circuit<br />

CHARACTERISTICS<br />

6 heating and cooling of interiors cooling output<br />

higher than 1 kW for 2 metre long convector<br />

6 directed air is blown far into the space<br />

6 active demisting of window surfaces<br />

6 implied condensate outlet<br />

6 4 pipe connection<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

303 mm<br />

132 mm<br />

900 to 3000 mm<br />

USAGE<br />

COIL–HC4pipe is a <strong>MINIB</strong> floor convector specially designed<br />

for heating and cooling of the space. The convector<br />

has the 4-pipe connection and completely separated cooling<br />

and heating circuit. The air is tangentially blown to<br />

the floor of the room up to the distance of approximately<br />

3 to 4 m – so that in summer there is a lightly flowing<br />

cool air effect in locations remote from the windows.<br />

This convector has been supplied with connection fittings<br />

and flexible hoses “3/8” for connection of the heat<br />

exchanger since 1st May 2009.<br />

TEMPERATURE EQUATION FOR HEATING<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

TEMPERATURE EQUATION FOR COOLING<br />

m<br />

( 17 )<br />

Q= Q t m<br />

w<br />

- t a<br />

N<br />

where:<br />

m= 1,0864 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for<br />

temperatures tw /tA = 70/20 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

where:<br />

m= 0,907 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for<br />

temperatures tw /tA = 9/26 ºC [W]<br />

Q heat transfer rate for other<br />

temperatures [W]<br />

35<br />

54 www.minib.cz


with a fan<br />

COIL – HC4P<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

HEAT TRANSFER RATE q [W] coil – HC4P<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 100 1 020 989 90 1 202 1 115 1 081 90 1 320 1 224 1 186<br />

80 941 863 832 80 1 029 943 909 80 1 130 1 035 998<br />

70 785 708 677 70 858 774 740 70 942 849 813<br />

50 480 406 377 50 525 444 412 50 577 488 452<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 283 1 190 1 153 90 1 402 1 301 1 261 90 1 539 1 428 1 384<br />

80 1 098 1 007 970 80 1 200 1 100 1 061 80 1 318 1 208 1 164<br />

70 916 826 790 70 1 001 903 863 70 1 099 991 948<br />

50 561 474 440 50 613 518 481 50 673 569 528<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 741 1 615 1 565 90 1 903 1 766 1 711 90 2 089 1 938 1 878<br />

80 1 490 1 366 1 317 80 1 629 1 493 1 439 80 1 788 1 640 1 580<br />

70 1 243 1 121 1 072 70 1 359 1 225 1 172 70 1 492 1 345 1 287<br />

50 761 643 597 50 831 703 652 50 913 772 716<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 199 2 040 1 977 90 2 404 2 230 2 161 90 2 639 2 449 2 373<br />

80 1 883 1 726 1 663 80 2 058 1 886 1 818 80 2 259 2 071 1 996<br />

70 1 570 1 416 1 354 70 1 716 1 547 1 480 70 1 884 1 699 1 625<br />

50 961 813 754 50 1 050 888 824 50 1 153 975 905<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 657 2 465 2 389 90 2 904 2 695 2 611 90 3 189 2 959 2 867<br />

80 2 275 2 085 2 010 80 2 486 2 279 2 197 80 2 730 2 502 2 412<br />

70 1 897 1 711 1 636 70 2 074 1 870 1 789 70 2 277 2 053 1 964<br />

50 1 161 982 911 50 1 269 1 073 996 50 1 393 1 178 1 093<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 116 2 891 2 801 90 3 405 3 159 3 061 90 3 739 3 469 3 361<br />

80 2 667 2 445 2 356 80 2 915 2 672 2 576 80 3 200 2 934 2 828<br />

70 2 224 2 006 1 919 70 2 431 2 192 2 097 70 2 669 2 407 2 302<br />

50 1 361 1 151 1 068 50 1 488 1 258 1 168 50 1 634 1 382 1 282<br />

length L (mm) 2500 length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 032 3 741 3 625 90 4 407 4 089 3 962 90 4 838 4 489 4 350<br />

80 3 451 3 164 3 049 80 3 772 3 458 3 333 80 4 142 3 797 3 660<br />

70 2 879 2 595 2 483 70 3 146 2 837 2 714 70 3 454 3 115 2 979<br />

50 1 762 1 490 1 382 50 1 925 1 629 1 511 50 2 114 1 788 1 659<br />

length L (mm) 3000 length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 948 4 591 4 449 90 5 408 5 018 4 862 90 5 938 5 509 5 338<br />

80 4 236 3 883 3 743 80 4 630 4 244 4 091 80 5 083 4 660 4 491<br />

70 3 533 3 185 3 047 70 3 861 3 481 3 330 70 4 239 3 822 3 657<br />

50 2 162 1 829 1 697 50 2 363 1 999 1 854 50 2 595 2 194 2 036<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

COOLING TRANSFER RATE q [W] coil – HC4P<br />

2 3<br />

med. speed<br />

max. speed<br />

length L (mm) 900 length L (mm) 900<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 314 333 351 370 9 339 359 379 399<br />

11 276 295 314 333 11 297 318 339 359<br />

13 237 256 276 295 13 256 277 297 318<br />

15 197 217 237 256 15 213 234 256 277<br />

16 177 197 217 237 16 191 213 234 256<br />

length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 366 388 410 432 9 395 419 443 466<br />

11 321 344 366 388 11 347 371 395 419<br />

13 276 299 321 344 13 298 323 347 371<br />

15 230 253 276 299 15 249 273 298 323<br />

16 207 230 253 276 16 223 249 273 298<br />

length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 497 527 556 586 9 536 568 601 632<br />

11 436 467 497 527 11 471 504 536 568<br />

13 375 406 436 467 13 405 438 471 504<br />

15 313 344 375 406 15 337 371 405 438<br />

16 281 313 344 375 16 303 337 371 405<br />

length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 627 665 703 740 9 677 718 759 799<br />

11 551 589 627 665 11 595 636 677 718<br />

13 474 512 551 589 13 511 553 595 636<br />

15 395 434 474 512 15 426 469 511 553<br />

16 355 395 434 474 16 383 426 469 511<br />

length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 758 804 849 894 9 818 868 917 965<br />

11 666 712 758 804 11 719 769 818 868<br />

13 572 619 666 712 13 618 668 719 769<br />

15 477 525 572 619 15 515 566 618 668<br />

16 429 477 525 572 16 463 515 566 618<br />

length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 889 942 996 1 049 9 959 1 017 1 075 1 132<br />

11 781 835 889 942 11 843 901 959 1 017<br />

13 671 726 781 835 13 724 784 843 901<br />

15 559 615 671 726 15 604 664 724 784<br />

16 503 559 615 671 16 542 604 664 724<br />

length L (mm) 2500 length L (mm) 2500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 150 1 220 1 289 1 357 9 1 241 1 316 1 391 1 465<br />

11 1 010 1 081 1 150 1 220 11 1 090 1 166 1 241 1 316<br />

13 868 940 1 010 1 081 13 937 1 014 1 090 1 166<br />

15 724 796 868 940 15 781 859 937 1 014<br />

16 650 724 796 868 16 702 781 859 937<br />

length L (mm) 3000 length L (mm) 3000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 412 1 497 1 581 1 666 9 1 524 1 615 1 707 1 798<br />

11 1 240 1 326 1 412 1 497 11 1 338 1 431 1 524 1 615<br />

13 1 066 1 153 1 240 1 326 13 1 150 1 244 1 338 1 431<br />

15 888 977 1 066 1 153 15 959 1 055 1 150 1 244<br />

16 798 888 977 1 066 16 862 959 1 055 1 150<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

55


COIL - HCM<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

118<br />

141<br />

147<br />

121<br />

89<br />

84<br />

50<br />

43<br />

coil – HCM<br />

CHARACTERISTICS<br />

6 heating output higher than 6.5 kW and cooling<br />

output higher than 2 kW for 2-meter long convector<br />

6 directed air is blown far into the space<br />

6 active demisting of window surfaces<br />

6 the most powerful <strong>MINIB</strong> floor convector<br />

6 implied condensate outlet<br />

6 2-pipe connection<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-HCM<br />

83<br />

178<br />

151<br />

340<br />

LONGITUDINAL SECTION COIL-HCM<br />

134<br />

96<br />

Ø30<br />

338<br />

340 mm<br />

147 mm<br />

900 to 2000 mm<br />

USAGE<br />

COIL–HCM is a <strong>MINIB</strong> floor convector specially designed for<br />

intensive heating and cooling of the space. The convector<br />

has the 2-pipe connection, which achieves the maximum<br />

heating and cooling output. The air is tangentially blown<br />

to the floor of the room up to a distance of 3 to 4 m – so<br />

that in summer there is a lightly flowing cool air effect in<br />

locations remote from the windows.<br />

This convector has been supplied with connection fittings<br />

and flexible hoses “3/8” for connection of the heat exchanger<br />

since 1st May 2009.<br />

Ø18<br />

Ø30<br />

Window<br />

56 www.minib.cz


with a fan<br />

COIL – HCM<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

TEMPERATURE EQUATION FOR HEATING<br />

Q = Q N<br />

HEAT TRANSFER RATE q [W] coil – HCM<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 298 2 149 2 089 90 2 787 2 606 2 533 90 3 458 3 233 3 143<br />

80 1 999 1 849 1 789 80 2 424 2 243 2 170 80 3 008 2 782 2 692<br />

70 1 699 1 549 1 488 70 2 060 1 878 1 805 70 2 556 2 330 2 239<br />

50 1 094 942 880 50 1 327 1 142 1 068 50 1 646 1 417 1 325<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 681 2 507 2 437 90 3 251 3 040 2 955 90 4 034 3 772 3 667<br />

80 2 332 2 158 2 088 80 2 828 2 616 2 531 80 3 509 3 246 3 141<br />

70 1 982 1 807 1 736 70 2 404 2 191 2 105 70 2 982 2 718 2 612<br />

50 1 276 1 099 1 027 50 1 548 1 332 1 246 50 1 920 1 653 1 545<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 639 3 402 3 308 90 4 413 4 126 4 011 90 5 475 5 119 4 976<br />

80 3 166 2 928 2 833 80 3 839 3 551 3 435 80 4 762 4 405 4 262<br />

70 2 690 2 452 2 356 70 3 262 2 973 2 857 70 4 047 3 689 3 545<br />

50 1 732 1 491 1 394 50 2 101 1 808 1 690 50 2 606 2 243 2 097<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 596 4 298 4 178 90 5 574 5 212 5 066 90 6 915 6 466 6 286<br />

80 3 999 3 699 3 579 80 4 849 4 485 4 339 80 6 016 5 565 5 384<br />

70 3 398 3 097 2 976 70 4 121 3 755 3 609 70 5 113 4 659 4 478<br />

50 2 188 1 883 1 761 50 2 654 2 284 2 135 50 3 292 2 833 2 649<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 554 5 193 5 049 90 6 735 6 297 6 122 90 8 356 7 813 7 596<br />

80 4 832 4 469 4 324 80 5 859 5 420 5 244 80 7 269 6 724 6 506<br />

70 4 106 3 742 3 596 70 4 979 4 538 4 361 70 6 178 5 630 5 411<br />

50 2 644 2 276 2 128 50 3 206 2 759 2 580 50 3 978 3 424 3 201<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 6 512 6 089 5 919 90 7 896 7 383 7 178 90 9 797 9 160 8 905<br />

80 5 665 5 240 5 070 80 6 869 6 354 6 148 80 8 522 7 883 7 627<br />

70 4 814 4 387 4 216 70 5 838 5 320 5 113 70 7 243 6 601 6 344<br />

50 3 100 2 668 2 495 50 3 759 3 235 3 025 50 4 664 4 014 3 753<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 0,9738 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for temperatures<br />

tw /tA = 70/20 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

m<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

COOLING TRANSFER RATE q [W] coil – HCM<br />

2 3<br />

med. speed<br />

max. speed<br />

length L (mm) 900 length L (mm) 900<br />

mean air temperature tA<br />

TEMPERATURE EQUATION FOR COOLING<br />

( 17 )<br />

Q= Q t m<br />

w<br />

- t a<br />

N<br />

where:<br />

m= 1 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for temperatures<br />

tw /tA = 9/26 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 571 609 647 685 9 666 711 755 800<br />

11 495 533 571 609 11 578 622 666 711<br />

13 419 457 495 533 13 489 533 578 622<br />

15 342 381 419 457 15 400 444 489 533<br />

16 304 342 381 419 16 355 400 444 489<br />

length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 666 710 755 799 9 778 829 881 933<br />

11 577 622 666 710 11 674 726 778 829<br />

13 488 533 577 622 13 570 622 674 726<br />

15 400 444 488 533 15 467 518 570 622<br />

16 355 400 444 488 16 415 467 518 570<br />

length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 904 964 1 024 1 084 9 1 055 1 126 1 196 1 266<br />

11 783 843 904 964 11 915 985 1 055 1 126<br />

13 663 723 783 843 13 774 844 915 985<br />

15 542 602 663 723 15 633 703 774 844<br />

16 482 542 602 663 16 563 633 703 774<br />

length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 142 1 218 1 294 1 370 9 1 333 1 422 1 511 1 599<br />

11 989 1 065 1 142 1 218 11 1 155 1 244 1 333 1 422<br />

13 837 913 989 1 065 13 977 1 066 1 155 1 244<br />

15 685 761 837 913 15 800 889 977 1 066<br />

16 609 685 761 837 16 711 800 889 977<br />

length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 379 1 471 1 563 1 655 9 1 611 1 718 1 825 1 933<br />

11 1 195 1 287 1 379 1 471 11 1 396 1 503 1 611 1 718<br />

13 1 012 1 104 1 195 1 287 13 1 181 1 288 1 396 1 503<br />

15 828 920 1 012 1 104 15 966 1 074 1 181 1 288<br />

16 736 828 920 1 012 16 859 966 1 074 1 181<br />

length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 617 1 725 1 833 1 941 9 1 888 2 014 2 140 2 266<br />

11 1 402 1 509 1 617 1 725 11 1 637 1 762 1 888 2 014<br />

13 1 186 1 294 1 402 1 509 13 1 385 1 511 1 637 1 762<br />

15 970 1 078 1 186 1 294 15 1 133 1 259 1 385 1 511<br />

16 863 970 1 078 1 186 16 1 007 1 133 1 259 1 385<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

57


COIL - HCM4p<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

147<br />

118<br />

141<br />

121<br />

83<br />

78<br />

43<br />

89<br />

84<br />

50<br />

coil – HCM4pipe<br />

CHARACTERISTICS<br />

6 cooling output higher than 2 kW for 2-meter long convector<br />

6 directed air is blown far into the space<br />

6 active demisting of window surfaces<br />

6 the most powerful <strong>MINIB</strong> floor convector<br />

6 the convector is suitable for connection to the 4-pipe<br />

system with the separated heating and cooling circuit<br />

6 implied condensate outlet<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-HC4pipe<br />

57 83 151178 340<br />

338<br />

LONGITUDINAL SECTION COIL-HC4pipe<br />

134<br />

96<br />

Ø30<br />

340 mm<br />

147 mm<br />

900 to 2000 mm<br />

USAGE<br />

COIL–HCM4pipe is a <strong>MINIB</strong> floor convector specially<br />

designed for intensive heating and cooling of the space.<br />

The convector has the 4-pipe connection. The air<br />

is tangentially blown to the floor of the room up to a<br />

distance of 3 to 4 m – so that in summer there is a<br />

lightly flowing cool air effect in locations remote from<br />

the windows.<br />

This convector has been supplied with connection fittings<br />

and flexible hoses “3/8” for connection of the<br />

heat exchanger since 1st May 2009.<br />

Ø30<br />

Ø18<br />

Window<br />

outlet = heating circuit<br />

inlet = cooling circuit<br />

inlet = heating circuit<br />

outlet = cooling circuit<br />

58 www.minib.cz


with a fan<br />

COIL – HCM4P<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

Q = Q N<br />

HEAT TRANSFER RATE q [W] coil – HCM4P<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 292 1 201 1 165 90 1 445 1 343 1 303 90 1 625 1 510 1 464<br />

80 1 110 1 020 984 80 1 242 1 141 1 101 80 1 396 1 283 1 237<br />

70 930 841 805 70 1 040 941 901 70 1 170 1 057 1 013<br />

50 576 490 455 50 645 548 509 50 725 616 572<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 507 1 401 1 359 90 1 686 1 567 1 520 90 1 895 1 762 1 709<br />

80 1 295 1 190 1 148 80 1 449 1 331 1 284 80 1 629 1 496 1 444<br />

70 1 085 981 940 70 1 214 1 097 1 051 70 1 365 1 234 1 181<br />

50 672 571 531 50 752 639 594 50 845 718 668<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 046 1 902 1 844 90 2 288 2 127 2 063 90 2 572 2 391 2 319<br />

80 1 758 1 615 1 558 80 1 966 1 806 1 743 80 2 210 2 031 1 959<br />

70 1 473 1 331 1 275 70 1 647 1 489 1 426 70 1 852 1 674 1 603<br />

50 913 775 720 50 1 021 867 806 50 1 147 975 906<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 584 2 402 2 329 90 2 890 2 687 2 605 90 3 249 3 020 2 929<br />

80 2 221 2 040 1 968 80 2 484 2 282 2 201 80 2 792 2 565 2 475<br />

70 1 861 1 682 1 611 70 2 081 1 881 1 801 70 2 339 2 115 2 025<br />

50 1 153 979 910 50 1 289 1 095 1 018 50 1 449 1 231 1 144<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 122 2 902 2 815 90 3 492 3 246 3 148 90 3 926 3 649 3 539<br />

80 2 683 2 465 2 378 80 3 001 2 757 2 660 80 3 374 3 100 2 990<br />

70 2 248 2 032 1 946 70 2 514 2 273 2 177 70 2 827 2 555 2 447<br />

50 1 393 1 183 1 100 50 1 558 1 323 1 230 50 1 751 1 488 1 383<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 661 3 403 3 300 90 4 094 3 806 3 691 90 4 603 4 279 4 149<br />

80 3 146 2 890 2 788 80 3 519 3 233 3 119 80 3 956 3 634 3 506<br />

70 2 636 2 383 2 282 70 2 948 2 665 2 552 70 3 314 2 996 2 869<br />

50 1 633 1 387 1 289 50 1 826 1 551 1 442 50 2 053 1 744 1 621<br />

TEMPERATURE EQUATION FOR HEATING<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

m= 1,0592 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for temperatures tw /tA = 70/20 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

mean water<br />

temperature tW<br />

COOLING TRANSFER RATE q [W] coil – HCM4P<br />

2 3<br />

med. speed<br />

max. speed<br />

length L (mm) 900 length L (mm) 900<br />

mean air temperature tA<br />

TEMPERATURE EQUATION FOR COOLING<br />

( 17 )<br />

Q= Q t m<br />

w<br />

- t a<br />

N<br />

m= 1,0 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for temperatures<br />

tw /tA = 9/26 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 479 511 543 575 9 624 666 708 749<br />

11 415 447 479 511 11 541 583 624 666<br />

13 351 383 415 447 13 458 499 541 583<br />

15 287 319 351 383 15 375 416 458 499<br />

16 255 287 319 351 16 333 375 416 458<br />

length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 559 596 633 670 9 728 777 826 874<br />

11 484 521 559 596 11 631 680 728 777<br />

13 410 447 484 521 13 534 583 631 680<br />

15 335 372 410 447 15 437 486 534 583<br />

16 298 335 372 410 16 388 437 486 534<br />

length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 758 809 859 910 9 989 1 054 1 120 1 186<br />

11 657 708 758 809 11 857 923 989 1 054<br />

13 556 606 657 708 13 725 791 857 923<br />

15 455 505 556 606 15 593 659 725 791<br />

16 404 455 505 556 16 527 593 659 725<br />

length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 958 1 021 1 085 1 149 9 1 249 1 332 1 415 1 498<br />

11 830 894 958 1 021 11 1 082 1 165 1 249 1 332<br />

13 702 766 830 894 13 916 999 1 082 1 165<br />

15 575 638 702 766 15 749 832 916 999<br />

16 511 575 638 702 16 666 749 832 916<br />

length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 157 1 234 1 311 1 389 9 1 509 1 609 1 710 1 811<br />

11 1 003 1 080 1 157 1 234 11 1 308 1 408 1 509 1 609<br />

13 849 926 1 003 1 080 13 1 106 1 207 1 308 1 408<br />

15 694 771 849 926 15 905 1 006 1 106 1 207<br />

16 617 694 771 849 16 805 905 1 006 1 106<br />

length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA<br />

mean air temperature tA<br />

24 25 26 27 24 25 26 27<br />

9 1 357 1 447 1 538 1 628 9 1 769 1 887 2 005 2 123<br />

11 1 176 1 266 1 357 1 447 11 1 533 1 651 1 769 1 887<br />

13 995 1 085 1 176 1 266 13 1 297 1 415 1 533 1 651<br />

15 814 904 995 1 085 15 1 061 1 179 1 297 1 415<br />

16 724 814 904 995 16 943 1 061 1 179 1 297<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

59


COIL - MT2<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

131<br />

90<br />

Cooling effect of the convector<br />

COIL – MT2:<br />

For water flow temperatures of<br />

6/12.C take<br />

an estimated cooling output of<br />

300W/per linear metre at speed 2<br />

and approximately 400W per linear<br />

metre at speed 3.<br />

48<br />

CROSS SECTION OF COIL-MT2<br />

160<br />

222<br />

380<br />

Ø30<br />

140<br />

COIL – MT2<br />

CHARACTERISTICS<br />

6 the most universal <strong>MINIB</strong> convector<br />

6 automatic angle of airflow<br />

6 heating of dry and wet interiors<br />

6 automatic blowing to window surfaces for demisting<br />

6 partial cooling of the space in the summer<br />

6 use possible only with the MT 2 control<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

380 mm<br />

140 mm<br />

900 to 2000 mm<br />

USAGE<br />

This convector includes 12 V DC motors with an extremely<br />

low power consumption and economical heating is ensured<br />

during operation. It uses the newly developed electronic<br />

IQ controller <strong>MINIB</strong> MT-2. This controller includes automatic<br />

continuous speed control of the fan (thus the heat<br />

output of the convector) via a microprocessor, automatic<br />

angle of airflow, user adjustable max. speed level, night<br />

speed reduction, user selection of the operation mode, disabling<br />

of fan at low water temperature and contactless,<br />

noiseless switching of the thermostat. The multifunctional<br />

convector enables automatic inclination of airflow with an<br />

extremely high heat output at very low speed. (At temperatures<br />

of 75/65/20 ºC, the convector achieves a heat output<br />

of approx. 1600 W for 1m length at medium speed.).<br />

The inclination of the warm airflow to different directions<br />

provides (based on the pulse from the sensor) either automatic<br />

demisting of steamed up windows by warm air from<br />

the convector or intensive heating of objects in the room<br />

into the interior by declined airflow. In standard mode, the<br />

convector generates the vertical heat curtain providing<br />

either heating of the interior or demisting of the window.<br />

Thanks to an arrangement of fans the convector can be<br />

used for cooling of the space in the summer as the cool<br />

air is directed into the room at an angle and not vertically.<br />

The fast-acting heat exchanger reacts very quickly to changing<br />

requirements and provides user‘s optimum levels of<br />

comfort.<br />

Window<br />

LONGITUDINAL SECTION COIL-MT2<br />

Ø30<br />

116<br />

45 49<br />

162<br />

382<br />

Ø18<br />

60 www.minib.cz


with a fan<br />

COIL – MT2<br />

HEAT TRANSFER RATE q [W] coil – MT2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 983 1 841 1 784 90 2 134 1 980 1 919 90 2 392 2 220 2 152<br />

80 1 699 1 558 1 502 80 1 828 1 677 1 616 80 2 050 1 880 1 812<br />

70 1 418 1 280 1 225 70 1 526 1 377 1 318 70 1 711 1 544 1 477<br />

50 871 737 684 50 937 793 736 50 1 050 889 825<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 313 2 147 2 081 90 2 489 2 310 2 239 90 2 791 2 591 2 511<br />

80 1 982 1 818 1 753 80 2 133 1 956 1 886 80 2 391 2 193 2 114<br />

70 1 655 1 493 1 429 70 1 781 1 606 1 537 70 1 997 1 801 1 724<br />

50 1 016 860 798 50 1 093 925 859 50 1 225 1 037 963<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 140 2 914 2 824 90 3 378 3 135 3 039 90 3 788 3 516 3 407<br />

80 2 690 2 467 2 378 80 2 894 2 655 2 559 80 3 245 2 977 2 870<br />

70 2 246 2 026 1 939 70 2 416 2 180 2 086 70 2 710 2 445 2 339<br />

50 1 378 1 167 1 083 50 1 483 1 256 1 165 50 1 663 1 408 1 307<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 966 3 681 3 568 90 4 267 3 961 3 839 90 4 785 4 441 4 304<br />

80 3 398 3 116 3 004 80 3 656 3 353 3 233 80 4 099 3 760 3 625<br />

70 2 837 2 559 2 449 70 3 052 2 754 2 635 70 3 423 3 088 2 955<br />

50 1 741 1 474 1 368 50 1 873 1 586 1 472 50 2 101 1 778 1 651<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 792 4 448 4 311 90 5 156 4 786 4 638 90 5 781 5 366 5 201<br />

80 4 106 3 766 3 630 80 4 418 4 052 3 906 80 4 953 4 543 4 380<br />

70 3 428 3 093 2 959 70 3 688 3 328 3 184 70 4 136 3 731 3 570<br />

50 2 104 1 781 1 653 50 2 264 1 916 1 779 50 2 538 2 149 1 995<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 618 5 215 5 054 90 6 045 5 611 5 438 90 6 778 6 291 6 097<br />

80 4 814 4 415 4 256 80 5 179 4 750 4 580 80 5 807 5 326 5 135<br />

70 4 019 3 626 3 469 70 4 324 3 901 3 733 70 4 849 4 374 4 186<br />

50 2 467 2 088 1 938 50 2 654 2 247 2 086 50 2 976 2 519 2 339<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

where:<br />

m= 1,080 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature, vzduchu [°C]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

61


<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

SPECIAL<br />

CONVECTORS<br />

62 www.minib.cz


<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

63


COIL - TE<br />

with a fan<br />

COIL – TE<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Window<br />

CHARACTERISTICS<br />

6 electrical heating of dry interiors<br />

6 electric direct heating convector with 230 V fan<br />

6 electrical cover protection IP20<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

CROSS SECTION OF COIL-TE<br />

303<br />

305<br />

303 mm<br />

125 mm<br />

500 to 2500 mm<br />

USAGE<br />

Recommended for individual use in dry interiors with a<br />

variety of heating demands.<br />

Funkce<br />

The heat is generated by electrical heating coils that are<br />

transversally cooled by fan. The thermal protection of<br />

the unit is ensured with temperature limiters reacting<br />

to the temperature of the discharge air. The convector<br />

has a single fan speed and heat output is fixed at 750<br />

W per 500 mm long convector module. Only control A (<br />

one speed) is available and the fan speed is fixed to the<br />

speed level 2.<br />

HEAT TRANSFER RATE COIL-TE<br />

length L (mm) 500 1000 1500 2000 2500<br />

Q (W) 750 1500 2250 3000 3750<br />

125<br />

64 www.minib.cz


with a fan<br />

COIL – SK<br />

COIL – sK<br />

CHARACTERISTICS<br />

6 heating for kitchen and hall interiors<br />

6 not designed for mounting into the floor but for<br />

skirting or kick space mounting<br />

6 installation under skirting, cabinets<br />

(kitchen cupboards etc.)<br />

6 air inlet and outlet at the front<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

HEAT TRANSFER RATE q [W] coil – SK<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 556 length L (mm) 556 length L (mm) 556<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 526 491 477<br />

mean water<br />

temperature<br />

tW<br />

328 mm<br />

102 mm<br />

556 mm<br />

USAGE<br />

The front section of the convector (97 x 500 mm) is covered<br />

with a decorative grille and is divided into upper and<br />

lower sections. The air is drawn from the space through<br />

the upper front section and heated air is delivered back<br />

to the space through the lower front section. All this provides<br />

a very compact unit design. The convector is suitable<br />

for kitchen heating as well as in stairs, bathroom<br />

and hallway skirting.<br />

1. min. speed<br />

2. med. speed 3. max. speed<br />

90 554 518 503<br />

mean water<br />

temperature<br />

tW<br />

90 714 667 648<br />

80 456 422 408 80 481 444 430 80 620 573 554<br />

70 387 352 338 70 408 371 356 70 525 478 459<br />

50 247 212 198 50 261 224 209 50 336 288 269<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

where:<br />

m= 0,99 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-SK<br />

328<br />

102<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

65


COIL - KP<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

where:<br />

m= 1,0365 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

39<br />

20<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

CROSS SECTION OF COIL-KP<br />

272<br />

19<br />

135<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

coil – KP<br />

CHARACTERISTICS<br />

6 heating output higher than 2.3 kW for 1.5 m long<br />

convector<br />

6 heating of dry interiors<br />

6 the convector is designed for installation into the<br />

window sill incl. the window sill<br />

6 the sill is only supplied in beech or oak design<br />

without wood surface finish.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

272 mm<br />

135 mm incl. the window sill<br />

900 to 1500 mm<br />

USAGE<br />

The <strong>MINIB</strong> window sill convector is suitable for all types<br />

of windows with a sill of a minimum depth of 250 mm.<br />

HEAT TRANSFER RATE q [W] coil – KP<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 144 1 065 1 033 90 1 432 1 333 1 294 90 1 769 1 647 1 598<br />

80 986 907 876 80 1 235 1 136 1 097 80 1 525 1 404 1 355<br />

70 829 751 720 70 1 038 941 902 70 1 282 1 162 1 114<br />

50 519 442 412 50 650 554 516 50 803 684 637<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 334 1 242 1 205 90 1 671 1 556 1 510 90 2 064 1 921 1 864<br />

80 1 150 1 059 1 022 80 1 441 1 326 1 280 80 1 779 1 637 1 581<br />

70 967 876 840 70 1 212 1 098 1 052 70 1 496 1 355 1 299<br />

50 606 516 480 50 758 646 602 50 937 798 743<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 811 1 686 1 636 90 2 268 2 111 2 049 90 2 801 2 607 2 530<br />

80 1 561 1 437 1 387 80 1 955 1 799 1 737 80 2 414 2 222 2 146<br />

70 1 313 1 189 1 140 70 1 644 1 490 1 428 70 2 031 1 840 1 763<br />

50 822 700 652 50 1 029 877 817 50 1 271 1 083 1 009<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 287 2 129 2 066 90 2 864 2 667 2 588 90 3 538 3 293 3 196<br />

80 1 972 1 815 1 752 80 2 469 2 273 2 194 80 3 050 2 807 2 710<br />

70 1 658 1 502 1 440 70 2 077 1 882 1 804 70 2 565 2 324 2 227<br />

50 1 038 885 824 50 1 300 1 108 1 032 50 1 606 1 368 1 274<br />

36<br />

72<br />

LONGITUDINAL SECTION COIL-KP<br />

65 80<br />

18<br />

242<br />

66 www.minib.cz


without a fan<br />

COIL – LP<br />

coil – LP<br />

CHARACTERISTICS<br />

6 Minib heating bench with heat output higher than<br />

1.3 kW for 1 m long convector<br />

6 for heating dry and wet environments<br />

6 cover board from real marble<br />

6 load capacity of the bench up to 150 kg<br />

6 equipped with the thermostatic head<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L rámu tělesa<br />

281 mm<br />

435 mm<br />

1000, 1250 a 1500 mm<br />

USAGE<br />

COIL-LP is a fast responding heating unit with a medium<br />

heat output. The bench heater is manufactured from<br />

silver, light or eventually dark bronze finish aluminium<br />

alloy or white Ral paint finish.<br />

This bench heater is an aesthetic heating option for interiors<br />

and swimming pool areas. Marble tops are provided<br />

in a range of designs - see details on left. The bench<br />

heater is designed for a load up to 150 kg.<br />

Info:<br />

Lengths 1000 and 1250 mm are supplied with the<br />

marble top and the convector length of 1500 mm with<br />

the beech wooden top.<br />

CROSS SECTION OF COIL-LP<br />

281<br />

232<br />

435<br />

Window<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 1,4035 temperature exponent<br />

pro LP+<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for<br />

difference of temperatures<br />

tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other<br />

temperatures [W]<br />

HEAT TRANSFER RATE q [W] COIL-LP<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 351 2 134 2 049<br />

80 1 923 1 719 1 639<br />

70 1 521 1 331 1 257<br />

50 807 650 590<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 3 072 2 789 2 678<br />

80 2 513 2 246 2 142<br />

70 1 988 1 739 1 642<br />

50 1 054 849 771<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 3 794 3 443 3 306<br />

80 3 103 2 774 2 645<br />

70 2 455 2 147 2 028<br />

50 1 302 1 048 952<br />

m<br />

TYPES OF<br />

GENUINE GRANITE<br />

red<br />

brown-green<br />

white<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

67


COIL - DP<br />

without a fan<br />

coil – DP<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= 1,3788 temperature exponent<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

m<br />

CROSS SECTION OF COIL-DP<br />

176<br />

214<br />

CHARACTERISTICS<br />

6 for heating dry interiors<br />

6 easthetic all wood self-standing convector<br />

6 medium heat output from natural convection<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

176 mm<br />

214 mm<br />

900 to 2000 mm<br />

USAGE<br />

COIL – DP is the <strong>MINIB</strong> floor self-standing convector<br />

specially designed as an aesthetic interior option made<br />

from solid wood.<br />

info:<br />

The decorative all wood grille of the convector must not<br />

be covered or loaded. The convector is manufactured in<br />

beech with matt varnish finish.<br />

HEAT TRANSFER RATE q [W] coil – DP<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 910 828 795<br />

80 747 669 639<br />

70 594 521 492<br />

50 318 257 234<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 062 966 928<br />

80 872 781 745<br />

70 693 607 574<br />

50 371 300 273<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 821 1 656 1 591<br />

80 1 495 1 339 1 277<br />

70 1 187 1 041 984<br />

50 637 515 468<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 579 2 345 2 254<br />

80 2 118 1 896 1 810<br />

70 1 682 1 475 1 394<br />

50 902 729 663<br />

177<br />

68 www.minib.cz


with a fan<br />

COIL – LP<br />

WALL AND SELF-STANDING<br />

CONVECTORS<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

69


COIL - NK1<br />

with a fan<br />

coil – NK1<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CROSS SECTION OF COIL-NK1<br />

156<br />

CHARACTERISTICS<br />

6 wall convector with the fan<br />

6 designed for installation on the wall<br />

of the room<br />

6 for heating dry interiors<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

170 mm<br />

900 to 2000 mm<br />

USAGE<br />

Wall convectors are fast responding heating units<br />

from a higher heat output series of <strong>MINIB</strong> convectors<br />

with 12V fans. They are also suitable for applications<br />

when the window sill is placed 25 to 30 cm<br />

above the floor so as not to reach the window area.<br />

Info:<br />

The decorative grille of the convector must not be<br />

covered or loaded.<br />

m<br />

170<br />

where:<br />

m= temperature exponent 1,0952<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

Window<br />

70 www.minib.cz


with a fan<br />

COIL – NK1<br />

HEAT TRANSFER RATE q [W] coil – nk1<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 355 1 257 1 217 90 1 450 1 344 1 302 90 1 888 1 750 1 696<br />

80 1 159 1 061 1 023 80 1 239 1 135 1 094 80 1 614 1 478 1 425<br />

70 965 869 831 70 1 032 930 889 70 1 344 1 211 1 158<br />

50 588 497 461 50 629 531 493 50 819 692 642<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 581 1 466 1 420 90 1 691 1 568 1 519 90 2 202 2 042 1 978<br />

80 1 352 1 238 1 193 80 1 446 1 325 1 276 80 1 883 1 725 1 662<br />

70 1 126 1 014 970 70 1 204 1 085 1 037 70 1 568 1 413 1 351<br />

50 686 580 537 50 734 620 575 50 956 807 749<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 146 1 990 1 927 90 2 296 2 128 2 062 90 2 989 2 771 2 685<br />

80 1 834 1 680 1 619 80 1 963 1 798 1 732 80 2 555 2 341 2 255<br />

70 1 528 1 376 1 316 70 1 634 1 472 1 408 70 2 128 1 917 1 833<br />

50 931 787 729 50 996 841 780 50 1 297 1 096 1 016<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 710 2 513 2 435 90 2 900 2 689 2 605 90 3 775 3 501 3 391<br />

80 2 317 2 123 2 045 80 2 479 2 271 2 188 80 3 228 2 957 2 849<br />

70 1 930 1 738 1 662 70 2 064 1 860 1 779 70 2 688 2 422 2 316<br />

50 1 176 994 921 50 1 258 1 063 986 50 1 638 1 384 1 283<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 275 3 037 2 942 90 3 504 3 249 3 147 90 4 562 4 230 4 098<br />

80 2 800 2 565 2 471 80 2 995 2 744 2 644 80 3 900 3 573 3 443<br />

70 2 332 2 101 2 009 70 2 495 2 247 2 149 70 3 248 2 926 2 798<br />

50 1 421 1 201 1 113 50 1 521 1 284 1 191 50 1 980 1 672 1 551<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 840 3 560 3 449 90 4 108 3 809 3 690 90 5 349 4 959 4 804<br />

80 3 283 3 007 2 898 80 3 512 3 217 3 100 80 4 573 4 189 4 036<br />

70 2 734 2 463 2 355 70 2 925 2 635 2 520 70 3 808 3 431 3 281<br />

50 1 666 1 408 1 305 50 1 783 1 506 1 396 50 2 321 1 961 1 818<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

71


COIL - NK2<br />

with a fan<br />

coil – NK2<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

m<br />

where:<br />

m= temperature exponent 1,171<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-NK2<br />

156<br />

340<br />

CHARACTERISTICS<br />

6 wall convector with the fan<br />

6 designed for installation on the wall<br />

of the room<br />

6 for heating dry interiors<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height od<br />

length L<br />

156 mm<br />

340 mm<br />

900 to 2000 mm<br />

USAGE<br />

Wall convectors are fast responding heating<br />

units from a higher heat output series of MI-<br />

NIB convectors with 12V fans. They are also<br />

suitable for applications when the window sill<br />

is placed 50 to 60 cm above the floor so as not<br />

to reach the window area.<br />

Info:<br />

The decorative grille of the convector must not<br />

be covered or loaded..<br />

Window<br />

72 www.minib.cz


with a fan<br />

COIL – NK2<br />

HEAT TRANSFER RATE q [W] coil – nk2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 026 1 869 1 807 90 2 131 1 966 1 900 90 2 415 2 227 2 153<br />

80 1 714 1 560 1 500 80 1 802 1 641 1 577 80 2 042 1 859 1 787<br />

70 1 409 1 260 1 202 70 1 482 1 326 1 264 70 1 679 1 502 1 432<br />

50 830 693 639 50 873 729 672 50 989 826 762<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 364 2 181 2 108 90 2 487 2 294 2 217 90 2 817 2 598 2 512<br />

80 1 999 1 820 1 750 80 2 103 1 915 1 840 80 2 382 2 169 2 085<br />

70 1 644 1 470 1 402 70 1 729 1 547 1 474 70 1 959 1 752 1 670<br />

50 968 808 746 50 1 019 850 784 50 1 154 963 889<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 208 2 959 2 861 90 3 375 3 113 3 009 90 3 823 3 526 3 409<br />

80 2 713 2 471 2 374 80 2 854 2 599 2 497 80 3 233 2 944 2 829<br />

70 2 231 1 996 1 902 70 2 347 2 099 2 001 70 2 659 2 378 2 267<br />

50 1 314 1 097 1 012 50 1 382 1 154 1 065 50 1 566 1 307 1 206<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 053 3 738 3 613 90 4 263 3 932 3 801 90 4 829 4 454 4 306<br />

80 3 427 3 121 2 999 80 3 605 3 282 3 155 80 4 084 3 719 3 574<br />

70 2 818 2 521 2 403 70 2 964 2 651 2 528 70 3 358 3 004 2 864<br />

50 1 660 1 386 1 278 50 1 746 1 458 1 345 50 1 978 1 652 1 523<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 897 4 517 4 366 90 5 151 4 751 4 592 90 5 835 5 382 5 203<br />

80 4 141 3 771 3 624 80 4 356 3 966 3 812 80 4 935 4 493 4 319<br />

70 3 406 3 046 2 904 70 3 582 3 204 3 054 70 4 058 3 630 3 460<br />

50 2 006 1 675 1 545 50 2 110 1 762 1 625 50 2 390 1 996 1 841<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 741 5 296 5 119 90 6 039 5 570 5 384 90 6 841 6 310 6 100<br />

80 4 855 4 421 4 249 80 5 107 4 650 4 469 80 5 786 5 268 5 063<br />

70 3 993 3 571 3 404 70 4 200 3 756 3 581 70 4 758 4 255 4 057<br />

50 2 352 1 963 1 811 50 2 474 2 065 1 905 50 2 803 2 340 2 158<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

73


COIL - SK1<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

CROSS SECTION OF COIL-SK1<br />

156<br />

m<br />

COIL – SK1<br />

CHARACTERISTICS<br />

6 self-standing convector with the fan<br />

6 for heating dry interiors<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

230 mm<br />

900 to 2000 mm<br />

USAGE<br />

Self-standing <strong>MINIB</strong> convector with the fan suitable<br />

for heating of interiors. The modern product made<br />

from aesthetically pleasing alloy and colour matched<br />

to <strong>MINIB</strong> floor convectors. Available in colour tints –<br />

silver, light bronze, dark bronze and white.<br />

Info:<br />

The decorative grille of the convector must not be<br />

covered or loaded.<br />

230<br />

where:<br />

m= temperature exponent 1,0953<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

Window<br />

74 www.minib.cz


with a fan<br />

COIL – SK1<br />

HEAT TRANSFER RATE q [W] coil – SK1<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 355 1 257 1 217 90 1 450 1 344 1 302 90 1 888 1 750 1 696<br />

80 1 159 1 061 1 023 80 1 239 1 135 1 094 80 1 614 1 478 1 425<br />

70 965 869 831 70 1 032 930 889 70 1 344 1 211 1 158<br />

50 588 497 461 50 629 531 493 50 819 692 642<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 1 581 1 466 1 420 90 1 691 1 568 1 519 90 2 202 2 042 1 978<br />

80 1 352 1 238 1 193 80 1 446 1 325 1 276 80 1 883 1 725 1 662<br />

70 1 126 1 014 970 70 1 204 1 085 1 037 70 1 568 1 413 1 351<br />

50 686 580 537 50 734 620 575 50 956 807 749<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 146 1 990 1 927 90 2 296 2 128 2 062 90 2 989 2 771 2 685<br />

80 1 834 1 680 1 619 80 1 963 1 798 1 732 80 2 555 2 341 2 255<br />

70 1 528 1 376 1 316 70 1 634 1 472 1 408 70 2 128 1 917 1 833<br />

50 931 787 729 50 996 841 780 50 1 297 1 096 1 016<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 710 2 513 2 435 90 2 900 2 689 2 605 90 3 775 3 501 3 391<br />

80 2 317 2 123 2 045 80 2 479 2 271 2 188 80 3 228 2 957 2 849<br />

70 1 930 1 738 1 662 70 2 064 1 860 1 779 70 2 688 2 422 2 316<br />

50 1 176 994 921 50 1 258 1 063 986 50 1 638 1 384 1 283<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 275 3 037 2 942 90 3 504 3 249 3 147 90 4 562 4 230 4 098<br />

80 2 800 2 565 2 471 80 2 995 2 744 2 644 80 3 900 3 573 3 443<br />

70 2 332 2 101 2 009 70 2 495 2 247 2 149 70 3 248 2 926 2 798<br />

50 1 421 1 201 1 113 50 1 521 1 284 1 191 50 1 980 1 672 1 551<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 840 3 560 3 449 90 4 108 3 809 3 690 90 5 349 4 959 4 804<br />

80 3 283 3 007 2 898 80 3 512 3 217 3 100 80 4 573 4 189 4 036<br />

70 2 734 2 463 2 355 70 2 925 2 635 2 520 70 3 808 3 431 3 281<br />

50 1 666 1 408 1 305 50 1 783 1 506 1 396 50 2 321 1 961 1 818<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

75


COIL - SK2<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,171<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

m<br />

COIL – SK2<br />

CHARACTERISTICS<br />

6 self-standing convector with the fan<br />

6 for heating dry interiors<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

400 mm<br />

900 to 2000 mm<br />

USAGE<br />

Self-standing <strong>MINIB</strong> convector with the fan suitable<br />

for heating of interiors. The modern product made<br />

from aesthetically pleasing alloy and colour matched<br />

to <strong>MINIB</strong> floor convectors. Available in colour<br />

tints – silver, light bronze, dark bronze and white.<br />

Info:<br />

The decorative grille of the convector must not be<br />

covered or loaded.<br />

CROSS SECTION OF COIL-SK2<br />

156<br />

400<br />

Window<br />

76 www.minib.cz


with a fan<br />

COIL – SK2<br />

HEAT TRANSFER RATE q [W] coil – SK2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

1 2 3<br />

min. speed med. speed max. speed<br />

length L (mm) 900 length L (mm) 900 length L (mm) 900<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 026 1 869 1 807 90 2 131 1 966 1 900 90 2 415 2 227 2 153<br />

80 1 714 1 560 1 500 80 1 802 1 641 1 577 80 2 042 1 859 1 787<br />

70 1 409 1 260 1 202 70 1 482 1 326 1 264 70 1 679 1 502 1 432<br />

50 830 693 639 50 873 729 672 50 989 826 762<br />

length L (mm) 1000 length L (mm) 1000 length L (mm) 1000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 2 364 2 181 2 108 90 2 487 2 294 2 217 90 2 817 2 598 2 512<br />

80 1 999 1 820 1 750 80 2 103 1 915 1 840 80 2 382 2 169 2 085<br />

70 1 644 1 470 1 402 70 1 729 1 547 1 474 70 1 959 1 752 1 670<br />

50 968 808 746 50 1 019 850 784 50 1 154 963 889<br />

length L (mm) 1250 length L (mm) 1250 length L (mm) 1250<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 3 208 2 959 2 861 90 3 375 3 113 3 009 90 3 823 3 526 3 409<br />

80 2 713 2 471 2 374 80 2 854 2 599 2 497 80 3 233 2 944 2 829<br />

70 2 231 1 996 1 902 70 2 347 2 099 2 001 70 2 659 2 378 2 267<br />

50 1 314 1 097 1 012 50 1 382 1 154 1 065 50 1 566 1 307 1 206<br />

length L (mm) 1500 length L (mm) 1500 length L (mm) 1500<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 053 3 738 3 613 90 4 263 3 932 3 801 90 4 829 4 454 4 306<br />

80 3 427 3 121 2 999 80 3 605 3 282 3 155 80 4 084 3 719 3 574<br />

70 2 818 2 521 2 403 70 2 964 2 651 2 528 70 3 358 3 004 2 864<br />

50 1 660 1 386 1 278 50 1 746 1 458 1 345 50 1 978 1 652 1 523<br />

length L (mm) 1750 length L (mm) 1750 length L (mm) 1750<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 4 897 4 517 4 366 90 5 151 4 751 4 592 90 5 835 5 382 5 203<br />

80 4 141 3 771 3 624 80 4 356 3 966 3 812 80 4 935 4 493 4 319<br />

70 3 406 3 046 2 904 70 3 582 3 204 3 054 70 4 058 3 630 3 460<br />

50 2 006 1 675 1 545 50 2 110 1 762 1 625 50 2 390 1 996 1 841<br />

length L (mm) 2000 length L (mm) 2000 length L (mm) 2000<br />

mean air temperature tA mean air temperature tA mean air temperature tA<br />

15 20 22 15 20 22 15 20 22<br />

90 5 741 5 296 5 119 90 6 039 5 570 5 384 90 6 841 6 310 6 100<br />

80 4 855 4 421 4 249 80 5 107 4 650 4 469 80 5 786 5 268 5 063<br />

70 3 993 3 571 3 404 70 4 200 3 756 3 581 70 4 758 4 255 4 057<br />

50 2 352 1 963 1 811 50 2 474 2 065 1 905 50 2 803 2 340 2 158<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

77


COIL - SK PTG, NK PTG<br />

with a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

COIL-NK PTG<br />

HEAT TRANSFER RATE q [W]<br />

coil – SK PTG, NK PTG<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 610 1 503 1 460<br />

80 1 395 1 288 1 245<br />

70 1 108 1 007 967<br />

50 554 475 443<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 2 098 1 958 1 902<br />

80 1 818 1 678 1 622<br />

70 1 447 1 315 1 262<br />

50 734 629 587<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 2 659 2 482 2 411<br />

80 2 304 2 127 2 056<br />

70 1 836 1 669 1 602<br />

50 933 800 747<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 3 132 2 923 2 839<br />

80 2 714 2 505 2 422<br />

70 2 158 1 962 1 884<br />

50 1 083 928 866<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 3 572 3 334 3 239<br />

80 3 096 2 858 2 763<br />

70 2 465 2 241 2 151<br />

50 1 239 1 062 991<br />

COIL-SK PTG<br />

COIL – SK PTG, NK PTG<br />

CHARACTERISTICS<br />

6 self-standing or wall <strong>MINIB</strong> convector with the fan<br />

6 equipped with the thermoelectric generator of el. energy<br />

6 this convector does not require individual el. installation<br />

6 equipped with the thermostatic head<br />

6 heating of dry interiors<br />

DIMENSIONS<br />

total width<br />

construction height – self-standing<br />

construction height – wall<br />

length L<br />

156 mm<br />

300 mm<br />

240 mm<br />

1000 to 2000 mm<br />

USAGE<br />

PTG convector is a fast reacting heating unit equipped with<br />

the thermoelectric generator. There is not needed to install<br />

any cable connection to convectors because el. energy is<br />

generated from the warm water supplied to the heat exchanger<br />

through the PTG system. The aluminium cover of the unit<br />

is supplied with varnished coating in colour tints – silver,<br />

white, light or dark bronze.<br />

CROSS SECTION OF COIL-SK PTG<br />

156<br />

300<br />

CROSS SECTION OF COIL-NK PTG<br />

156<br />

240<br />

78 www.minib.cz


without a fan<br />

COIL – NU1<br />

coil – nu1<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of only 116 mm<br />

6 only for heating of dry environments<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

116 mm<br />

170 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NU1 is a fast reacting heating unit from a new<br />

design series of <strong>MINIB</strong> wall convectors without the fan.<br />

The aluminium cover of the unit can be supplied with<br />

silver, light bronze, dark bronze or white varnished or<br />

eloxal coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3667<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-NU1<br />

116<br />

m<br />

170<br />

HEAT TRANSFER RATE q [W] coil – NU1<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 820 746 717<br />

80 675 605 577<br />

70 537 471 446<br />

50 289 234 213<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 935 851 818<br />

80 769 689 658<br />

70 612 537 508<br />

50 330 267 243<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 222 1 112 1 069<br />

80 1 005 901 860<br />

70 800 702 664<br />

50 431 349 318<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 509 1 373 1 320<br />

80 1 241 1 112 1 062<br />

70 987 867 820<br />

50 532 431 392<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 1 796 1 634 1 570<br />

80 1 477 1 324 1 264<br />

70 1 175 1 032 976<br />

50 634 513 467<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 082 1 895 1 821<br />

80 1 712 1 535 1 465<br />

70 1 363 1 196 1 131<br />

50 735 595 542<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

79


COIL - NU2<br />

without a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3667<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-NU2<br />

116<br />

m<br />

340<br />

coil – nu2<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of only 116 mm<br />

6 only for heating of dry environments<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

116 mm<br />

340 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NU2 is a fast reacting heating unit from a new<br />

design series of <strong>MINIB</strong> self-standing convectors without<br />

the fan. The aluminium cover of the unit can be supplied<br />

with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – NU2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 061 966 928<br />

80 873 782 747<br />

70 695 610 577<br />

50 375 303 276<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 210 1 101 1 058<br />

80 995 892 851<br />

70 792 695 657<br />

50 427 346 315<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 581 1 439 1 383<br />

80 1 300 1 165 1 113<br />

70 1 035 908 859<br />

50 558 452 411<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 952 1 776 1 707<br />

80 1 605 1 439 1 374<br />

70 1 277 1 121 1 061<br />

50 689 558 508<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 2 323 2 114 2 032<br />

80 1 910 1 712 1 635<br />

70 1 520 1 335 1 262<br />

50 820 664 604<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 694 2 452 2 356<br />

80 2 215 1 986 1 896<br />

70 1 763 1 548 1 464<br />

50 951 770 701<br />

80 www.minib.cz


without a fan<br />

COIL – SU1<br />

coil – Su1<br />

CHARACTERISTICS<br />

6 self-standing floor convector with a width of only 116 mm<br />

6 only for heating of dry environments<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

116 mm<br />

230 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector SU1 is a fast reacting heating unit from a new<br />

design series of <strong>MINIB</strong> self-standing convectors without<br />

the fan. The aluminium cover of the unit can be supplied<br />

with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – SU1<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 817 743 714<br />

80 671 601 573<br />

70 533 467 442<br />

50 286 231 210<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 931 846 813<br />

80 764 685 653<br />

70 607 533 504<br />

50 326 264 240<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 216 1 106 1 063<br />

80 999 895 854<br />

70 794 696 658<br />

50 426 345 313<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 502 1 366 1 312<br />

80 1 233 1 105 1 054<br />

70 980 859 813<br />

50 526 425 387<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 1 787 1 625 1 562<br />

80 1 468 1 315 1 255<br />

70 1 166 1 023 967<br />

50 626 506 461<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 073 1 885 1 811<br />

80 1 702 1 525 1 455<br />

70 1 353 1 186 1 121<br />

50 726 587 534<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3764<br />

t W<br />

, A<br />

mean heating water temperature, vzduchu [°C]<br />

Q N<br />

jmenovitý HEAT TRANSFER RATE pro teploty<br />

t W<br />

- t A<br />

= 50 °C [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-SU1<br />

116<br />

230<br />

m<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

81


COIL - SU2<br />

without a fan<br />

coil – Su2<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE<br />

EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3764<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL-SU2<br />

116<br />

m<br />

400<br />

CHARACTERISTICS<br />

6 self-standing floor convector with a width of only 116 mm<br />

6 only for heating of dry environments<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

116 mm<br />

400 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector SU2 is a fast reacting heating unit from a new<br />

design series of <strong>MINIB</strong> self-standing convectors without<br />

the fan. The aluminium cover of the unit can be supplied<br />

with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – SU2<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 044 950 912<br />

80 858 768 733<br />

70 681 598 565<br />

50 366 296 269<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 190 1 082 1 040<br />

80 977 876 836<br />

70 777 681 644<br />

50 417 337 307<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 555 1 414 1 359<br />

80 1 277 1 144 1 092<br />

70 1 015 890 842<br />

50 545 441 401<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 920 1 747 1 678<br />

80 1 577 1 413 1 348<br />

70 1 253 1 099 1 039<br />

50 673 544 495<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 2 286 2 079 1 997<br />

80 1 877 1 681 1 605<br />

70 1 491 1 308 1 237<br />

50 801 648 589<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 651 2 411 2 316<br />

80 2 177 1 950 1 861<br />

70 1 730 1 517 1 434<br />

50 929 751 683<br />

82 www.minib.cz


without a fan<br />

COIL – NP1/4<br />

coil – NP1/4<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of 156 mm<br />

6 only for heating of dry environments<br />

6 high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

170 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NP1/4 is a fast reacting heating unit from a<br />

new design series of <strong>MINIB</strong> wall convectors without the<br />

fan. The aluminium cover of the unit can be supplied<br />

with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W]<br />

coil – NP1/4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 114 1 017 979<br />

80 922 830 793<br />

70 740 652 618<br />

50 407 332 303<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 269 1 159 1 115<br />

80 1 051 946 904<br />

70 843 743 704<br />

50 464 379 346<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 659 1 514 1 458<br />

80 1 373 1 236 1 182<br />

70 1 102 971 920<br />

50 607 495 452<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 2 048 1 870 1 800<br />

80 1 696 1 526 1 459<br />

70 1 360 1 199 1 136<br />

50 749 611 558<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 2 438 2 225 2 142<br />

80 2 018 1 816 1 736<br />

70 1 619 1 427 1 352<br />

50 891 727 664<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 827 2 581 2 484<br />

80 2 340 2 106 2 014<br />

70 1 877 1 655 1 568<br />

50 1 034 843 770<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,32<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – NP1/4<br />

156<br />

m<br />

170<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

83


COIL - NP2/4<br />

without a fan<br />

coil – NP2/4<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,4153<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – NP2/4<br />

156<br />

m<br />

340<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of 156 mm<br />

6 only for heating of dry environments<br />

6 high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

340 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NP2/4 is a fast reacting heating unit from a<br />

new design series of <strong>MINIB</strong> wall convectors without the<br />

fan. The aluminium cover of the unit can be supplied<br />

with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W]<br />

coil – NP2/4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 621 1 470 1 411<br />

80 1 324 1 182 1 127<br />

70 1 045 913 862<br />

50 551 443 402<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 848 1 676 1 609<br />

80 1 509 1 347 1 284<br />

70 1 191 1 041 983<br />

50 628 505 458<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 2 415 2 190 2 102<br />

80 1 972 1 761 1 678<br />

70 1 557 1 360 1 284<br />

50 821 660 599<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 2 981 2 704 2 595<br />

80 2 435 2 174 2 072<br />

70 1 922 1 680 1 585<br />

50 1 014 815 739<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 3 548 3 218 3 089<br />

80 2 898 2 587 2 466<br />

70 2 288 1 999 1 887<br />

50 1 207 970 880<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 4 115 3 732 3 582<br />

80 3 361 3 001 2 860<br />

70 2 653 2 318 2 188<br />

50 1 399 1 125 1 020<br />

84 www.minib.cz


without a fan<br />

COIL – SP0<br />

coil – Sp0<br />

CHARACTERISTICS<br />

6 self-standing convector with a width of 156 mm<br />

6 only for heating of dry environments<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

135 mm<br />

900 to 2000 mm<br />

USAGE<br />

Self-standing convector SP0 is a fast reacting heating unit<br />

from a new design series of <strong>MINIB</strong> self-standing convectors<br />

without the fan. The aluminium cover of the unit can be<br />

supplied with silver, light bronze, dark bronze or white-varnished<br />

coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W]<br />

coil – SP0<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 545 500 482<br />

80 456 412 395<br />

70 370 328 312<br />

50 210 173 159<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 621 570 550<br />

80 520 470 451<br />

70 422 374 356<br />

50 240 198 181<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 812 745 718<br />

80 679 614 589<br />

70 551 489 465<br />

50 313 258 237<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 003 920 887<br />

80 838 759 727<br />

70 680 604 574<br />

50 387 319 293<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 1 193 1 095 1 056<br />

80 998 903 865<br />

70 810 719 683<br />

50 460 380 348<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 384 1 269 1 224<br />

80 1 157 1 047 1 004<br />

70 939 834 792<br />

50 534 440 404<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,2497<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – SP0<br />

156<br />

m<br />

135<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

85


COIL - SP1/4<br />

without a fan<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,277<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – SP1/4<br />

156<br />

m<br />

230<br />

coil – Sp1/4<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> self-standing convector with a width of 156 mm<br />

6 only for heating of dry environments<br />

6 high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

230 mm<br />

900 to 2000 mm<br />

USAGE<br />

Self-standing convector SP1/4 is a fast reacting heating<br />

unit from a new design series of <strong>MINIB</strong> self-standing convectors<br />

without the fan. The aluminium cover of the unit<br />

can be supplied with silver, light bronze, dark bronze or<br />

white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W]<br />

coil – SP1/4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 900 824 794<br />

80 749 677 648<br />

70 605 536 509<br />

50 340 279 256<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 026 939 905<br />

80 854 771 739<br />

70 690 611 580<br />

50 388 318 291<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 1 340 1 227 1 183<br />

80 1 116 1 008 965<br />

70 902 799 758<br />

50 506 416 381<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 1 655 1 515 1 460<br />

80 1 378 1 244 1 192<br />

70 1 114 986 936<br />

50 625 514 470<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 1 969 1 803 1 738<br />

80 1 640 1 481 1 418<br />

70 1 325 1 173 1 114<br />

50 744 611 560<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 284 2 091 2 015<br />

80 1 903 1 718 1 645<br />

70 1 537 1 361 1 292<br />

50 863 709 649<br />

86 www.minib.cz


without a fan<br />

COIL – SP2/4<br />

coil – Sp2/4<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> self-standing convector with a width of 156 mm<br />

6 only for heating of dry environments<br />

6 high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

156 mm<br />

400 mm<br />

900 to 2000 mm<br />

USAGE<br />

Self-standing convector SP2/4 is a fast reacting heating<br />

unit from a new design series of <strong>MINIB</strong> self-standing convectors<br />

without the fan. The aluminium cover of the unit<br />

can be supplied with silver, light bronze, dark bronze or<br />

white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W]<br />

coil – SP2/4<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 595 1 449 1 392<br />

80 1 307 1 169 1 116<br />

70 1 036 907 857<br />

50 552 446 405<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 1 818 1 652 1 586<br />

80 1 490 1 333 1 272<br />

70 1 181 1 034 977<br />

50 630 508 462<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 2 376 2 158 2 073<br />

80 1 947 1 742 1 662<br />

70 1 543 1 352 1 277<br />

50 823 664 603<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 2 934 2 665 2 560<br />

80 2 404 2 151 2 052<br />

70 1 906 1 669 1 577<br />

50 1 016 820 745<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 3 491 3 172 3 046<br />

80 2 861 2 560 2 442<br />

70 2 268 1 986 1 877<br />

50 1 209 976 887<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 4 049 3 678 3 533<br />

80 3 318 2 968 2 832<br />

70 2 630 2 303 2 176<br />

50 1 402 1 132 1 028<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3911<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – SP2/4<br />

156<br />

m<br />

400<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

87


COIL - NW170<br />

without a fan<br />

coil – NW170<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,4173<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – NW170<br />

232<br />

m<br />

170<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of 232 mm<br />

6 only for heating of dry environments<br />

6 very high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

232 mm<br />

170 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NW170 is a fast reacting heating unit that is<br />

a part of a new design series of <strong>MINIB</strong> wall convectors<br />

regarding its heat output and dimensions. The aluminium<br />

cover of the unit can be supplied with silver, light<br />

bronze, dark bronze or white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – NW170<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 878 1 703 1 634<br />

80 1 533 1 369 1 305<br />

70 1 210 1 057 998<br />

50 638 512 465<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 141 1 941 1 863<br />

80 1 748 1 560 1 487<br />

70 1 379 1 205 1 137<br />

50 727 584 530<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 2 797 2 537 2 435<br />

80 2 284 2 039 1 943<br />

70 1 802 1 575 1 486<br />

50 950 763 692<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 3 454 3 132 3 006<br />

80 2 820 2 517 2 399<br />

70 2 225 1 944 1 835<br />

50 1 173 943 855<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 4 111 3 728 3 578<br />

80 3 356 2 996 2 856<br />

70 2 648 2 314 2 184<br />

50 1 396 1 122 1 017<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 4 767 4 323 4 149<br />

80 3 892 3 475 3 312<br />

70 3 072 2 683 2 533<br />

50 1 619 1 301 1 180<br />

88 www.minib.cz


without a fan<br />

COIL – NW340<br />

coil – NW340<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> wall convector with a width of 232 mm<br />

6 only for heating of dry environments<br />

6 very high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

232 mm<br />

340 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector NW340 is a fast reacting heating unit that is<br />

a part of a new design series of <strong>MINIB</strong> wall convectors<br />

regarding its heat output and dimensions. The aluminium<br />

cover of the unit can be supplied with silver, light<br />

bronze, dark bronze or white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – NW340<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 2 254 2 051 1 972<br />

80 1 854 1 662 1 587<br />

70 1 476 1 296 1 226<br />

50 796 645 587<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 569 2 338 2 247<br />

80 2 113 1 894 1 809<br />

70 1 682 1 477 1 397<br />

50 908 735 669<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 3 357 3 055 2 937<br />

80 2 761 2 476 2 364<br />

70 2 198 1 930 1 825<br />

50 1 186 961 875<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 4 145 3 773 3 626<br />

80 3 410 3 057 2 918<br />

70 2 714 2 383 2 254<br />

50 1 465 1 187 1 080<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 4 933 4 490 4 316<br />

80 4 058 3 638 3 473<br />

70 3 230 2 836 2 682<br />

50 1 743 1 412 1 285<br />

length L (mm) 2000<br />

mean air temperature tA<br />

15 20 22<br />

90 5 721 5 207 5 005<br />

80 4 706 4 219 4 028<br />

70 3 746 3 289 3 111<br />

50 2 021 1 638 1 491<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3651<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – NW340<br />

232<br />

m<br />

340<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

89


COIL - SW250<br />

without a fan<br />

coil – SW250<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,4173<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – SW250<br />

232<br />

m<br />

250<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> self-standing convector with a width of 232 mm<br />

6 only for heating of dry environments<br />

6 very high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

232 mm<br />

250 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector SW250 is a fast reacting heating unit that is<br />

a part of a new design series of <strong>MINIB</strong> self-standing convectors<br />

regarding its heat output and dimensions. The<br />

aluminium cover of the unit can be supplied with silver,<br />

light bronze, dark bronze or white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – SW250<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 1 878 1 703 1 634<br />

80 1 533 1 369 1 305<br />

70 1 210 1 057 998<br />

50 638 512 465<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 141 1 941 1 863<br />

80 1 748 1 560 1 487<br />

70 1 379 1 205 1 137<br />

50 727 584 530<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 2 797 2 537 2 435<br />

80 2 284 2 039 1 943<br />

70 1 802 1 575 1 486<br />

50 950 763 692<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 3 454 3 132 3 006<br />

80 2 820 2 517 2 399<br />

70 2 225 1 944 1 835<br />

50 1 173 943 855<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 4 111 3 728 3 578<br />

80 3 356 2 996 2 856<br />

70 2 648 2 314 2 184<br />

50 1 396 1 122 1 017<br />

length L (mm) 2000<br />

mean air temperature tA<br />

mean water<br />

temperature<br />

tW<br />

15 20 22<br />

90 4 767 4 323 4 149<br />

80 3 892 3 475 3 312<br />

70 3 072 2 683 2 533<br />

50 1 619 1 301 1 180<br />

90 www.minib.cz


without a fan<br />

COIL – SW420<br />

coil – SW420<br />

CHARACTERISTICS<br />

6 <strong>MINIB</strong> self-standing convector with a width of 232 mm<br />

6 only for heating of dry environments<br />

6 very high heat output of the convector without the fan<br />

6 equipped with the thermostatic head.<br />

DIMENSIONS<br />

total width<br />

construction height<br />

length L<br />

232 mm<br />

420 mm<br />

900 to 2000 mm<br />

USAGE<br />

Convector SW420 is a fast reacting heating unit that is<br />

a part of a new design series of <strong>MINIB</strong> self-standing convectors<br />

regarding its heat output and dimensions. The<br />

aluminium cover of the unit can be supplied with silver,<br />

light bronze, dark bronze or white-varnished coating.<br />

info:<br />

The decorative grille of the convector must not be loaded.<br />

HEAT TRANSFER RATE q [W] coil – SW420<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

mean water<br />

temperature<br />

tW<br />

length L (mm) 900<br />

mean air temperature tA<br />

15 20 22<br />

90 2 261 2 056 1 976<br />

80 1 857 1 663 1 588<br />

70 1 476 1 295 1 224<br />

50 793 641 583<br />

length L (mm) 1000<br />

mean air temperature tA<br />

15 20 22<br />

90 2 577 2 344 2 252<br />

80 2 117 1 896 1 810<br />

70 1 682 1 476 1 395<br />

50 904 731 665<br />

length L (mm) 1250<br />

mean air temperature tA<br />

15 20 22<br />

90 3 368 3 063 2 943<br />

80 2 766 2 478 2 365<br />

70 2 198 1 928 1 823<br />

50 1 181 955 869<br />

length L (mm) 1500<br />

mean air temperature tA<br />

15 20 22<br />

90 4 158 3 782 3 634<br />

80 3 415 3 059 2 920<br />

70 2 714 2 381 2 251<br />

50 1 458 1 179 1 073<br />

length L (mm) 1750<br />

mean air temperature tA<br />

15 20 22<br />

90 4 949 4 501 4 325<br />

80 4 065 3 641 3 475<br />

70 3 230 2 833 2 679<br />

50 1 735 1 404 1 277<br />

length L (mm) 2000<br />

mean air temperature tA<br />

TEMPERATURE EQUATION<br />

Q = Q N<br />

t<br />

(<br />

w<br />

- t a<br />

50 )<br />

where:<br />

m= temperature exponent 1,3752<br />

t W<br />

, A<br />

mean heating water temperature,<br />

mean air temperature [ºC]<br />

Q N<br />

nominal heat transfer rate for difference<br />

of temperatures tw - tA = 50 ºC [W]<br />

Q heat transfer rate for other temperatures [W]<br />

CROSS SECTION OF COIL – SW420<br />

232<br />

m<br />

420<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

mean water<br />

temperature<br />

tW<br />

15 20 22<br />

90 5 739 5 220 5 016<br />

80 4 714 4 222 4 030<br />

70 3 746 3 286 3 107<br />

50 2 012 1 628 1 480<br />

www.minib.cz<br />

91


Control A1<br />

Control of <strong>MINIB</strong> convectors<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

CHARACTERISTICS<br />

Application of 12 V DC fan motors that the company <strong>MINIB</strong> has<br />

been using for its convectors since the year 2005 brings energy<br />

savings up to 80% compared with normal AC motors.<br />

Along with low energy consumption the control of the DC motor<br />

is also easier and gives improved user comfort. During last<br />

years there was collected a lot of knowledge related to installations,<br />

operation and maintenance of <strong>MINIB</strong> convectors and<br />

their controls. The catalogue for the year 2009 includes a set<br />

of recommended connections of control circuits that actually<br />

cover almost all made installations of <strong>MINIB</strong> convectors. For<br />

specific installations, e.g. very large areas or centrally controlled<br />

systems, the company <strong>MINIB</strong> is able to also provide necessary<br />

technical consultations under advantageous conditions.<br />

DESCRIPTION OF INDIVIDUAL CONTROL SYSTEMS<br />

CONTROL A/A1 - the simplest type of a single speed control system<br />

for dry/wet environments. The thermostat directly switches the<br />

Control A1 (wet interior, on/off)<br />

Max. length of connected convectors is 12 linear metres.<br />

CYKY 2x2.5 (black, brown)<br />

CYKY 2x4 (black, brown)<br />

CYKY 3x1,5 (black, blue, yellow/green)<br />

or<br />

20A TT3<br />

25A TT5<br />

Thermostat with the switching contact<br />

~230V/4A of ind. load<br />

CYKY 2x1.5 (black, brown)<br />

Switchboard<br />

Switching contact of the thermostat must be dimensioned for switching of the<br />

inductive load at voltage of 230 VAC. The minimum switched current by contact is<br />

set with the number of connected transformers and their total rated output power.<br />

(For example: for one transformer TT5, which has the output power 330VA, must<br />

have the contact dimensioned for the current of cca 2A.<br />

CYKY 2x2.5 (black, brown)<br />

CYKY 2x4 (black, brown)<br />

Wire cross-section is selected according<br />

to the allowed voltage loss<br />

current in either the primary or secondary circuit of<br />

the isolating transformer. Any suitable mechanical<br />

thermostat, whose contacts are rated appropriately,<br />

can be used. Thermostat contacts must be sized for<br />

either the maximum current of the secondary winding<br />

of the transformer or must be able to switch the<br />

line voltage 230 VAC/50 Hz and must be sufficiently<br />

protected against the dangerous contact voltage<br />

according to the environment, in which they will be<br />

installed when switching the primary winding of the<br />

isolating transformers.<br />

The control A1 can also be used for convectors with<br />

AC asynchronous motors used in swimming pool applications.<br />

In this case thermostats used for swimming<br />

pools (control A1) must comply with the necessary<br />

standards for coverage of el. units in specified<br />

swimming pool zones, especially if they switch the<br />

supply voltage of the primary winding of the isolating<br />

transformer.<br />

To the main switchboard<br />

The convectors can be connected in<br />

series if the distance from the transformer<br />

is small. The Y-connection<br />

is more suitable when the distance<br />

to the furthest convector exceeds<br />

20m.<br />

Tapping can be made in the electrical<br />

conduit box EMK on the wall or<br />

through WAGO terminals directly under<br />

the convector cover.<br />

Wires of the convector side terminals<br />

can be crossed. Middle terminals<br />

can remain unconnected. If the<br />

middle terminals are linked, there<br />

can be only interconnected the middle<br />

terminals. When the cable with<br />

colours “black“, „black“, „brown“ is<br />

used, use the brown wire for interconnection<br />

of middle terminals of<br />

the convectors.<br />

92 www.minib.cz


Control A<br />

Control A (dry interior, on/off)<br />

The control with the thermostat connected on the secondary circuit side of the safety isolating transformer. The switching contact must<br />

be dimensioned for the highest switched current of the secondary winding of the safety isolating transformer TT1-DC, which can be up<br />

to 8A. Recommended for the simplest control of convectors, especially with AC motors but also with DC motors.<br />

One pole of the thermostat (Com)<br />

is always connected to the terminal<br />

“Com“ of the transformer TT1-DC.<br />

The other contact pole of the<br />

thermostat is connected to one of<br />

terminals Lo, Mi, Hi for low, medium<br />

or high speed.<br />

CYKY 2x1,5<br />

(black, brown)<br />

CYKY 3x1,5 (brown, black, yellow-green)<br />

Thermostat with the 7A switching<br />

contact<br />

TH0343<br />

CYKY 2x1,5 (black, brown)<br />

CYKY 2x1,5 (black, brown)<br />

Switchboard<br />

There can be used convectors with DC and AC motors and also in their combination.<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable when<br />

the distance to the furthest convector exceeds 20m. Tapping can be made in the electrical conduit box EMK on the wall or through<br />

WAGO terminals directly under the convector cover.<br />

Wires of the convector side terminals can be crossed. Middle terminals can remain unconnected. If the middle terminals are linked,<br />

there can be only interconnected the middle terminals. When the cable with colours “black“, „black“, „brown“ is used, use the<br />

brown wire for interconnection of middle terminals of the convectors.<br />

To the main switchboard<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

93


CONTROL B<br />

Control B (dry interior, on/off, programmable thermostat)<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

The control for <strong>MINIB</strong> convectors with the weekly programmable thermostat <strong>MINIB</strong> TH-0108. In the year 2009 DC motors in convectors for<br />

wet interiors are supposed to be used as well so that it will be possible to use this control for convectors designed to wet interiors. Convectors<br />

are equipped with the contact thermal switch TS, which disables fan operation if the heating water temperature is too low. (This<br />

switch must be disconnected if fans are needed for forced ventilation or subcooling in summer periods).<br />

The control with the programmable thermostat for simple control of convectors with DC motors up to the current load of ca. 7A, i.e. length<br />

of convectors is max. 12 linear metres.<br />

Fan speed is set with the jumper<br />

between the pin “Com“ and pins<br />

“Lo“, “Mi“, “Hi“. It is normally recommended<br />

to use the jumper between<br />

“Com – Mi“<br />

CYKY 3 x 1.5 (black, blue, yellow-green)<br />

CYKY 3 x 1.5 (black, black, brown)<br />

Switchboard<br />

If the actuator switching contact of the master system is<br />

used instead of the thermostat, this connection can be<br />

used for centrally controlled heating systems.<br />

CYKY 3 x 1.5 (black, black, brown)<br />

Attention: On this controller JP1 and JP2 must be set for control with active signal, i.e. both pins of the jumper JP2<br />

connected and pins no. 2-3 of the jumper JP1! One pole of the thermal switch is connected from the terminal ~ 12V to<br />

terminal REG, the other remains connected on the fourth terminal of TS. If the system is used for subcooling, the thermal<br />

switch cannot be used and the control signal wire (brown) must be connected directly to terminal REG.<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable<br />

when the distance to the furthest convector exceeds 20 m.<br />

Tapping can be made in the electrical conduit box EMK on the wall or through WAGO terminals directly under the convector<br />

cover.<br />

Wires of the convector side terminals can be crossed. There must be only interconnected middle terminals. If the cable<br />

with colours “black“, „black“, „brown“ is used, use the brown wire for interconnection of middle terminals of the convectors.<br />

To the main switchboard<br />

94 www.minib.cz


CONTROL C<br />

Control C (dry environment, three-speed manual speed selection, programmable thermostat)<br />

This control provides a manual speed selection. The control function is the same as control A, but in addition the manual speed selection<br />

is available. The control allows quick achievement of the set temperature after coming back from the weekend, dynamic response<br />

of the heating system during daily routine operation and quiet operation in night hours.<br />

The control with the programmable thermostat for simple control of convectors with the manual three-level fan speed setting with DC<br />

motors. The maximum current load is 7A, i.e. length of convectors with DC motors is max. 12 linear metres.<br />

CYKY 2x1.5<br />

(black, brown)<br />

Cable to the switchboard<br />

Cable to convectors<br />

CYKY 3 x 1.5 (black, blue, yellow-green)<br />

2 cables to thermostat<br />

2xCYKY 3x1.5<br />

(black, black, brown)<br />

Tapping can be made in the electrical conduit box or directly on<br />

the terminal board of the convector.<br />

Switchboard<br />

Terminal TT1-DC Terminal TH-0023 Terminal TH-0482<br />

Heat (not connected)<br />

Cool (not connected)<br />

The current is set by characteristics of the thermostat switching contact.<br />

CYKY 2 x 1.5 (black, brown)<br />

The variant with the use of only one thermal switch.<br />

CYKY 2 x 1.5 (black, brown)<br />

Heat (not connected)<br />

Cool (not connected)<br />

To the main switchboard<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable<br />

when the distance to the furthest convector exceeds 20m. Tapping can be made in the electrical conduit box EMK<br />

on the wall or through WAGO terminals directly under the convector cover.<br />

www.minib.cz<br />

95


CONTROL D<br />

Control D (dry environment, automatic step speed control, programmable thermostat)<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Control D is the automatic step control suitable for dry and wet environment. This control can be also used for heating modes in winters<br />

and subcooling in summers. Automatic multi-level control with the programmable thermostat for the control of convectors with DC motors.<br />

Maximum current load is 7A. Length of convectors max. 20 linear metres.<br />

Terminals “Com“ and “Mi“ or “Hi“<br />

are always connected through the<br />

jumper. (Voltage 10 -12V AC). Fan<br />

speed is controlled through the<br />

control panel.<br />

CYKY 2x1.5<br />

(black, brown)<br />

CYKY 3 x 1.5 (black, blue, yellow-green)<br />

Thermostat contacts can be used for<br />

the control of other units of the heating<br />

system. Eventually the relay can be<br />

disconnected by breaking wire jumper.<br />

contactless<br />

Variant with the standard thermostat<br />

switching or change over<br />

contact of the thermostat<br />

CYKY 3 x 1.5<br />

(black, black, brown)<br />

Switchboard<br />

Control panel D<br />

Control D also enables to control subcooling of the space, when sufficiently cool water is supplied to the heat exchanger.<br />

If the convector is only used for heating, it is possible to connect the thermal switch TS that will disable the function of<br />

fans when the temperature of heating water is not sufficiently high.<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable<br />

when the distance to the furthest convector exceeds 20m. Tapping can be made in the electrical conduit box EMK<br />

on the wall or through WAGO terminals directly under the convector cover.<br />

Wires of the convector side terminals can be crossed. Middle terminals can remain unconnected. If the middle terminals<br />

are linked, there can be only interconnected the middle terminals. When the cable with colours “black“, „black“, „brown“<br />

is used, use the brown wire for interconnection of middle terminals of the convectors.<br />

To the main switchboard<br />

96 www.minib.cz


CONTROL E1<br />

Control E1 (wet environment, automatic step speed control, programmable thermostat)<br />

Automatic control for convectors used in wet environment. Automatic multi-level control with the programmable thermostat for the<br />

control of convectors with AC motors. Maximum current load is 20A (27A). The length of convectors max. 6m (8m).<br />

CYKY 2x4<br />

(black, brown)<br />

CYKY 3 x 1.5 (black, blue, yellow-green)<br />

contactless<br />

Link cable UTP5 with RJ45 connectors<br />

CYKY 2x1.5 (black, brown)<br />

CYKY 2x1.5 (black, brown)<br />

25A<br />

Switchboard<br />

Control panel E1<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable<br />

when the distance to the furthest convector exceeds 20m. Tapping can be made in the electrical conduit box EMK<br />

on the wall or through WAGO terminals directly under the convector cover.<br />

Regarding the electrical safety the thermostat can be placed in the wet environment because it is powered from batteries<br />

with the total voltage 3V and fan motors use the safe voltage 12V AC. But the thermostat should be installed in the place,<br />

where air humidity does not condensate to prevent batteries from corrosion.<br />

To the main switchboard<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

97


CONTROL E<br />

Control E (dry and wet environment, automatic speed control, programmable thermostat)<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Fully automatic control of convectors with continuous speed control. Automatic continuous control with the programmable thermostat<br />

for the control of convectors with DC motors. Maximum current load is 7A. The length of convectors is max. 12m.<br />

Terminals “Com“ and “Mi“ or “Hi“<br />

are always connected through the<br />

jumper. (Voltage 10 -12V AC). Fan<br />

speed is controlled through the<br />

control panel.<br />

CYKY 3x1.5 (black, black, brown),<br />

brown wire is not connected<br />

CYKY 3 x 1.5 (black, blue, yellow-green)<br />

CYKY 3 x 1.5<br />

(black, black, brown)<br />

Thermostat contacts can be used for<br />

the control of other units of the heating<br />

system. Eventually the relay can be<br />

disconnected by breaking wire jumper.<br />

contactless<br />

Switchboard<br />

Control panel E<br />

Control E does not allow subcooling of the space. A thermal switch TS can be used to disable fan operations.<br />

The convectors can be connected in series if the distance from the transformer is small. The Y-connection is more suitable when the<br />

distance to the furthest convector exceeds 20m. Tapping can be made in the electrical conduit box EMK on the wall or through WAGO<br />

terminals directly under the convector cover.<br />

Wires of the convector side terminals can be crossed. Middle terminals can remain unconnected. If the middle terminals are linked,<br />

there can be only interconnected the middle terminals. When the cable with colours “black“, „black“, „brown“ is used, use the brown<br />

wire for interconnection of middle terminals of the convectors.<br />

The electronic control was developed for the user to increase the heating comfort in the interior and to introduce floor convectors as the device that<br />

is able to react besides the standard modes “on – off“ on outside conditions in more intelligent way. The automatic control includes:<br />

I) electronic contactless <strong>MINIB</strong> thermostat TH-0108 with a weekly program. The user is not disturbed by mechanical switching of contacts.<br />

II) automatic fan speed control. Revolutions are continuously increased or reduced on basis of the programmed algorithm. There can be set three<br />

modes of the automatic operation suitable for a) halls and offices, b) living rooms, c) bedrooms and very quiet areas. In all cases the fan speed<br />

is continuously changed, only maximum noise levels and fan activation times are different for a variety of environment.<br />

III) temperature sensor of the inlet water that will disable a fan operation in case, when the heating water is not heated enough. This prevents the<br />

not sufficiently heated air to be blown out from the convector.<br />

IV) light sensor – photosensor – detecting a presence of light and limiting the maximum fan speed during night hours so that the noise level during<br />

operation of the convector is minimum.<br />

V) user‘s possibility to set the maximum fan speed. The user can set an acceptable maximum noise level according to his own sensitivity, which will<br />

be never exceeded and this level is further reduced to minimum speed during the night.<br />

VI) initial fan calibration of all convectors to the same speed so as to eliminate a loss voltage for distant convectors connected to the common<br />

safety isolating transformer TT1-DC 230/12V.<br />

To the main switchboard<br />

98 www.minib.cz


CONTROL MT2, TE<br />

Control MT-2 (dry and wet environment, automatic speed control and control of warm<br />

air blow direction from the convector)<br />

It is recommended to use the special control MT-2 for MT-2 convectors. These convectors are equipped with their own special electric,<br />

resp. electronic circuits. Control of MT-2 convectors with DC motors and control unit REG<strong>MINIB</strong> through the control systém Reg.<br />

MT2 with the programmable thermostat. The control is made by combination of two logic signals (four-level control). Current load is<br />

max. 10A. Length of convectors is max. 8 linear metres.<br />

Note that it is necessary to follow the orientation of the convector against<br />

the window during the instalation and to secure proper assignment of temperature<br />

sensors of heating water and inlet air.<br />

When four-pipe two-circuit system (heating / cooling) is installed, it is necessary<br />

to consult a solution with <strong>MINIB</strong> technicians!<br />

Control TE (on/off control for electric direct heating convectors, thermostats also switches on<br />

heating spirals)<br />

CYKY 3x1,5 (brown, black, yellow-green)<br />

Power source<br />

150W<br />

Standard data switched Patch cable UTP5<br />

KADO<br />

terminal<br />

KP - KP pomocný - auxiliary stykač contactor<br />

Ovládací cívka Control ~240V/50Hz<br />

coil – Contacts – 240V/50Hz/Imax ohmic load<br />

Kontakty ~240V/50Hz/Imax odporová zátěž<br />

Current Imax is set by the total heat input of all switched units.<br />

Proud Imax je dán celkovým topným příkonem všech spínaných<br />

The contactor can be also a three-phase type, and then the total length of těles. convectors<br />

Stykač can be divided může být into three i třífázový, same sections pak lze and celkovou every section délku can be konvektorů connected to<br />

rozdělit na tři stejné one phase. části The a contactor ktodou coil část can zapojit be powered do from jedné any fáze. phase.<br />

Cívka stykače může být pochopitelně napájena z libovolné fáze.<br />

Switchboard<br />

The supply transformer TT1-DC can be used for the system with one<br />

convector MT2 or more convectors with the total length less than 4 m.<br />

contactless<br />

Control<br />

panel MT2<br />

To the main switchboard<br />

Thermostat contacts must be rated for the<br />

voltage 230V/50Hz and for the current<br />

corresponding to the coil current of the<br />

auxiliary relay or contactor.<br />

KADO<br />

terminal<br />

The main switchboard<br />

The main<br />

circuit breaker<br />

The main<br />

heating<br />

switch<br />

Heating<br />

circuit<br />

breaker<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

99


PHYSICAL CHARACTERISTICS OF <strong>MINIB</strong> CONVECTORS<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

1. Acoustic pressure<br />

Acoustic pressure vs. fan speed<br />

Shown on this page are experimental and calculated values of the acoustic<br />

(COIL-KT-0) Ø 30mm Ø pressure (noise) of <strong>MINIB</strong> convectors. The results were obtained by measuring<br />

3. 3. Water Vodní volume objem of <strong>MINIB</strong> konvektorů convectors, <strong>MINIB</strong>, dm3 dm 3<br />

of selected representative samples of convectors at the distance of 1m from<br />

the measured object at an angle of 45º from the floor. The convectors were<br />

2200min -1<br />

embedded in concrete in an acoustically hard room. When the convector is<br />

installed, e.g. in a living room furnished with furniture and carpet, the resulting<br />

noise level can be considered lower by 1 to 2 dB than the level published<br />

here due to the influence of higher noise absorption of the furnished room. In<br />

1500min -1<br />

addition we note that for the purpose of comparison the noise of a personal<br />

computer in the same room was measured and found to be 40.8 dB.<br />

It results from the charts, which are always shown individually for the specific<br />

1250min -1<br />

group of convectors, that minimum speed 1 and medium speed 2 of the fan<br />

meet standard requirements for daytime (up to 40 dB) and night operation (up<br />

to 30 dB) for all convector lengths in all cases. For these reasons we propose to<br />

Convector length L, mm<br />

project <strong>MINIB</strong> convectors for the speed 2 alias medium fan revolutions. In case<br />

of requirements to minimize noise levels in the room or where a large number<br />

of convectors should be placed, we recommend to project convectors for the<br />

minimum fan speed 1, when the acoustic pressure is almost indistinguishable<br />

from the normal noise background in the interior.<br />

Acoustic pressure vs. fan speed, Ø Ø 50mm<br />

Acoustic pressure vs. fan speed, Ø 50mm Ø 50mm<br />

(COIL-KT/KO, COIL-MT/MO, KT-2/KO-2, HC-4P, MT-2)<br />

(COIL-KT-3, HC, SK-1, NK-2, SK, KP)<br />

1250min -1<br />

1250min -1<br />

850min -1<br />

850min -1<br />

750min -1<br />

750min -1<br />

Convector length L, mm<br />

Convector length L, mm<br />

Acoustic pressure vs. fan speed, Ø 30mm<br />

Acoustic pressure vs. fan speed, Ø 30mm<br />

Ø 30mm<br />

Ø 30mm<br />

(COIL-T50)<br />

(COIL-KT-1)<br />

2200min -1<br />

2200min -1<br />

1500min -1<br />

1500min -1<br />

1250min -1<br />

1250min -1<br />

Convector length L, mm<br />

Convector length L, mm<br />

2. 2. Approximate Orientační airflow vzduchový of <strong>MINIB</strong> convectors, průtok konvektorů m3/hour <strong>MINIB</strong>, m 3 /h<br />

Fan wheel diameter Convector length low speed medium speed max. speed<br />

30 mm 1000 mm 100 120 250<br />

50 mm 1000 mm 200 220 300<br />

Info:<br />

Airflow values listed in the table are valid for convector length of 1000 mm. For other lengths, multiply these unit flows<br />

by the relevant length of the convector in metres (e.g. COIL-KT at a length of 2 500mm has a flow 220 x 2.5 = 550<br />

m3/hour for medium speed).<br />

Average water volume of <strong>MINIB</strong> convectors (two-pipe heat exchangers):<br />

Length of the convector, m 0,9 1,0 1,25 1,5 1,75 2,0 2,5 3,0<br />

Heat exchanger water volume, dm 3 0,6 0,65 0,8 1,0 1,2 1,4 1,8 2,2<br />

100 www.minib.cz


PHYSICAL CHARACTERISTICS OF <strong>MINIB</strong> CONVECTORS AND CONNECTION<br />

4. 4. Pressure Tlakové loses ztráty of <strong>MINIB</strong> konvektorů convectors <strong>MINIB</strong><br />

(including (zahrnující the effect vliv of the šroubení screwed fitting a uzavíracího and manual shut-off kohoutu) valve)<br />

5. Characteristics Charakteristika of the thermostatic termostatické head hlavice<br />

(for <strong>MINIB</strong> (pro konvektory convectors) <strong>MINIB</strong>)<br />

Pressure losses Δp, Pa<br />

L A<br />

6. 6. Characteristics Charakteristika of the screwed regulačního fitting šroubení<br />

(for <strong>MINIB</strong> (pro convectors) konvektory <strong>MINIB</strong>)<br />

Example Příklad of necessary stanovení adjustment potřebného of fittings: nastavení armatury:<br />

Dáno: průtok Q=180 kg/h<br />

Set:<br />

Flow Q = 180 kg/h<br />

Requirement: Požadavek: Setting nastavení for differential pro pressure diferenční Δp = 10 tlak 000pa Dp=10 000Pa<br />

Solution: Řešení: Required Hledané setting nastavení is the intersection je průsečík of values drawn hodnot on axes vynesených of the<br />

flow na and osách pressure průtoku loss. a tlakové ztráty.<br />

The result is the setting of 2.5 turns.<br />

Výsledkem je nastavení o 2,5otáčky.<br />

nastavení setting<br />

(turns) (ot.)<br />

Kv<br />

(m 3 .h -1 )<br />

7. Possible Možné angles úhly and a oblouky curves of <strong>MINIB</strong> konvektorů convectors <strong>MINIB</strong><br />

B<br />

A<br />

0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 5,75<br />

α<br />

Pressure losses of <strong>MINIB</strong> convectors<br />

(for all lengths of heat exchangers)<br />

mass water rate m/kg/h<br />

0 0,9 0,18 0,37 0,54 0,72 0,93 1,13 1,23 1,31 1,35 1,38<br />

L<br />

1. Setting of the minimum temperature, opening of the thermostatic head<br />

2. Setting of the maximum temperature, opening of the thermostatic head<br />

3. Setting of the mean temperature, opening of the thermostatic head<br />

4. Setting of the mean temperature, closing of the thermostatic head<br />

5. Setting of the mean temperature. Pressure difference is 60kPa when the thermostatic<br />

head is closed<br />

Pressure Tlaková ztráta loss Δp, ∆p [Pa]<br />

100000<br />

10000<br />

1000<br />

Průtokový diagram regulačního šroubení, hodnoty Kv<br />

Nastavení [ot.]<br />

1 2<br />

1,5 2,5 3 3,5<br />

10 100 1000<br />

Nastavení<br />

[ot.]<br />

0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 5,75<br />

Kv<br />

[m 3 .h -1 ]<br />

0 0,09 0,18 0,37 0,54 0,72 0,93 1,13 1,23 1,31 1,35 1,38<br />

L<br />

Příklad stanovení potřebného nastavení armatury:<br />

Dáno:<br />

Požadavek:<br />

Řešení:<br />

R<br />

Flow diagram of screwed fitting, Kv values<br />

A<br />

A<br />

Průtok Q=180 kg/h<br />

Nastavení pro diferenční tlak ∆p=10 000 Pa<br />

Hledané nastavení je průsečík hodnot vynesených na osách průtoku a tlakové ztráty.<br />

Výsledkem je nastavení o 2,5 otáčky.<br />

α<br />

Setting [turns]<br />

Flow Průtok Q [kg/h]<br />

L<br />

4<br />

4,5<br />

5<br />

5,5<br />

5,75<br />

B<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

α<br />

B<br />

www.minib.cz<br />

101


EXAMPLES OF CONVECTOR CONNECTIONS<br />

COIL KT0<br />

COIL T50<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

COIL HC 4pipe – from the side<br />

COIL KT – from the side<br />

COIL HC 4pipe – from the front<br />

COIL KT – from the front<br />

102 www.minib.cz


EXAMPLES OF CONVECTOR CONNECTIONS<br />

COIL P – from the side<br />

COIL P – from the front<br />

COIL PT – from the side<br />

COIL PT – from the front<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

www.minib.cz<br />

103


ACCESSORIES<br />

1. Thermostat TH-0023 / control C<br />

(dimensions: 70x30x120mm)<br />

replacement for the thermostat TH 0482<br />

2. Thermostat TH0343 / control A<br />

(dimensions: 74x74x30mm)<br />

3. Thermostat Eberle 524<br />

(IP54), control A1<br />

(dimensions: 90x55x90mm)<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

4. Control panel D, E, E1, MT2<br />

(dimensions: 70x25x70mm)<br />

6. Transformer TT1-DC in the<br />

electric installation box<br />

(box dimensions:<br />

175x70x145mm)<br />

8. Transformer TT3 and TT3-E1 in the electric installation<br />

box<br />

(box dimensions: TT3: 209x165x71mm,<br />

TT3-E1: 255x205x71mm)<br />

10. Reinforcement frame:<br />

It prevents the trough of<br />

the convector from deformation.<br />

It is recommended when<br />

convectors are placed in<br />

hollow floors.<br />

5. Thermostat TH-0108, control B, D, E, E1 and MT-2<br />

(dimensions: 90x30x125mm)<br />

7. Transformer TT5 and TT5-E1 in the electric<br />

installation box<br />

(box dimensions: 255x205x71mm)<br />

9. Examples of colour designs of wall<br />

and self-standing convectors<br />

a) dark bronze, b) light bronze, c) white, d) silver<br />

a) b) c) d)<br />

Note: not included<br />

in the price<br />

of the convector<br />

a place for supporting<br />

104 www.minib.cz


ACCESSORIES<br />

Information for customers:<br />

a) Convectors are supplied as standard with the wooden or aluminium grille<br />

b) In case of the interest in the stainless steel grille, it is necessary to order this grille together with the convector (the profile 10x10mm)<br />

c) Convectors <strong>Coil</strong>-T50 and KT-0 are only supplied with the low aluminium profile of the grille (the profile 8x7mm)<br />

d) Angled corner pieces are produced for all types of floor convectors<br />

e) Curved designs of convectors are produced as standard for COIL-PT, KT and T80(change of width to 254mm) - other types – please consult<br />

11. Examples of decorative frames<br />

standard frame with<br />

the wooden grille<br />

12. Grille materials:<br />

wood:<br />

oak maple beech<br />

aluminium:<br />

dark bronze light bronze silver elox<br />

15. Cross sections of grille partitions:<br />

9<br />

10<br />

except COIL T50<br />

<strong>Coil</strong> T50, KT0<br />

Stainless steel – rolling Al – segment<br />

9 8 14,5 7<br />

<strong>Coil</strong> KT3, KT3105,<br />

HC, T80<br />

Al - segment<br />

7,8<br />

17,8<br />

9 8<br />

16. Antivibration foil<br />

Intensively dampens noise when the convector is placed in hollow<br />

floors and cannot be embedded in concrete<br />

Note: it is not included in the price of the convector<br />

The convector embedded in concrete<br />

standard frame<br />

with the aluminium grille<br />

12,7<br />

18<br />

<strong>Coil</strong> KT2, KO2, MT2, series<br />

PMW, HCM, HCM4p<br />

Al – rolling<br />

9 8<br />

<strong>Coil</strong> T60<br />

Al – segment<br />

7<br />

The convector with antivibration foil placed in the hollow floor<br />

4,3<br />

1,8<br />

1,4<br />

13<br />

7 2,6<br />

13<br />

cover decorative frame<br />

13. Decorative frame and<br />

cover decorative frame<br />

12,5<br />

5,7<br />

4,3<br />

<strong>Coil</strong> KT, PT, P, PO, PO/4, PT/4, P80,<br />

PT80, PT105, PT180, PT300, KO,<br />

KT1, KT110, MT, MO, TE<br />

Al – distant segment<br />

8<br />

1,8<br />

15<br />

13<br />

14. Levelling screw<br />

length 50 mm, thread M8<br />

16,5<br />

<strong>Coil</strong> KT, PT, P, PO, PO/4, PT/4, P80, PT80, PT105,<br />

PT180, PT300, KO, KT1, KT110, MT, MO, KT2, MT2<br />

Wood – distant segment<br />

17,8<br />

9<br />

10<br />

0,6<br />

10<br />

2<br />

18<br />

18<br />

<strong>Coil</strong> KT3, KT3 105, HC, T80<br />

Wood - segment<br />

Wood – rolling: application after<br />

consultation with the trade department<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

fólie<br />

www.minib.cz<br />

105


ASSEMBLY INSTRUCTION MANUALS<br />

Other information and instruction manuals for Minib convectors<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Minib convectors are supplied as standard in lengths of 0.9<br />

to 3m. It is possible to produce other lengths to order.<br />

Non-standard convectors longer than 3m (i.e. a 6m unit)<br />

can be assembled from two 3m units connected with a single<br />

6m walkway grille.<br />

Minib can also produce curved convectors and convectors<br />

joined at various angles.<br />

Technical data<br />

Voltage – 12V via safety isolating transformer<br />

(except wall radiators <strong>Coil</strong>-TE – 230V).<br />

Electrical input power – 5 to 130VA according to the length<br />

and number of fans.<br />

Applications – dry and wet interiors depending on the specification.<br />

Heat exchanger – Al fin/Cu tube construction – fins 0.25mm<br />

and 0.32mm thick – Cu tube diameter 15mm, working pressure<br />

0.6 MPa, test pressure 1.5 MPa<br />

Protection – provided by low safe voltage 12V. Motor protection<br />

IP2X where “ X ” indicates protection by low safe voltage<br />

12V.<br />

Working pressure – 6 bars permanently in the heat exchanger<br />

(0.6 MPa), outlet load tests made with the pressure of<br />

15 bars (1.5 MPa), maximum load of connecting stainless<br />

steel hoses is 1.0 MPa<br />

Heating medium – water; maximum permitted inlet temperature<br />

of heating water is 90°C<br />

Environment for applications – interiors with temperatures<br />

from +5°C to +40°C<br />

Convector mounting<br />

Install so that the heat exchanger is on the side of the unit<br />

furthest from the window or wall.<br />

6 Always connect the heat exchanger to the flow and<br />

return piping using the stainless steel hoses (if not<br />

recommended otherwise), control valve and shut-off<br />

valve supplied with the unit. Connections can be made<br />

straight out or at right angles to the heat exchanger.<br />

6 Convectors must be installed horizontally with the<br />

upper edges of the trough unbuckled. This will ensure<br />

proper seating of the walkway grille and proper venting<br />

of the heat exchanger.<br />

6 Convectors with an ornamental edge cover strip which<br />

should be installed on the level with the floor covering<br />

+/-1mm.<br />

6 Leave the protective top cover on the convector while<br />

performing any concrete work so as to prevent debris<br />

falling inside.<br />

6 Note that this protective cover cannot be walked upon!<br />

6 When pouring concrete ensure that the convector is<br />

secured to the floor using clamping bolts in order to<br />

prevent any vertical movement. It is also possible to<br />

vertically load the convector during concrete pouring<br />

I. Installation of convectors into prepared floors<br />

Dimensions of the existing trench should be as follows:<br />

trench depth = convector height + min. 20mm, trench width<br />

= convector width +min. 20 mm<br />

FLOOR<br />

COVERING<br />

FLOOR<br />

concrete<br />

floor and<br />

convector<br />

foundation<br />

SILICON SEALING<br />

AT THE WOODEN FLOOR WITH SEALING COMPOUND<br />

II. Installation of convectors prior to concreting the floor<br />

6 Concrete the space below the convector so that the finished total<br />

height of the fitted convector equals the final floor height +/-1mm.<br />

6 Set the convector in position by means of the vertical setting bolts.<br />

6 Bolt the convector into the floor using the outer brackets<br />

and bolts.<br />

floor<br />

covering<br />

Thermal<br />

insulation<br />

Floor<br />

concrete<br />

Floor and<br />

convector<br />

foundation<br />

silicon sealing<br />

at the wooden floor with sealing compound<br />

Finishing of installation I and II<br />

6 Connect piping and wiring.<br />

6 Check height, levelness, assembly braces and installation<br />

of ornamental cover strip. The walkway grille can be laid<br />

in as a check.<br />

6 Fit the protective cover over the convector and load and secure<br />

the convector to prevent shifting.<br />

6 Fix and provide noise insulation by pouring a thin layer of concrete<br />

around and under the convector.<br />

6 Embed the convector directly in concrete to achieve the optimum<br />

noise elimination.<br />

6 When the convector is installed into the free space in a wooden<br />

floor without using concrete, it necessary to provide the convector<br />

body with special noise insulation (for additional charge).<br />

6 Lay the floor covering (tiles, carpet).<br />

6 Clean the space between the cover strip and the floor covering<br />

with silicone. When you install the convector into the wooden<br />

floor, it is recommended to fill the space between the convector<br />

and the floor with the cork dilatation tape.<br />

6 The floor convector must be solidly embedded in concrete.<br />

Adjusting bolts are used only for horizontal levelling of<br />

the convector trough. The convector must not stand on these<br />

bolts without being embedded in concrete.<br />

Installation of convectors into hollow floors<br />

6 It is necessary to use reinforcement frames, refer to<br />

the Accessories section, clause 10.<br />

6 It is necessary to use the antivibration foil at convectors with a fan.<br />

Installation procedure I.:<br />

6 set the convector in position by means of vertical adjusting<br />

bolts<br />

6 bolt the convector into the floor using the brackets<br />

Installation of convectors in wet areas<br />

This refers to KO, PO, KO2, MO and HC type units designed with a drain outlet.<br />

Proceed in accordance with the instructions I or II above as well as connecting<br />

the drainpipe at the bottom of the trough to an inclined drain line.<br />

106 www.minib.cz


ASSEMBLY INSTRUCTION MANUALS<br />

Mounting of non-standard convectors longer than 3m<br />

Convectors supplied in more than one section should be installed as<br />

above while paying special attention to the alignment of each. Such units<br />

are equipped with connecting plates, M4 inserts and M4x12mm screws to<br />

join the sections. It is recommended that the continuous walkway grille is<br />

laid down to check the alignment before proceeding with the concrete fill.<br />

Further proceed according to assembly instructions I or II listed above.<br />

Installation of wall mounted and self-standing convectors<br />

6 Measure the total height of the convector.<br />

6 Remove the ornamental cover panels, mark and drill holes<br />

in the wall.<br />

6 Screw the back plate c/w fan and heat exchanger to the wall.<br />

6 Connect water and electrical services.<br />

6 Place the ornamental cover panels over the installed unit.<br />

Control of hot water convectors<br />

Control is possible in two ways:<br />

1. Water side control for convectors with or without fans.<br />

2. Air side control for convectors fitted with fans.<br />

1) The convector’s output can be controlled by regulating either the<br />

temperature or flow rate of the water supplied to it. This can be achieved<br />

by either regulating the boiler temperature or using a thermostatic<br />

valve. The capillary sensor of the thermostatic valve should be positioned<br />

in a suitable position within the heated space. This type of control<br />

is recommended for convectors without fans.<br />

2) It is recommended that convectors fitted with fans are controlled on<br />

the air side by switching the fan on and off. When the fan is switched<br />

on the output of the convector will increase, by approximately 200%. A<br />

thermostat placed in a representative position within the space is used<br />

to switch the fan on and off. Detailed descriptions of possible standard<br />

and “IQ” control systems are given earlier in the catalogue or on internet<br />

site www.minib.cz of the company <strong>MINIB</strong> s.r.o.<br />

Electrical installation and input cable dimensioning<br />

I. Convectors installed in dry areas – fans with 12V DC motors<br />

6 The two wire input cable CYKY to the convectors should be sized<br />

for currents of 10A at 12V regarding the voltage drop.<br />

6 Connecting cables for a branch of convectors to one transformer<br />

should be CYKY 2x2.5mm, and for connections to individual<br />

convectors should be CYKY 2x1.5 mm.<br />

6 If only one convector is connected to the transformer TT1-DC,<br />

use the cable CYKY 2x1.5mm.<br />

6 To determine the maximum length of the convector to be<br />

connected to the power supplies (e.g. TT1-DC), calculate with<br />

the consumption value of 7W per one metre of the convector.<br />

TT1-DC = 96 VA and the length is approx. 13 m. TT3 = 240<br />

VA – approx. 32 m, TT5 = 330VA – approx. 47m.<br />

6 TT1-DC transformers in the electrical installation box should be<br />

mounted in the wall or switchboard as close as possible to the<br />

convectors so as to prevent high voltage drops. Maximum allo<br />

wable voltage drop is 1 to 2V.<br />

6 Dimensions of the electrical installation boxes with transformers<br />

TT1-DC are 145 x 175 x 70 mm.<br />

6 Important: -Layout and installation of convectors fitted with fans<br />

must meet the relevant standards for safe positioning<br />

of all devices (TT1-DC, thermostat etc.).<br />

transformer should be CYKY 2x4mm, and for connections<br />

to individual convectors should be CYKY 2x1.5 mm.<br />

6 If only one convector is connected to the transformer<br />

then the cable should be CYKY 2x2.5mm2.<br />

6 If DC motors for wet areas are used (shaft sealing),<br />

you must calculate with the input power of approx.<br />

14W, and maximum lengths of convectors to be<br />

connected to one power supply are half of the length<br />

in comparison with DC motors. When convectors with<br />

AC motors are used, calculate with the consumption<br />

of approx. 50 VA per one metre of the convector.<br />

6 The TT3 or TT5 transformer in its installation box<br />

should be mounted in the wall or switchboard as close<br />

as possible to the convectors so as to prevent high<br />

voltage drops. Maximum allowable voltage drop<br />

is 1 to 2V.<br />

6 Installation box sizes are as follows:<br />

TT3 165mm x 210mm x 70mm and<br />

TT5 205mm x 255mm x 70mm.<br />

6 Important – Layout and installation of convectors fitted<br />

with fans must meet the relevant standards for safe<br />

positioning of all devices (transformer, thermostat etc.),<br />

on which there is no safe voltage, out of the swimming<br />

pool zone 0, 1 and 2.<br />

6 Convectors for wet areas, especially COIL-KO, MO,<br />

KO-2, COIL-HC equipped with a 12V fan motor and<br />

condense drain are developed and approved for use<br />

in zone 1 of wet areas.<br />

The layout of electrical installation must be made by project<br />

designer with relevant qualification and must be in line with<br />

relevant standards (the list of relevant standards is listed<br />

in the detailed assembly instruction manual). Installation<br />

of electrical devices must be undertaken only by qualified<br />

personnel trained according to local standards with respect<br />

to the project documentation and instructions laid down in<br />

this manual.<br />

Make no other wiring connections at the convectors as these<br />

are protected by the low voltage supply from the transformer.<br />

In wet areas ensure that all drainage lines are non-conducting<br />

and perform all safety checks under local electrical<br />

regulations before putting the system into operation.<br />

Warranty<br />

All Minib s.r.o. products are certified and carry a warranty. The<br />

manufacturer provides for a two-year warranty on all the parts<br />

of the convectors, additionally a ten-year warranty is provided<br />

for the <strong>MINIB</strong> heat exchanger and against rusting-through of<br />

the stainless steel trough. The warranty does not cover damage<br />

caused by incorrect handling or abnormal use. The warranty is<br />

only valid assuming that the stainless steel flexible hoses supplied<br />

with the convectors are used. The standard aluminium or<br />

wooden grille is designed for loads up to 120kg. For more extreme<br />

point loads or highly exposed areas it is recommended<br />

that the more durable stainless steel grille is used (available at<br />

an extra cost).<br />

Minib s.r.o. guarantees that all convectors and parts thereof<br />

are tested, functional and free of defects before leaving<br />

the factory.<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

II. Convectors installed in wet areas – fans with 12V AC motors<br />

6 The two wire input cable CYKY to the convectors should be sized<br />

for currents up to 27 A at 12V regarding the voltage drop (TT5).<br />

6 Connecting cables for a branch of convectors to one<br />

www.minib.cz<br />

107


City Tower<br />

Praha<br />

S & P <strong>Coil</strong> <strong>Products</strong> <strong>Limited</strong><br />

<strong>SPC</strong> House, Evington Valley Road,<br />

LE5 5LU, Leicester, UK<br />

Tel.: +44 (0)116 2490044<br />

Fax: +44 (0)116 2490033<br />

email: spc@spcoils.co.uk<br />

webmail: www.spcoils.co.uk<br />

<strong>MINIB</strong>, s. r. o., Střešovická 49, 162 00 Praha 6 CZ, office@minib.cz tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779<br />

Head office and sales<br />

in the Czech Rep.:<br />

<strong>MINIB</strong> offices:<br />

<strong>MINIB</strong> s r. o.<br />

Střešovická 49<br />

162 00 Praha 6<br />

Czech republic<br />

Tel.: +420 220 180 780<br />

Fax: +420 220 180 779<br />

Email: office@minib.cz<br />

www.minib.com<br />

Mandík a.s.<br />

Hostomice<br />

Family houses<br />

Chateau Dobříš<br />

Jaguar Praha<br />

108 www.minib.cz

Hooray! Your file is uploaded and ready to be published.